2006-02-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA STATUTES |
| |
| FROM PREVIOUS REVIEW: (FROM 1ST REVIEW) |
| |
| 12) SHT A4.41 KITCHEN SINK & JUICE BAR |
| SINK IN COMMON AREAS SHALL COMPLY WITH |
| SECTION 11-4.24 AND ALL SUBSECTIONS. |
| SUBMIT A DETAIL. RESPONSE NOTED, BUT NO |
| DETAIL WAS FOUND. - THIS WILL BE A FIELD |
| INSPECTOR APPROVAL. IF COMMON USE AREA |
| IS AVAILABLE TO TENANTS AND GUESTS, ALL |
| REQUIREMENTS OF SECTION 11-4.24 WILL BE |
| ADHERED TO. - DETAIL SUBMITTED IS FOR |
| THE DWELLING UNITS. SINKS INDICATED |
| SHALL COMPLY AS REQUIRED IN SECTION |
| 11-4.24 AND ALL SUBSECTIONS. SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH SECTIONS |
| 11-4.24.2/HEIGHT, 11-4.24.3/KNEE |
| CLEARANCE, 11-4.24.4/SINK DEPTH, |
| 11-4.24.5/CLEAR FLOOR SPACE (FORWARD |
| APPROACH), 11-4.24.6/EXPOSED PIPES & |
| SURFACES, & 11-4.24.7/FAUCETS. |
| |
| SECOND REVIEW |
| **************NEW COMMENTS************** |
| |
| 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES |
| NOT REFLECT THE RISER DIAGRAM. SECTION |
| 104.2.1. - RISER #60 SHOWS W/M'S & |
| KITCHEN SINKS, BUT FLOOR PLAN SHOWS |
| POWDER ROOMS 2ND, 3RD, & 4TH FLOORS. |
| PLEASE CORRELATE RISER & FLOOR PLAN. - |
| FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ. |
| LEVEL, THEN CONNECTING TO RISER 60, BUT |
| RISERS DO NOT SHOW THIS. PLEASE |
| CORRELATE RISERS AND FLOOR PLAN.- |
| THERE ARE TWO NUMBER 60 SANT. RISER |
| DIAGRAMS. (SEE SHEETS P2.03, P2.09, |
| P2.14, P2.20, P2.26, P2.32, & P2.38 FOR |
| ONE RISER #60). (SEE SHEETS P2.05, |
| P2.11, P2.16, P2.22, P2.29, P2.35, & |
| P2.41 FOR THE OTHER RISER #60). THE |
| FIRST RISER #60 SHOWS A SHOWER BATH FROM |
| THE 6TH FLOOR UP, AND THE SECOND RISER |
| #60 SHOWS W/M'S AND KITCHEN SINKS (WHICH |
| REFLECT THE RISER DIAGRAM). PLEASE |
| CLARIFY. (3.26, P3.29, P3.34, P3.35). |
| 73B) SHT P2.39 ALL UNITS SHOW PIPING TO |
| REFLECT RISERS. SECTION 104.2.1. - RISER |
| #54 DOES NOT REFLECT THE FLOOR PLAN. |
| (SEE SHT P3.21 SEALED 7-1-5) - THIS USED |
| TO SHOW CORRECT FIXTURES, BUT WAS IN |
| WRONG LOCATION. IT HAS BEEN CHANGED TO |
| BATHROOM FIXTURES. PLEASE CLARIFY. - NOW |
| SHEET HAS BEEN CHANGED AND DOES NOT |
| REFLECT THE FLOOR PLAN INDICATED IN THE |
| KEY PLAN AREA. NOT ALL UNITS ARE SHOWN. |
| - NOW RISERS 1 & 2 ARE NOT SHOWN ON SHTS |
| P2.02 & P2.08. - OFFSET SHOWN ON THE 5TH |
| FLOOR, (P2.25), AND W/C PIPING DOES NOT |
| REFLECT RISER 54A. DOES THIS THEN OFFSET |
| BACK ON THE NEXT FLOOR? |
| 94B) SHT P2.64 STORM DRAIN LINE RUNNING |
| EAST TO WEST AND CONNECTING TO RISER |
| (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE |
| LENGTH. SECTION 704.1 - NOT ADDRESSED, |
| INDICATE ON PLANS. - PIPE SIZE INCREASED |
| TO 12" BUT STILL SHOWS 1/4"FT ON ONE |
| LENGTH AND NOT ENTIRE RUN. PLEASE |
| CLARIFY. |
| 103B) SHTS P3.16 THRU P3.25 THE |
| FOLLOWING SANITARY RISER DIAGRAMS WERE |
| NOT LOCATED ON THE BUILDING DRAIN |
| ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN), |
| 10, 59, 12, 13, 14, 17, 15, 18, 19, 20, |
