2006-01-05 00:00:00 | **************************************** |
| PLEASE SEE THE FOLLOWING WILL BE SET UP |
| AS A "PROVISO" WHICH WILL REQUIRE SOME |
| SHEETS TO BE REVISED "BEFORE ANY ROUGH |
| ELECTRICAL INSPECTION" OR 6 MONTHS WHICH |
| EVER COMES FIRST. |
| THESE ITEMS HAVE ALSO BEEN REDLINED ON |
| PLANS. |
| ITEMS FROM PREVIOUS REVIEWS AND |
| INFORMATION TO BE FORTH COMING. |
| |
| |
| ********** PROVISO/REVISION *********** |
| |
| 1)NOTE: PLEASE SEE MISSING RECEPTS IN |
| UNITS |
| "A", "G","D","HD". 210.52 |
| REDLINED |
| |
| 2)NOTE:PLEASE SEE SOME AREAS LABLED AS |
| "FOYER CONTAIN RECEPTS ON SMALL |
| APPLIANCE CIRCUITS. SEE 210.52B1 UNIT |
| G-1,E-1, VV1 |
| REDLINED. |
| |
| 3)NOTE:PLEASE SEE THE FOLLOWING UNITS |
| WHICH SMOKE DETECTORS ARE STILL SHOWN ON |
| MORE THAN ONE CIRCUIT. SEE UNIT #4, C-1 |
| REDLINED. |
| |
| 4)NOTE: PLEASE SEE UNIT "S" DINING RM |
| DESIGNATION REMOVED. |
| REDLINED |
| |
| 5)NOTE: PLEASE SEE SHEET 7.09 DOES NOT |
| CONTAIN THE FEEDER SCHEDULE FOR THE 225A |
| PANEL "N", THIS WAS REVISED ON 7.08. |
| REDLINED. |
| |
| 6)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| UNIT "D-2" WAS SUBMITTED, HOWEVER |
| CIRCUIT #15 FOR SD'S DOES NOT INDICATE |
| THE REQUIRED ARC FAULT PROTECTION NOTE. |
| REDLINED ON PANEL SCHEDULE, UNIT.210.12 |
| |
| 7)NOTE:POOL AREA LIGHTING TO MEET MIN |
| CLEARENCES PER 680.22 AND 411.4 |
| SOME FIXTURES SHOWN CLOSER THAN |
| PERMITTED. |
| REDLINED. |
| |
| 8)NOTE:PLEASE SEE LS101 7.8.1.3 (1) |
| WHICH REQUIRES A MIN OF 10FT |
| CANDLES(108LUX) IN STAIR TOWERS. THIS |
| LEVEL OF LIGHTING IS REQUIRED ON THE |
| WALKING SURFACES DURING NOMRAL POWER |
| CONDITIONS.(1FT CANDLE IN EMERGENCY |
| CONDITIONS. PHOTO-METRICS WILL BE |
| REQUIRED OF STAIR- |
| TOWERS. |
| |
| PLEASE SEE LS101 7.9.2.2 WHICH MENTIONS |
| IN THE EVENT OF THE TRIPPING OF ANY |
| SINGLE MEANS OF OCP WSHOULD NOT LEAVE |
| ANY EGRESS AREA IN TOTAL DARKNESS. |
| PLEASE ALSO SEE A MIN OF SOME SORT OF |
| BATTERY BACK UP FIXTURE FOR CORRIDOR'S |
| AND PARKING GARAGE WILL BE REQUIRD TO |
| PROVIDE MEANS OF EGRESS AT A LIGHTING |
| LEVEL OF 1FT CANDLE. |
| |
| 9)NOTE: PLEASE SEE 230.95,707.7D,700.26 |
| ETC. |
| PLEASE SEE A 4-POLE ATS WILL BE |
| REQUIRED. |
| PLEASE KNOW, THE GFP IS NOT REQUIRED ON |
| THE EMERGENCY/ GENERATOR SIDE OF THE EM |
| DISTRIBUTION SYSTEM, HOWEVER PLEASE SEE |
| THE ABOVE REFERENCES WHICH DO REQUIRE GF |
| SENSING. PLEASE SEE THE FOLLOWING IS |
| TAKEN DIRECTLY FROM ASCO DOCUMENTS |
| FORWARD TO ME. |
| "WHERE GROUND FAULTPROTECTION IS |
| TRIGGERED BY THE CODE AND AN ALTERNATE |
| POWER SUPPLY IS INCLUDED,SWITCHING OF |
| THE NEUTRAL BECOMES NECESSARY.THE |
| SERVICE IS LARGER THAN 1,000 AMPS. |
| CONSEQUENTLY, GROUNDFAULT PROTECTION |
| IS REQUIRED AT THE MAIN SERVICE |
| DISCONNECT AT A MINIMUM. IF ITIS |
| INSTALLED THERE AND THE GENERATOR |
| NEUTRAL GROUNDING WAS THROUGH A SOLID |
| CONNECTION TO THE MAIN SERVICE NEUTRAL, |
| A GROUND FAULT WHEN THE GENERATOR IS |
| FEEDING THE LOAD WILL CAUSE THE MAIN |
| SERVICE DISCONNECT TO OPEN. THIS WILL |
| NOTDISCONNECT THE ARCING FAULT FROM |
| THE GENERATOR. COORDINATION IS THUS |
| LOST." |
| PLEASE KNOW, IF THE MAIN IS IN THE |
| OPENING POSITION WHEN POWERM COMES BACK |
| ON, THE SENSING OF THE FPL WOULD CAUSE |
| THE ATS TO SWITCH BACK, HOWEVER THERE |
| WOULD NOT BE ANY POWER THROUGH THE |
| ELECTRICAL SYSTEM AS THE MAIN FOR THE EM |
| SYSTEM WOULD HAVE TRIPPED/OPENED. |
| PLEASE REVISE RISER AND REVISE NOTES TO |
| REFERENCE A 4-POLE TRANSFER SWITCH AND |
| INDICATING THE SEPARATELY DERIVED |
| SYSTEM. |
| |
| |
| **PLEASE SEE THE ABOVE REDLINES/PROVISO |
| ITEMS WILL NEED TO BE ADDRESSED BEFORE |
| ANY ROUGH ELECTRICAL INSPECTION IS |
| SCHEDULED. |
| ** PLEASE KNOW, ELECTRICAL PERMIT MAY BE |
| PLACED IN A "HOLD" STATUS UPON 6 MONTHS |
| TIME TABLE AND "PROVISO" HAS NOT BEEN |
| SUBMITTED. |
| |
| ** PLEASE KNOW, ANY OTHER |
| REVISIONS/DESIGN CHANGES MAY ALSO BE |
| SUBMITTED AT THAT TIME. |
| |
| |
| ** PLEASE CALL TO GO OVER SUCH ITEMS |
| LISTED ABOVE TO HELP IN EXPEDITING THIS |
| PROJECT TO A "P" STATUS. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE. |
| |