Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop P
Sequence Number 4
Notes
Date Text
2006-02-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW: (FROM 1ST REVIEW)
  
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND. - THIS WILL BE A FIELD
 INSPECTOR APPROVAL. IF COMMON USE AREA
 IS AVAILABLE TO TENANTS AND GUESTS, ALL
 REQUIREMENTS OF SECTION 11-4.24 WILL BE
 ADHERED TO. - DETAIL SUBMITTED IS FOR
 THE DWELLING UNITS. SINKS INDICATED
 SHALL COMPLY AS REQUIRED IN SECTION
 11-4.24 AND ALL SUBSECTIONS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.24.2/HEIGHT, 11-4.24.3/KNEE
 CLEARANCE, 11-4.24.4/SINK DEPTH,
 11-4.24.5/CLEAR FLOOR SPACE (FORWARD
 APPROACH), 11-4.24.6/EXPOSED PIPES &
 SURFACES, & 11-4.24.7/FAUCETS.
  
 SECOND REVIEW
 **************NEW COMMENTS**************
  
 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1. - RISER #60 SHOWS W/M'S &
 KITCHEN SINKS, BUT FLOOR PLAN SHOWS
 POWDER ROOMS 2ND, 3RD, & 4TH FLOORS.
 PLEASE CORRELATE RISER & FLOOR PLAN. -
 FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ.
 LEVEL, THEN CONNECTING TO RISER 60, BUT
 RISERS DO NOT SHOW THIS. PLEASE
 CORRELATE RISERS AND FLOOR PLAN.-
 THERE ARE TWO NUMBER 60 SANT. RISER
 DIAGRAMS. (SEE SHEETS P2.03, P2.09,
 P2.14, P2.20, P2.26, P2.32, & P2.38 FOR
 ONE RISER #60). (SEE SHEETS P2.05,
 P2.11, P2.16, P2.22, P2.29, P2.35, &
 P2.41 FOR THE OTHER RISER #60). THE
 FIRST RISER #60 SHOWS A SHOWER BATH FROM
 THE 6TH FLOOR UP, AND THE SECOND RISER
 #60 SHOWS W/M'S AND KITCHEN SINKS (WHICH
 REFLECT THE RISER DIAGRAM). PLEASE
 CLARIFY. (3.26, P3.29, P3.34, P3.35).
 73B) SHT P2.39 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1. - RISER
 #54 DOES NOT REFLECT THE FLOOR PLAN.
 (SEE SHT P3.21 SEALED 7-1-5) - THIS USED
 TO SHOW CORRECT FIXTURES, BUT WAS IN
 WRONG LOCATION. IT HAS BEEN CHANGED TO
 BATHROOM FIXTURES. PLEASE CLARIFY. - NOW
 SHEET HAS BEEN CHANGED AND DOES NOT
 REFLECT THE FLOOR PLAN INDICATED IN THE
 KEY PLAN AREA. NOT ALL UNITS ARE SHOWN.
 - NOW RISERS 1 & 2 ARE NOT SHOWN ON SHTS
 P2.02 & P2.08. - OFFSET SHOWN ON THE 5TH
 FLOOR, (P2.25), AND W/C PIPING DOES NOT
 REFLECT RISER 54A. DOES THIS THEN OFFSET
 BACK ON THE NEXT FLOOR?
 94B) SHT P2.64 STORM DRAIN LINE RUNNING
 EAST TO WEST AND CONNECTING TO RISER
 (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE
 LENGTH. SECTION 704.1 - NOT ADDRESSED,
 INDICATE ON PLANS. - PIPE SIZE INCREASED
 TO 12" BUT STILL SHOWS 1/4"FT ON ONE
 LENGTH AND NOT ENTIRE RUN. PLEASE
 CLARIFY.
 103B) SHTS P3.16 THRU P3.25 THE
 FOLLOWING SANITARY RISER DIAGRAMS WERE
 NOT LOCATED ON THE BUILDING DRAIN
 ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN),
 10, 59, 12, 13, 14, 17, 15, 18, 19, 20,
 21, 22, 72, 57, 75, 40, 41, 42, 37. -
 RISERS 12 THRU 22, 40 THRU 42 AND RISER
 75 HAVE NOT BEEN LOCATED ON THE BUILDING
 DRAIN ISOMETRIC AS NOTED IN THE COMMENT
 RESPONSE. - RISERS 19, 20, 72, & 75
 STILL NOT LOCATED ON BLDG DRAIN
 ISOMETRIC. COMMENT RESPONSE REFERS TO
 SHT P2.00. NO SHT P2.00 SUBMITTED.
 PLEASE CLARIFY.
 108B) SHT P3.21 RISER 26/35 KITCHEN SINK
 NOT SHOWN, DOES NOT REFLECT THE FLOOR
 PLAN, WASH MACHINE/LAUNDRY SINK OFFSET
 TO THE RIGHT SIDE NOT TO THE LEFT,
 VENTING FROM LAV DOES NOT REFLECT FLOOR
 PLAN. SECTION 104.2.1. - RISER 26/35 NOT
 SPLIT AND RISER 26 NOT FOUND ABOVE THE
 5TH FLOOR. PLEASE CLARIFY. - RISER 26
 STILL DOES NOT REFLECT THE FLOOR PLAN.
 (P3.31). VENTING FROM LAV NOT ADDRESSED.
 RISER 26 NOT FOUND ABOVE THE 5TH FLOOR.
 SHT P3.31 STATES "FOR CONT. SEE P3.16".
 RISER 26 NOT FOUND ON P3.16. PLEASE
 CLARIFY.
 109B) SHT P3.22 RISER 55 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 - STILL DOES NOT REFLECT FROM THE 6TH
 FLOOR UP. PLEASE CORRELATE RISER & FLOOR
 PLAN. RESPONSE INDICATES RISER 55 HAS
 BEEN CHANGED TO RISER 55A. WHY THE
 CHANGE. RISER IS SHOWN AS 55 & 55A.
 RISER 55 NOT LOCATED FROM THE 6TH FLOOR
 UP. RISER 55A DOES NOT REFLECT THE FLOOR
 PLAN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 THIRD REVIEW
 **************NEW COMMENTS**************
  
