Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop P
Sequence Number 5
Notes
Date Text
2006-03-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW: (FROM 1ST REVIEW)
  
 12) SHT A4.41 KITCHEN SINK AND JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND. - THIS WILL BE A FIELD
 INSPECTOR APPROVAL. IF COMMON USE AREA
 IS AVAILABLE TO TENANTS AND SUESTS, ALL
 REQUIREMENTS OF SECTION 11-4.24 WILL BE
 ADHERED TO. - DETAIL SUBMITTED IS FOR
 THE DWELLING UNITS. SINKS INDICATED
 SHALL COMPLY AS REQUIRED IN SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.24.2 HEIGHT, 11-4.24.3 KNEE
 CLEARANCE, 11-4.24.4 SINK DEPTH,
 11-4.24.5 CLEAR FLOOR SPACE, (FORWARD
 APPROACH), 11-4.24.6 EXPOSED PIPES AND
 SURFACES, AND 11-4.24.7 FAUCETS.
  
 NEW COMMENTS GENERATED FROM CHANGES TO
 PLANS. 4/A:
 1-4A. SHEET P2.37 MISSING FROM ONE SET
 OF PLANS.
 2-4A. NEW SEAL REQUIRED FOR ENGINEER
 EFFECTIVE 1-1-06. SEE ATTACHED SHEET
 FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
 3-4A. SHT P2.04, CHANGE 4.1 CONDENSATE
 DRAIN PIPING SHOWS EXTRA LINES TO UNITS
 11 AND 12. PLEASE CLARIFY. SECTION
 104.2.1.
 4-4A. SHT P2.05 CHANGE 5.3 CONDENSATE
 DRAIN FOR A/C UNIT P1-5 NOT SHOWN ON SHT
 P2.61 AS NOTED. PLEASE CLARIFY. SECTION
 104.2.1.
 5-4A. SHT P2-06 CHANGE 6.4 PLEASE
 INDICATE WHAT IS DRAINING INTO THE 3" FD
 CONNECTED TO RWL'S 7 & 8.
 6-4A. SHT P2.06 CHANGE 6.4 CONDENSATE
 DRAIN 28A DOES NOT CONNECT TO RISER C14,
 15, 16, 24 & 26. RISER SHOWS 24A & 26A
 CONNECTING TO THIS RISER. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER
 SHOWN IS NOT SHOWN ON THE GROUND FLOOR.
 WHERE DOES THIS RISER TERMINATE? PLEASE
 CLARIFY. SECTION 104.2.1.
 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO
 RISER 10 DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
 9-4A. SHT P2.26 CHANGE 24.1 HORIZONTAL
 BRANCH SHALL NOT CONNECT WITHIN THE
 HORIZONTAL STACK OFFSET OR WITH 2 FEET
 ABOVE OR BELOW SUCH OFFSET. SECTION
 711.2
 10-4A. SHT P2.27 CHANGE 25.1 NOT ALL
 VENT PIPING IS SHOWN ON THE FLOOR PLAN.
 SECTION 104.2.1.
 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT
 SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 12-4A. SHT P2.36 CHANGE 32.1 VENTING NOT
 SHOWN FOR BATH #2. SECTION 104.2.1.
 13-4A. SHT 2.44 CHANGE 37.3 UNIT P2
 PIPING DOES NOT REFLECT RISER 59. NO
 VENT CONNECTION FROM W/M TO L/SK AND
 FLOOR PLAN SHOWS THE RISER BEHIND THE
 LAUNDRY SINK. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING
 LAYOUT DOES NOT REFLECT RISERS 10A, 11,
 11A AND 12 AS INDICATED. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION
 104.2.1.
 15-4A. SHT P2.45 CHANGE 38.3 NOT ALL
 VENT PIPING WAS ADDED TO REFLECT THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
 16-4A. SHT P2.61 CHANGE 47.1 STORM
 RISERS6, 7 & 8, 9 & 10, AND DOWNSTREAM
 OF 4 & 5 SHOW 3" FLOOR DRAINS. PLEASE
 INDICATE WHAT IS DRAINING INTO THESE
 FD'S. SECTION 104.2.1.