| 21, 22, 72, 57, 75, 40, 41, 42, 37. - |
| RISERS 12 THRU 22, 40 THRU 42 AND RISER |
| 75 HAVE NOT BEEN LOCATED ON THE BUILDING |
| DRAIN ISOMETRIC AS NOTED IN THE COMMENT |
| RESPONSE. - RISERS 19, 20, 72, & 75 |
| STILL NOT LOCATED ON BLDG DRAIN |
| ISOMETRIC. COMMENT RESPONSE REFERS TO |
| SHT P2.00. NO SHT P2.00 SUBMITTED. |
| PLEASE CLARIFY. |
| 108B) SHT P3.21 RISER 26/35 KITCHEN SINK |
| NOT SHOWN, DOES NOT REFLECT THE FLOOR |
| PLAN, WASH MACHINE/LAUNDRY SINK OFFSET |
| TO THE RIGHT SIDE NOT TO THE LEFT, |
| VENTING FROM LAV DOES NOT REFLECT FLOOR |
| PLAN. SECTION 104.2.1. - RISER 26/35 NOT |
| SPLIT AND RISER 26 NOT FOUND ABOVE THE |
| 5TH FLOOR. PLEASE CLARIFY. - RISER 26 |
| STILL DOES NOT REFLECT THE FLOOR PLAN. |
| (P3.31). VENTING FROM LAV NOT ADDRESSED. |
| RISER 26 NOT FOUND ABOVE THE 5TH FLOOR. |
| SHT P3.31 STATES "FOR CONT. SEE P3.16". |
| RISER 26 NOT FOUND ON P3.16. PLEASE |
| CLARIFY. |
| 109B) SHT P3.22 RISER 55 DOES NOT |
| REFLECT THE FLOOR PLAN. SECTION 104.2.1. |
| - STILL DOES NOT REFLECT FROM THE 6TH |
| FLOOR UP. PLEASE CORRELATE RISER & FLOOR |
| PLAN. RESPONSE INDICATES RISER 55 HAS |
| BEEN CHANGED TO RISER 55A. WHY THE |
| CHANGE. RISER IS SHOWN AS 55 & 55A. |
| RISER 55 NOT LOCATED FROM THE 6TH FLOOR |
| UP. RISER 55A DOES NOT REFLECT THE FLOOR |
| PLAN. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| THIRD REVIEW |
| **************NEW COMMENTS************** |
| |
| 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR |
| PLAN DOES NOT REFLECT THE RISER DIAGRAM. |
| - RISER 55 UNIT B1 NO REVENT TO RISER 27 |
| SHOWN ON FLOOR PLAN. SECTION 104.2.1. |
| 5C) SHT P2.40 UNABLE TO LOCATE RISER 56. |
| SECTION 104.2.1. - NOW SHT P2.39 DOES |
| NOT SHOW ALL UNITS. |
| |
| 19C) SEE ATTACHED SHEET CONCERNING THE |
| DESIGN PROFESSIONAL AND FS 553.80(2)(B). |
| THIS IS GIVEN AS A NOTICE ONLY. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| FORTH REVIEW |
| ***************NEW COMMENTS************* |
| |
| 1D. SHTS P2.05, P2.11, & P2.16 SHOW |
| RISER 76 ON ALL FLOORS FROM GROUND FLOOR |
| BASE OF STACK. SECTION 104.2.1. |
| 2D. SHTS P202 & P2.08 SHOW RISERS 1 & 2 |
| ON ALL FLOORS FROM THE GROUND FLOOR BASE |
| OF STACK. SECTION 104.2.1. |
| 3D. SHT P2.13 VENT SHOWN ON RISER |
| DIAGRAM NOT SHOWN ON THE FLOOR PLAN. |
| (RISER 3,56,57). RISER AND FLOOR PLAN |
| SHALL REFLECT EACH OTHER. SECTION |
| 104.2.1. |
| 4D. SHT P2.18 RISER 26 DOES NOT REFLECT |
| THE FLOOR PLAN AT THE W/C OF THE POWDER |
| ROOM. CORRELATE. SECTION 104.2.1. |
| 5D. SHTS P2.21, P2.22, P2.23,. P2.50 & |
| P2.52 HAVE DIFFERENT DATES ON THE SEAL, |
| DIFFERENT INFORMATION. - IT SEEMS THAT |
| THE 6-3-5 SHEETS HAVE MORE UP TO DATE |
| INFORMATION THAN THE 7-14-5 SHEETS. |
| PLEASE CLARIFY. SECTION 104.2.1. |
| 6D. SHT P2.24 NOTE IN UNIT H6 STATES |
| "SEE DRWG P2.20" PIPING LAYOUT NOT SHOWN |
| ON SHT P2.20. PLEASE CLARIFY. SECTION |
| 104.2.1. |
| 7D. SHT P2.25 OFFSET NOT SHOWN ON THE |
| 5TH FLOOR FLOOR PLAN AT RISER 54A, BUT |
| IS SHOWN ON THE RISER DIAGRAM. PLEASE |
