2008-01-19 12:13:22 | REV.18 PAGES M2.08, M2.20, M2.27, M2.29, M2.30, M2.32, | | M2.32A, M2.32B, M2.32C, M2.32D, M2.32F, M5.01 | | | | 1. M2.32C:THE FOLLOWING COMMENT FROM THE 10/25/07 | | REVIEW OF REV 16 HAS NOT BEEN ADDRESSED "UNIT P1, 12X8 | | RETURN TRANSFER FOR MASTER BEDROOM IS TOO SMALL TO MEET | | THE BALANCED RETURN EXCEPTIONS UNDER FBC,M 601.4. IF | | TRANSFERS ARE NOT DESIGNED TO MEET THESE EXCEPTIONS, A | | FIELD TEST WILL BE REQUIRED AT FNAL INSPECTION TO | | VERIFY PRESSURE DIFFERENTIALS ARE LESS THAN 0.01 INCHES | | W.C AS REQUIRED BY THIS SECTION." THE PAGE WILL PASS | | REVIEW AS IT IS THE ONLLY OUTSTANDING COMMENT. THERE | | WILL BE A STAMP ON PLANS CALLING FOR A FIELD TEST TO | | VERIFY BALANCED RETURN AT FINAL INSPECTION. | | | | 2. M2.30 AND M2.32D: SAME COMMENT AS ABOVE APPLIES TO | | UNIT P ON THIS PAGE FOR 15X6 TRANSFER FROM MASTER | | BEDROOM. | | | | 3. M2.32 AND M2.32F: SAME COMMENT AS ABOVE APPLIES TO | | UNIT N ON THIS PAGE FOR 10 INCH ROUND TRANSFER FROM | | BEDROOM 3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|