 17-4A. SHT P2.61 CHANGE 47.1 STORM
 PIPING DOWNSTREAM OF WHERE RWL 1 & RWL
 11 TIE TOGETHER SHALL BE 12". 10" SHOWN.
 DOWNSTREAM OF THAT THE STORM DRAIN SHOWS
 16" PIPE BUT IS SHOWN AS 15" ON THE
 RISER DIAGRAM. PLEASE CORRELATE. SECTION
 104.2.1.
 18-4A. SHT P2.61 CHANGE 47.1 CONDENSATE
 LINE LEFT OF RWL 1, PLEASE INDICATE WHAT
 RISERS ARE BEING PICKED UP BY THE 3
 LINES. NO INDICATION OF WHAT IS
 CONNECTING TO THESE LINES. PLEASE
 CLARIFY. SECTION 104.2.1.
 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS
 REQUIRED ON RISER 54A AT THE 5TH FLOOR
 OFFSET. SECTIONS 915.2 & 915.3.
 20-4A. SHT P3.22 NEW SHEET RISERS 28 &
 84 LAV FOR 6TH FLOOR MISSING AND THE W/M
 IS ON THE WRONG STACK. CORRELATE RISER
 AND FLOOR PLAN. SECTION 104.2.1.
 21-4A. SHT P3.24 VENT PIPING DOES NOT
 REFLECT THE ROOF VENT LAYOUTS. VENTING
 ALSO INDICATE "TO 31" WHEN THE VENTS ARE
 COMMING FROM 31. SUBMIT A RISER
 ISOMETRIC DIAGRAM FOR THE VENT PIPING
 SHOWING ALL PIPE SIZES, TOTAL DEVELOPED
 LENGTH AND INDICATE FIXTURE UNITS AS
 THEY ACCUMULATE IN THE VENT SYSTEM.
 TABLE 916.1
 22-4A. SHT P3.26 CHANGE 64.1 WATER
 CLOSET IS NOT VENTED AS CHANGED. SECTION
 901.2.1.
 23-4A. SHT P3.28 CHANGE 66.2SANITARY
 RISER 12 THRU 17 AND 51 DOES NOT REFLECT
 THE FLOOR PLAN WHERE IT CONNECTS TO THE
 BUILDING DRAIN. PLEASE CORRELATE RISER
 AND FLOOR PLAN, AND RECHECK THE FIXTURE
 UNITS AND PIPE SIZE. SECTION 104.2.1.
 24-4A. SHT P3.28 CHANGE 66.5 A
 HORIZONTAL BRANCH SHALL NOT CONNECT
 WITHIN THE HORIZONTAL STACK OFFSET.
 SECTION 711.2.
 25-4A. SHT P3.29 CHANGE 67.1 TABLE
 710.1(1) 1/8"/FT SLOPE REQUIRED.
 INDICATE ON PLANS. (ALSO SEE SHT P3.28
 10 @ 2559FU).
 26-4A. SHT P3.29 CHANGE 67.2 DOES NOT
 CONNECT TO THE BUILDING DRAIN IN THE
 CORRECT LOCATION. CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
 27-4A. SHT P3.30 CHANGE 68.1 INDICATE
 SLOPE OF PIPE (1/8"/FT) FOR WHERE
 REQUIRED. TABLE 710.1(1).
 28-4A. SHT P3.31 CHANGE 69.1 SHOW SLOPE
 AS 1/8"/FT WHERE REQUIRED. TABLE
 710.1(1).
 29-4A. SHT P3.31 RISER 54 5TH FLOOR W/M
 MISSING. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 104.2.1.
 30-4A. SHT P3.32 CHANGE 70.1 INDICATE
 SLOPE AT 1/8"/FT AS REQUIRED PER TABLE
 710.1(1).