 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR
 PLAN DOES NOT REFLECT THE RISER DIAGRAM.
 - RISER 55 UNIT B1 NO REVENT TO RISER 27
 SHOWN ON FLOOR PLAN. SECTION 104.2.1.
 5C) SHT P2.40 UNABLE TO LOCATE RISER 56.
 SECTION 104.2.1. - NOW SHT P2.39 DOES
 NOT SHOW ALL UNITS.
  
 19C) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
 THIS IS GIVEN AS A NOTICE ONLY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 FORTH REVIEW
 ***************NEW COMMENTS*************
  
 1D. SHTS P2.05, P2.11, & P2.16 SHOW
 RISER 76 ON ALL FLOORS FROM GROUND FLOOR
 BASE OF STACK. SECTION 104.2.1.
 2D. SHTS P202 & P2.08 SHOW RISERS 1 & 2
 ON ALL FLOORS FROM THE GROUND FLOOR BASE
 OF STACK. SECTION 104.2.1.
 3D. SHT P2.13 VENT SHOWN ON RISER
 DIAGRAM NOT SHOWN ON THE FLOOR PLAN.
 (RISER 3,56,57). RISER AND FLOOR PLAN
 SHALL REFLECT EACH OTHER. SECTION
 104.2.1.
 4D. SHT P2.18 RISER 26 DOES NOT REFLECT
 THE FLOOR PLAN AT THE W/C OF THE POWDER
 ROOM. CORRELATE. SECTION 104.2.1.
 5D. SHTS P2.21, P2.22, P2.23,. P2.50 &
 P2.52 HAVE DIFFERENT DATES ON THE SEAL,
 DIFFERENT INFORMATION. - IT SEEMS THAT
 THE 6-3-5 SHEETS HAVE MORE UP TO DATE
 INFORMATION THAN THE 7-14-5 SHEETS.
 PLEASE CLARIFY. SECTION 104.2.1.
 6D. SHT P2.24 NOTE IN UNIT H6 STATES
 "SEE DRWG P2.20" PIPING LAYOUT NOT SHOWN
 ON SHT P2.20. PLEASE CLARIFY. SECTION
 104.2.1.
 7D. SHT P2.25 OFFSET NOT SHOWN ON THE
 5TH FLOOR FLOOR PLAN AT RISER 54A, BUT
 IS SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
 8D. SHT P2.28 VENTS FOR LAVS NOT SHOWN
 IN M/B UNIT B2. SECTION 104.2.1.
 9D. SHT P2.33 UNIT BE NOTES STATE "FOR
 SANT. LAYOUT SEE UNIT B3 DRAWING P2.39".
 B3 UNIT NOT SHOWN ON P2.39. - SHOW
 KITCHEN SINK PIPING FOR UNITS J & H.
 SECTION 104.2.1.
 10D. SHT. P2.34 SHOW RISER NUMBERS WHERE
 RISERS 30 & 32 DROP DOWN TO THE 5TH
 FLOOR. SECTION 104.2.1.
 11D. SHT P2.35 UNIT B WASH MACHINE
 OFFSET NOT SHOWN ON RISER DIAGRAM.
 PIPING IS NOT SHOWN TO THE LAUNDRY BOX.
 CLARIFY. SECTION 104.2.1.
 12D. SHT P2.39 NEW SHEET DOES NOT SHOW
 ALL UNITS INDICATED ON THE SHEET TITLE
 OF KEY PLAN SECTION. NEW SHEET REQUIRED.
 SECTION 104.2.1.
