Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop M
Sequence Number 6
Notes
Date Text
2006-03-02 00:00:00REVIEW CHANGED FROM PASS STATUS TO FAIL
 STATUS.COMMENTS ARE TO BE ADDRESSED
 AND PLANS REVISED TO REFLECT CORRECTIONS
 PRIOR TO PERMIT ISSUANCE.
2006-02-23 00:00:00****************PROVISO***************
  
 PLEASE NOTE, PROVISO'S TO BE ADDRESSED
 AND REVISIONS RESUBMITTED WITHIN 30 DAYS
 OF THE DATE THE PERMIT IS ISSUED.
  
 1.PLAN SHEET A4.01 PLEASE REMOVE THE
 500 GALLON FUEL TANK INDICATED IN THE
 ROOM S105.PER CONVERSATION WITH MATT
 STILL, THE REMOTE FUEL TANK WAS
 ELIMINATED.
  
 2.PLAN SHEET M2.01 MAKE UP AIR AND
 EXHAUST FROM GARAGE THROUGH ROOM S110 TO
 S109, NO DAMPERS INDICATED. PLAN SHEET
 A9.01 INDICATES THESE PENETRATIONS AS 2
 HR & 1 HR RESPECTIVELY.
  
 3.PLAN SHEET M2.01 PLEASE REMOVE NOTE
 THAT INDICATES DRYER EXHAUST LOCATED
 INSIDE R/A PLENUM WILL BE SEALED
 ENCLOSURE.REPONSE FROM ENGINEER
 INDICATES THIS IS FOR UNIT 18 ONLY.
 PLEASE NOTE THIS SHALL BE A RATED
 ENCLOSURE AS DRYER DUCT CONVEYS
 COMBUSTIBLES.PLEASE PROVIDE A DETAIL
 OF RATED ENCLOSURE AND SUBMIT UNDER
 ALTERNATE MATERAILS & MEDTHODS 2001 FMC
 103.7.1.
  
 4.PLAN SHEET M2.02 UNIT 1 ALSO
 INDICATES DRYER DUCT THROUGH A PLENUM.
 PLEASE ALSO CORRECT NOTE #2.
  
 5.PLAN SHEET M2.03, 16" X 10" DUCT
 THROUGH THE WALL AT THE ENTRANCE FROM
 THE GARAGE, A FIRE DAMPER IS NOT
 INDICATED AT THIS LOCATION.DRYER DUCT
 RUNNING THROUGH RETURN AIR PLENUM UNIT 5
 & UNIT 8.
  
 6.PLAN SHEET M2.05 SUPPLY DUCT FROM
 MECHANICAL ROOM (HPU-P1-5), FIRE DAMPER
 REQUIRED.ALSO DUCT INTO FIRE CONTROL
 ROOM SHALL COMPLY WITH 2001 FMC 607.1.3
 ITEM #3 OR FIRE DAMPER WILL BE REQUIRED.
 PLEASE ANNOTATE IN THE SEQUENCE OF
 OPERATION HOW THIS UNIT WILL BE
 UTILIZED.ACCESS DOOR REQUIRED FOR
 MOTORIZED DAMPERS FOR SERVICE OR
 REPLACEMENT PER 2001 FMC 306.1.
  
 7.PLAN SHEET M2.07 THE MAKE-UP AIR &
 EXHAUST FROM THE ELECTRICAL METER ROOM.
 FIRE DAMPERS ARE NOT INDICATED ON THESE
 PENETRATIONS.
  
 8.PLAN SHEET M2.08 FIRE DAMPER
 REQUIRED IN THE TRANSFER GRILLE BETWEEN
 THE ENRY AREA & THE STORAGE AREA.
 SUPPLY DUCT SHALL COMPLY WITH 2001 FMC
 607.1.3.
  
 9.PLAN SHEET M2.09 8" X 8" TRANSFER
 DUCT HAS DAMPERS INDICATED BUT DOES NOT
 SPECIFY FIRE DAMPER OR FIRE/SMOKE
 DAMPER.
  
 10. PLAN SHEET M2.11 6" X 4" DUCT INTO
 TENANT STORAGE (BY STAIR #6), SHALL
 COMPLY WITH 2001 FMC 607.1.3 OR A FIRE
 DAMPER WILL BE REQUIRED.
  
 11. PLAN SHEET M2.12 TRANSFER GRILLE &
 38" X 16" DUCT PENETRATING THE WALL
 BETWEEN THE TENANT STORAGE & STORAGE RM
 A FIRE DAMPER IS REQUIRED.THE 4" X 4"
 SUPPLY DUCT THROUGH THE SAME PENETRATION
 SHALL COMPLY WITH 2001 FMC 607.1.3.
  
 12. PLAN SHEET M2.13 EXHAUST DUCT
 THROUGH RETURN AIR PLENUM.PER 2001 FMC
 601.3, EXHAUST DUCTS SHALL NOT EXTEND
 INTO OR PASS THROUGH PLENUMS.
  
 13. PLAN SHEET M2.15 TRANSFER GRILLE
 INTO ROOM S121 (TENANT STORAGE) IS
 REQUIRED TO HAVE A FIRE DAMPER.SUPPLY
 DUCT SHALL HAVE NO OPENINGS A MINIMUM OF
 5 FT FROM RATED WALL, 2001 FMC 607.1.3.
  
 14. PLAN SHEET M2.16, SUPPLY DUCT FROM
 HPU-P-4-3 PENETRATES 2 RATED OPENINGS.
 FIRE DAMPERS REQUIRED.
  
 15. PLAN SHEET M2.19 THE PARTITION
 BETWEEN ROOM L114 & THE BATHROOMS
 INDICATE A RATED PENETRATION.ALL DUCTS
 THAT PENETRATE THIS PARTITION IS
 REQUIRED TO HAVE A FIRE DAMPER.
  
 16. PLAN SHEET M2.20 O.A. DUCT INTO
 RESTROOMS PENETRATES RATED CORRIDOR WALL
 WITH NO FIRE DAMPER INDICATED.PLESAE
 ALSO PROVIDE SEQUENCE OF OPERATION FOR
 THIS SYSTEM.
  
 17. PLAN SHEET M2.27 UNIT M, PLAN SHEET
 M2.29 UNIT B4, & M2.32 UNIT N INDICATES
 EXHAUSTDUCT IN RETURN AIR PLENUM.
 PLEASE REVISE.
  
 18. PLEASE NOTE, PLAN SHEET M5.01 IS
 MISSING FROM ONE SET OF PLANS.
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.