Date |
Text |
2006-03-02 00:00:00 | REVIEW CHANGED FROM PASS STATUS TO FAIL |
| STATUS.COMMENTS ARE TO BE ADDRESSED |
| AND PLANS REVISED TO REFLECT CORRECTIONS |
| PRIOR TO PERMIT ISSUANCE. |
2006-02-23 00:00:00 | ****************PROVISO*************** |
| |
| PLEASE NOTE, PROVISO'S TO BE ADDRESSED |
| AND REVISIONS RESUBMITTED WITHIN 30 DAYS |
| OF THE DATE THE PERMIT IS ISSUED. |
| |
| 1.PLAN SHEET A4.01 PLEASE REMOVE THE |
| 500 GALLON FUEL TANK INDICATED IN THE |
| ROOM S105.PER CONVERSATION WITH MATT |
| STILL, THE REMOTE FUEL TANK WAS |
| ELIMINATED. |
| |
| 2.PLAN SHEET M2.01 MAKE UP AIR AND |
| EXHAUST FROM GARAGE THROUGH ROOM S110 TO |
| S109, NO DAMPERS INDICATED. PLAN SHEET |
| A9.01 INDICATES THESE PENETRATIONS AS 2 |
| HR & 1 HR RESPECTIVELY. |
| |
| 3.PLAN SHEET M2.01 PLEASE REMOVE NOTE |
| THAT INDICATES DRYER EXHAUST LOCATED |
| INSIDE R/A PLENUM WILL BE SEALED |
| ENCLOSURE.REPONSE FROM ENGINEER |
| INDICATES THIS IS FOR UNIT 18 ONLY. |
| PLEASE NOTE THIS SHALL BE A RATED |
| ENCLOSURE AS DRYER DUCT CONVEYS |
| COMBUSTIBLES.PLEASE PROVIDE A DETAIL |
| OF RATED ENCLOSURE AND SUBMIT UNDER |
| ALTERNATE MATERAILS & MEDTHODS 2001 FMC |
| 103.7.1. |
| |
| 4.PLAN SHEET M2.02 UNIT 1 ALSO |
| INDICATES DRYER DUCT THROUGH A PLENUM. |
| PLEASE ALSO CORRECT NOTE #2. |
| |
| 5.PLAN SHEET M2.03, 16" X 10" DUCT |
| THROUGH THE WALL AT THE ENTRANCE FROM |
| THE GARAGE, A FIRE DAMPER IS NOT |
| INDICATED AT THIS LOCATION.DRYER DUCT |
| RUNNING THROUGH RETURN AIR PLENUM UNIT 5 |
| & UNIT 8. |
| |
| 6.PLAN SHEET M2.05 SUPPLY DUCT FROM |
| MECHANICAL ROOM (HPU-P1-5), FIRE DAMPER |
| REQUIRED.ALSO DUCT INTO FIRE CONTROL |
| ROOM SHALL COMPLY WITH 2001 FMC 607.1.3 |
| ITEM #3 OR FIRE DAMPER WILL BE REQUIRED. |
| PLEASE ANNOTATE IN THE SEQUENCE OF |
| OPERATION HOW THIS UNIT WILL BE |
| UTILIZED.ACCESS DOOR REQUIRED FOR |
| MOTORIZED DAMPERS FOR SERVICE OR |
| REPLACEMENT PER 2001 FMC 306.1. |
| |
| 7.PLAN SHEET M2.07 THE MAKE-UP AIR & |
| EXHAUST FROM THE ELECTRICAL METER ROOM. |
| FIRE DAMPERS ARE NOT INDICATED ON THESE |
| PENETRATIONS. |
| |
| 8.PLAN SHEET M2.08 FIRE DAMPER |
| REQUIRED IN THE TRANSFER GRILLE BETWEEN |
| THE ENRY AREA & THE STORAGE AREA. |
| SUPPLY DUCT SHALL COMPLY WITH 2001 FMC |
| 607.1.3. |
| |
| 9.PLAN SHEET M2.09 8" X 8" TRANSFER |
| DUCT HAS DAMPERS INDICATED BUT DOES NOT |
| SPECIFY FIRE DAMPER OR FIRE/SMOKE |
| DAMPER. |
| |
| 10. PLAN SHEET M2.11 6" X 4" DUCT INTO |
| TENANT STORAGE (BY STAIR #6), SHALL |
| COMPLY WITH 2001 FMC 607.1.3 OR A FIRE |
| DAMPER WILL BE REQUIRED. |
| |
| 11. PLAN SHEET M2.12 TRANSFER GRILLE & |
| 38" X 16" DUCT PENETRATING THE WALL |
| BETWEEN THE TENANT STORAGE & STORAGE RM |
| A FIRE DAMPER IS REQUIRED.THE 4" X 4" |
| SUPPLY DUCT THROUGH THE SAME PENETRATION |
| SHALL COMPLY WITH 2001 FMC 607.1.3. |
| |
| 12. PLAN SHEET M2.13 EXHAUST DUCT |
| THROUGH RETURN AIR PLENUM.PER 2001 FMC |
| 601.3, EXHAUST DUCTS SHALL NOT EXTEND |
| INTO OR PASS THROUGH PLENUMS. |
| |
| 13. PLAN SHEET M2.15 TRANSFER GRILLE |
| INTO ROOM S121 (TENANT STORAGE) IS |
| REQUIRED TO HAVE A FIRE DAMPER.SUPPLY |
| DUCT SHALL HAVE NO OPENINGS A MINIMUM OF |
| 5 FT FROM RATED WALL, 2001 FMC 607.1.3. |
| |
| 14. PLAN SHEET M2.16, SUPPLY DUCT FROM |
| HPU-P-4-3 PENETRATES 2 RATED OPENINGS. |
| FIRE DAMPERS REQUIRED. |
| |
| 15. PLAN SHEET M2.19 THE PARTITION |
| BETWEEN ROOM L114 & THE BATHROOMS |
| INDICATE A RATED PENETRATION.ALL DUCTS |
| THAT PENETRATE THIS PARTITION IS |
| REQUIRED TO HAVE A FIRE DAMPER. |
| |
| 16. PLAN SHEET M2.20 O.A. DUCT INTO |
| RESTROOMS PENETRATES RATED CORRIDOR WALL |
| WITH NO FIRE DAMPER INDICATED.PLESAE |
| ALSO PROVIDE SEQUENCE OF OPERATION FOR |
| THIS SYSTEM. |
| |
| 17. PLAN SHEET M2.27 UNIT M, PLAN SHEET |
| M2.29 UNIT B4, & M2.32 UNIT N INDICATES |
| EXHAUSTDUCT IN RETURN AIR PLENUM. |
| PLEASE REVISE. |
| |
| 18. PLEASE NOTE, PLAN SHEET M5.01 IS |
| MISSING FROM ONE SET OF PLANS. |
| IF YOU HAVE ANY QUESTIONS, PLEASE |
| CONTACT PATTY KRAUSS AT (561)805-6719. |