2006-03-17 00:00:00 | PROVISO: |
| RESPONSE TO COMMENT #1 DATED 03/02/06: |
| 500 GALLON FUEL TANK WAS REMOVED FROM |
| PLAN SHEET A4.01 AND REPLACED WITH A |
| STORAGE ROOM. THE MECHANICAL PLAN |
| (M2.01) DOES NOT REFLECT THE NEW STORAGE |
| ROOM. |
| |
| RESPONSE TO COMMENT #2:FIRE DAMPERS |
| WERE ADDED TO THE SEPARATION BETWEEN THE |
| GARAGE AND THE DOMESTIC WATER PUMP ROOM |
| (S110).FIRE DAMPERS WERE NOT ADDED TO |
| THE SEPARATION BETWEEN ROOMS S110 & |
| S109.PLAN SHEET A4.01 INDICATES THIS |
| PENETRATION AS HAVING A 1 HOUR RATING |
| (K1 WALL TYPE), ACCORDING TO THE |
| SCHEDULE SHOWN ON PLAN SHEET A9.01. |
| |
| RESPONSE TO COMMENT #3:INSTALLATION OF |
| SHAFT SHALL NOT RESTRICT OR REDUCE THE |
| AMOUNT OF RETURN AIR REQUIRED PER 2004 |
| FMC 918.2. |
| |
| RESPONSE TO COMMENT #4:NOTE #2 ON PLAN |
| SHEET M2.02 INDICATES ALL DRYERS SHALL |
| HAVE A 200 CFM MAXIMUM EXHAUST FAN.PER |
| 2004 FMC 504.5 INSTALLATIONS EXHAUSTING |
| MORE THAN 200 CFM SHALL BE PROVIDED WITH |
| MAKEUP AIR.WHERE A CLOSET IS DESIGNED |
| FOR THE INSTALLATION OF A CLOTHES DRYER, |
| AN OPENING HAVING AN AREA OF NOT LESS |
| THAN 100 SQUARE INCHES, SHALL BE |
| PROVIDED IN THE CLOSET ENCLOSURE. |
| |