| CORRELATE RISER AND FLOOR PLAN. SECTION |
| 104.2.1. |
| 8D. SHT P2.28 VENTS FOR LAVS NOT SHOWN |
| IN M/B UNIT B2. SECTION 104.2.1. |
| 9D. SHT P2.33 UNIT BE NOTES STATE "FOR |
| SANT. LAYOUT SEE UNIT B3 DRAWING P2.39". |
| B3 UNIT NOT SHOWN ON P2.39. - SHOW |
| KITCHEN SINK PIPING FOR UNITS J & H. |
| SECTION 104.2.1. |
| 10D. SHT. P2.34 SHOW RISER NUMBERS WHERE |
| RISERS 30 & 32 DROP DOWN TO THE 5TH |
| FLOOR. SECTION 104.2.1. |
| 11D. SHT P2.35 UNIT B WASH MACHINE |
| OFFSET NOT SHOWN ON RISER DIAGRAM. |
| PIPING IS NOT SHOWN TO THE LAUNDRY BOX. |
| CLARIFY. SECTION 104.2.1. |
| 12D. SHT P2.39 NEW SHEET DOES NOT SHOW |
| ALL UNITS INDICATED ON THE SHEET TITLE |
| OF KEY PLAN SECTION. NEW SHEET REQUIRED. |
| SECTION 104.2.1. |
| 13D. SHT P2.43 VENT RISER "FROM" RISER |
| 53 TO RISER 5 IS SHOWN AS "TO RISER 5E". |
| THIS DOES NOT REFLECT THE RISER DIAGRAM. |
| PLEASE CLARIFY/CORRELATE. SECTION |
| 104.2.1. |
| 14D. SHT P2.60 SECONDARY ROOF DRAINS ARE |
| NOT SHOWN FOR THE DECK AREA. SECTIONS |
| 104.2.1. & 1107. |
| 15D. SHT P2.64 PIPE SIZING FOR THE NEW |
| OVERFLOW DRAINS IS NOT CORRECT. IF THEY |
| ARE SECONDARY DRAINS, THEN THEY SHALL BE |
| CALCULATED FOR ALL DRAINS IN EACH AREA |
| AND SHALL ALL BE 8". IF THEY ARE SCUPPER |
| DRAINS, ALL BUT THE AREAS THAT DRAIN |
| 3080SF & 3074SF SHALL BE 10". THE OTHER |
| TWO SHALL BE 8". PLEASE CLARIFY. SECTION |
| 1107 & ALL SUBSECTIONS. - 6" DECK DRAIN |
| 3806SF SHOWS 816SF-A + 3990SF-V WHICH |
| ADDS UP TO 4806SF & 6" DECK DRAIN 3619SF |
| SHOWS 719A + 2099SF-V WHICH ADDS UP TO |
| 2818SF. PLEASE RECHECK ADDITION ON |
| DRAINS. SECTION 104.2.1. - MUCH OF THE |
| VERTICAL CONTRIBUTION OF STORM WATER |
| WILL BE DRAINING INTO THE PLANTERS. WILL |
| THIS BECOME A NUISANCE PROBLEM. PLEASE |
| INDICATE HOW THISWILL WORK. |
| 16D. SHTS P3.01 THRU P3.16 ARE MISSING |
| FROM ONE SET OF PLANS. SECTION 104.2.1. |
| 17D. SHT P3.28 RISER 54A DOES NOT |
| REFLECT THE FLOOR PLAN ON THE 5TH FLOOR. |
| - RISER 3 VENT STACK ON THE 16TH FLOOR |
| NOT APPROVED AS SHOWN. VENT MAY NOT |
| TERMINATE ON THE 15TH FLOOR AND START |
| AGAIN ON THE 16TH FLOOR. SECTIONS |
| 104.2.1. & 903.3. |
| 18D. SHT P3.26 RISER 64 MISNUMBERED AT |
| 5TH FLOOR. (62) - INDICATE IF RISERS 48 |
| & 50 ARE TYPICAL FROM THE 16TH FLOOR |
| THRU THE 21ST FLOOR. SECTION 104.2.1. |
| 19D. SHT P3.30 RISER DIAGRAM 50 DOES NOT |
| REFLECT THE FLOOR PLAN 3RD & 4TH FLOORS. |
| PLEASE CORRELATE. (P2.21) - RISER |
| DIAGRAM 50/48 DOES NOT REFLECT THE FLOOR |
| PLAN ON THE 16TH FLOOR. RISER 50 SHOWS |
| NO FIXTURES FROM THE 16TH THRU THE 20TH |
| FLOORS. - RISER 78 IS NOT INDICATED |
| UNTIL THE 16TH FLOOR. SHOW RISER NUMBER |
| FROM THE GROUND FLOOR UP. SECTION |
| 104.2.1. |
| 20D. SHT P3.39 THE TRENCH DRAINS ON THE |
| 5TH FLOOR LANAI LEVEL ARE NOT SHOWN ON |
| THE RISER DIAGRAM FOR THE STORM. PLEASE |
| CORRELATE RISER AND FLOOR PLAN AND |
| INDICATE SQUARE FOOTAGE DRAINED BY THE |
| TRENCH DRAINS. SECTIONS 104.2.1 & 1106 |
| AND TABLE 1106.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| |
| |