 13D. SHT P2.43 VENT RISER "FROM" RISER
 53 TO RISER 5 IS SHOWN AS "TO RISER 5E".
 THIS DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CLARIFY/CORRELATE. SECTION
 104.2.1.
 14D. SHT P2.60 SECONDARY ROOF DRAINS ARE
 NOT SHOWN FOR THE DECK AREA. SECTIONS
 104.2.1. & 1107.
 15D. SHT P2.64 PIPE SIZING FOR THE NEW
 OVERFLOW DRAINS IS NOT CORRECT. IF THEY
 ARE SECONDARY DRAINS, THEN THEY SHALL BE
 CALCULATED FOR ALL DRAINS IN EACH AREA
 AND SHALL ALL BE 8". IF THEY ARE SCUPPER
 DRAINS, ALL BUT THE AREAS THAT DRAIN
 3080SF & 3074SF SHALL BE 10". THE OTHER
 TWO SHALL BE 8". PLEASE CLARIFY. SECTION
 1107 & ALL SUBSECTIONS. - 6" DECK DRAIN
 3806SF SHOWS 816SF-A + 3990SF-V WHICH
 ADDS UP TO 4806SF & 6" DECK DRAIN 3619SF
 SHOWS 719A + 2099SF-V WHICH ADDS UP TO
 2818SF. PLEASE RECHECK ADDITION ON
 DRAINS. SECTION 104.2.1. - MUCH OF THE
 VERTICAL CONTRIBUTION OF STORM WATER
 WILL BE DRAINING INTO THE PLANTERS. WILL
 THIS BECOME A NUISANCE PROBLEM. PLEASE
 INDICATE HOW THISWILL WORK.
 16D. SHTS P3.01 THRU P3.16 ARE MISSING
 FROM ONE SET OF PLANS. SECTION 104.2.1.
 17D. SHT P3.28 RISER 54A DOES NOT
 REFLECT THE FLOOR PLAN ON THE 5TH FLOOR.
 - RISER 3 VENT STACK ON THE 16TH FLOOR
 NOT APPROVED AS SHOWN. VENT MAY NOT
 TERMINATE ON THE 15TH FLOOR AND START
 AGAIN ON THE 16TH FLOOR. SECTIONS
 104.2.1. & 903.3.
 18D. SHT P3.26 RISER 64 MISNUMBERED AT
 5TH FLOOR. (62) - INDICATE IF RISERS 48
 & 50 ARE TYPICAL FROM THE 16TH FLOOR
 THRU THE 21ST FLOOR. SECTION 104.2.1.
 19D. SHT P3.30 RISER DIAGRAM 50 DOES NOT
 REFLECT THE FLOOR PLAN 3RD & 4TH FLOORS.
 PLEASE CORRELATE. (P2.21) - RISER
 DIAGRAM 50/48 DOES NOT REFLECT THE FLOOR
 PLAN ON THE 16TH FLOOR. RISER 50 SHOWS
 NO FIXTURES FROM THE 16TH THRU THE 20TH
 FLOORS. - RISER 78 IS NOT INDICATED
 UNTIL THE 16TH FLOOR. SHOW RISER NUMBER
 FROM THE GROUND FLOOR UP. SECTION
 104.2.1.
 20D. SHT P3.39 THE TRENCH DRAINS ON THE
 5TH FLOOR LANAI LEVEL ARE NOT SHOWN ON
 THE RISER DIAGRAM FOR THE STORM. PLEASE
 CORRELATE RISER AND FLOOR PLAN AND
 INDICATE SQUARE FOOTAGE DRAINED BY THE
 TRENCH DRAINS. SECTIONS 104.2.1 & 1106
 AND TABLE 1106.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]