 31-4A. SHT P3.33 CHANGE 7.1 FIXTURE UNIT
 COUNT AT 8" TO READ 1407FU, NOT 140FU AS
 SHOWN. SECTION 104.2.1.
 32-4A. SHT PP3.34 CHANGE 72.1 PIPE SIZE
 DOWNSTREAM OF RISERS 39/75 TO BE 5"
 203FU OR INDICATE AS 1/4"/FT SLOPE PER
 TABLE 710.1(1).
 33-4A. SHT P3.36 CHANGE 74.1 SHOW SLOPE
 OF PIPE IN BLDG DRAIN AS 1/8"/FT WHERE
 REQUIRED PER TABLE 710.1(1).
 34-4A. SHT P3.36 BRANCH LINE DOWNSTREAM
 OF RISER 37 IS 291FU 5" IS REQUIRED.
 ALSO SEE BASE OF STACK. TABLE 710.1(1).
 - THE SIZE OF THE DRAINAGE PIPING SHALL
 NOT BE REDUCED IN SIZE IN THE DIRECTION
 OF FLOW. SEE DOWNSTREAM OF RISER 37 AND
 WHERE RISERS CONNECT TO THE BLDG DRAIN.
 SECTION 704.2.
 35-4A. SHT P3.36 CHANGE 74.2 RISER 71
 DOES NOT CONNECT TO RISER 33. PLEASE
 CLARIFY. SECTION 104.2.1.
 36-4A. SHT P3.36 CHANGE 74.3 RISER 33 IS
 NOT SHOWN ON THIS SHEET. IT SHOULD BE
 INDICATED THAT THE VENT FROM THE EWC AND
 THE SINK CONNECT TO RISER 33. SECTION
 104.2.1.
 37-4A. SHT P3.37 CHANGE 75.1 PLEASE
 CORRECT PIPE SIZE AND SQUARE FOOTAGE FOR
 PIPE PRIOR TO AND AFTER RISERS RW1 AND
 RW11 CONNECT. SECTION 104.2.1. AND TABLE
 1106.3.
 38-4A SHT P3.37 CHANGE 75.2 RISER STATES
 "SEE P2.02 FOR CONT.", BUT NO PIPING
 SHOWN ON P2.02. PLEASE CLARIFY. SECTION
 104.2.1.
 39-4A SHT P3.40 CHANGE 78.1 SHOWS 1/4"
 CONDENSATE LINE. SHALL BE 1-1/4" AS
 SHOWN UPSTREAM.
 40-4A SHT P3.41 CHANGE 79.1 SHOWS 1"
 CONDENSATE LINE. SHEE BE 1-1/2" AS SHOWN
 UPSTREAM.
  
 NEW COMMENTS:
  
 1-E. SHT P3.21 RISER 26 DOES NOT REFLECT
 THE FLOOR PLAN. NO DRAINAGE LINE FROM
 KITCHEN SINK AND W/M SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 104.2.1.
 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN
 SHALL NOT TERMINATE IN THE PARKING
 GARAGE. SECTION 504.8.2. - EXPLAIN HOW
 DRAINING THE PTR DISCHARGE LINE INTO THE
 GARAGE PARKING MEETS THE REQUIREMENT FOR
 A SAFE DISCHARGE. SECTION 604.7.1
 3-E SHT P2.40 (NEW SHEET) NO DRAINAGE
 SHOWN FOR THE W/M, L/SINK, OR KITCHEN
 SINK. PLEASE CORRELATE WITH RISER
 DIAGRAM. SECTION 104.2.1.
 4-E SHTS P2.59 AND P2.60 PLEASE SHOW
 TOTAL DEVELOPED LENGTH AND TOTAL FIXTURE
 UNITS FOR COMBINED VENTS 31 THRU 45, 46
 THRU 50, 65 & 78. INDICATE ALL VENT PIPE
 SIZES. TABLE 916.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS