2006-01-23 00:00:00 | 19. PLEASE EXPLAIN "OR THROUGH THE |
| ANNUNCIATION OF AT LEAST THREE (3) AREA |
| WIDE SMOKE DETECTORS SERVING A SMOKE |
| CONTROL ZONE". (SMOKE CONTROL OPERATION |
| PAGE M7.01.) WHY WILL IT TAKE THREE |
| SMOKE DETECTORS TO OPERATE. |
| |
| 20. PLEASE INCLUDE NOTE TO PAGE M7.01 |
| "ANTICPATED STACK EFFECT" REGARDING |
| STAIR PRESSURIZATION. |
| |
| 21. FIRE SPRINKLER PROTECTION REQUIRED |
| BELOW DUCTWORK THAT IS GREATER THAN 48" |
| WIDE. |
| |
| 22. THE EMERGENCY GENERATOR TERMINATION |
| EXHAUST DUCT POINT SHALL BE LOCATED WITH |
| RESPECT TO WINDOWS, DOORS OR SUPPLY AIR |
| OPENING. ALSO ARCHITECTURAL FEATURES CAN |
| CAUSE A BACKFEED CONDITION. |
| |
| 23. ALL FIRE DAMPERS ARE TO BE DROP |
| TESTED AND CERTIFIED AFTER INSTALLATION. |
| |
| 24. COOLING TOWERS TO COMPLY WITH NFPA |
| 214. |
| |
| 25. TWO DAMPERS APPEAR TO BE SHOWN ON |
| DRAWING BUT ARE NOT CALLED OUT ON PAGE |
| M2.09. |
| |
| 26. A DAMPER IS SHOWN ON PAGE M2.03 DOES |
| NOT APPEAR TO BE CALLED OUT. |
| |
| 27. WILL THE HORIZONTAL MEMBERS OF THE |
| TRELLIS HAVE AN EFFECT ON SEF-1, SHOWN |
| ON THE SECTION 1, PAGE M1.13. |
| |
| 28. THE SMOKE SYSTEM AND STAIRWELL |
| PRESSURIZATION SYSTEMS SHALL BE TESTED |
| PRIOR TO REQUESTING A TCO OR CO AND BOTH |
| SYSTEMS MUST BE APPROVED BY CITY |
| OFFICIALS. |
2006-01-06 00:00:00 | 1. ALL EXIT ACCESS AREAS AND EXIT DOORS |
| SHALL BE PROVIDED WITH EXIT SIGNS. SOME |
| ELECTRICAL SHEETS APPEAR TO BE MISSING |
| EXIT SIGNS. |
| |
| 2. NO EXIT SIGNS SHOWN ON MAIN ROOF |
| LEVEL WEST. E2.19. THE SAME CONDITION |
| MAIN ROOF LEVEL EAST. |
| |
| 3. THERE APPEARS TO BE A DISCREPANCY |
| BETWEEN SOME DRAWING SHEETS. ON ONE |
| SHEET THE SMOKE MANAGEMENT PANEL IS |
| MISSING FROM THE FIRE COMMAND ROOM AND |
| ANOTHER PAGE IT IS SHOWN. |
| |
| 4. THE REQUIRED FIRE ALARM SYSTEM SHALL |
| BE MONITORED BY A UL LISTED CENTRAL |
| STATION APPROVED FOR CENTRAL STATION |
| SERVICE. |
| |
| 5. FIRE SPRINKLER HEADS SHALL BE QUICK |
| RESPONSE OR BE RESIDENTIAL TYPES. |
| |
| 6. STANDPIPES SHALL PROVIDE COVERAGE TO |
| ALL ARES OF THE BUILDING. ALL REQUIRED |
| STAIRWELLS ARE REQUIRED TO HAVE |
| STANDPIPES. |
| |
| 7. ALL ELEVATORS THAT CAN BE USED FOR |
| STRETCHERS SHALL BE IDENTIFIED. |
| |
| 8. DOOR MISSING FROM EXIT PATH FROM |
| ELEVATOR VESTIBULE # 3 UP THE STAIRS AND |
| APPEARS TO TRAVEL BEHIND PARKING SPACE. |
| PLEASE SEE PAGE LS1.03. |
| |
| 9. PLEASE VERIFY DOOR SWINGS IN |
| HORIZONTAL EXITS SHOWN ON PAGE LS1.03. |
| |
| 10. EXIT SIGNS ON POOL DECK SHALL NOT |
| EXCEED 100 FEET. PLEASE SEE LS1.10. |
| |
| 11. PLEASE PROVIDE FLAMESPREAD DATA ON |
| "THERMOCON SPRAY -ON INSULATION SHOWN ON |
| PAGE A4.02. |
| |
| 12. THE "3-0 WIDE PEDESTRIAN PASS GATE |
| MUST BE LABELED AS AN EXIT. WHEN THE |
| VEHICULAR SECTIONAL GATE IS DOWN ONLY |
| ONE EXIT APPEAR VISIBLES FROM THE THAT |
| SPECIFIC PARKING AREA. PLEASE SEE A4.11. |
| |
| 13. PLEASE EXPLAIN CARD READERS SHOWN ON |
| PAGE A4.14. WILL THEY POSE ANY PROBLEMS |
| WITH REGARDS TO EXITING. |
| |
| 14. CARD READERS NOTED IN SEVERAL PLACES |
| ON DOOR SCHEDULE. PLEASE NOTE ON THE |
| PLANS HOW THESE DEVICES WILL NOT |
| INTERFERE WITH EXITING REQUIREMENTS. |
| |
| 15. MECHANICAL ACCESS SPACES SHOWN ON |
| SEVERAL A PAGES. PLEASE PROVIDE DETAILS. |
| |
| 16. POOL DECK FLOOR HAS A DOOR THAT |
| OPPOSES ONE OF THE POOL PUMP ROOM DOOR. |
| PLEASE SEE PAGE A7.05A |
| |
| 17. MORE DETAILS NEEDED ON NON-RATED |
| METAL MESH PARTITION SHOWN ON PAGE |
| A7.03. |
| |
| 18. ON SOME OF THE REFLECTED CEILING |
| PLANS, SMOKE DETECTORS APPEAR TO BE |
| DIRECTLY NEXT TO HVAC DIFFUSERS. THE |
| MINIMUM THREE FOOT RULE IS TO APPLY. |
| |
| NOTE: MECHANICAL DRAWINGS WILL BE NEXT |
| SET OF DRAWINGS TO BE REVIEWED BY THIS |
| OFFICE. |