Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2006-01-23 00:00:0019. PLEASE EXPLAIN "OR THROUGH THE
 ANNUNCIATION OF AT LEAST THREE (3) AREA
 WIDE SMOKE DETECTORS SERVING A SMOKE
 CONTROL ZONE". (SMOKE CONTROL OPERATION
 PAGE M7.01.) WHY WILL IT TAKE THREE
 SMOKE DETECTORS TO OPERATE.
  
 20. PLEASE INCLUDE NOTE TO PAGE M7.01
 "ANTICPATED STACK EFFECT" REGARDING
 STAIR PRESSURIZATION.
  
 21. FIRE SPRINKLER PROTECTION REQUIRED
 BELOW DUCTWORK THAT IS GREATER THAN 48"
 WIDE.
  
 22. THE EMERGENCY GENERATOR TERMINATION
 EXHAUST DUCT POINT SHALL BE LOCATED WITH
 RESPECT TO WINDOWS, DOORS OR SUPPLY AIR
 OPENING. ALSO ARCHITECTURAL FEATURES CAN
 CAUSE A BACKFEED CONDITION.
  
 23. ALL FIRE DAMPERS ARE TO BE DROP
 TESTED AND CERTIFIED AFTER INSTALLATION.
  
 24. COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 25. TWO DAMPERS APPEAR TO BE SHOWN ON
 DRAWING BUT ARE NOT CALLED OUT ON PAGE
 M2.09.
  
 26. A DAMPER IS SHOWN ON PAGE M2.03 DOES
 NOT APPEAR TO BE CALLED OUT.
  
 27. WILL THE HORIZONTAL MEMBERS OF THE
 TRELLIS HAVE AN EFFECT ON SEF-1, SHOWN
 ON THE SECTION 1, PAGE M1.13.
  
 28. THE SMOKE SYSTEM AND STAIRWELL
 PRESSURIZATION SYSTEMS SHALL BE TESTED
 PRIOR TO REQUESTING A TCO OR CO AND BOTH
 SYSTEMS MUST BE APPROVED BY CITY
 OFFICIALS.
2006-01-06 00:00:001. ALL EXIT ACCESS AREAS AND EXIT DOORS
 SHALL BE PROVIDED WITH EXIT SIGNS. SOME
 ELECTRICAL SHEETS APPEAR TO BE MISSING
 EXIT SIGNS.
  
 2. NO EXIT SIGNS SHOWN ON MAIN ROOF
 LEVEL WEST. E2.19. THE SAME CONDITION
 MAIN ROOF LEVEL EAST.
  
 3. THERE APPEARS TO BE A DISCREPANCY
 BETWEEN SOME DRAWING SHEETS. ON ONE
 SHEET THE SMOKE MANAGEMENT PANEL IS
 MISSING FROM THE FIRE COMMAND ROOM AND
 ANOTHER PAGE IT IS SHOWN.
  
 4. THE REQUIRED FIRE ALARM SYSTEM SHALL
 BE MONITORED BY A UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 5. FIRE SPRINKLER HEADS SHALL BE QUICK
 RESPONSE OR BE RESIDENTIAL TYPES.
  
 6. STANDPIPES SHALL PROVIDE COVERAGE TO
 ALL ARES OF THE BUILDING. ALL REQUIRED
 STAIRWELLS ARE REQUIRED TO HAVE
 STANDPIPES.
  
 7. ALL ELEVATORS THAT CAN BE USED FOR
 STRETCHERS SHALL BE IDENTIFIED.
  
 8. DOOR MISSING FROM EXIT PATH FROM
 ELEVATOR VESTIBULE # 3 UP THE STAIRS AND
 APPEARS TO TRAVEL BEHIND PARKING SPACE.
 PLEASE SEE PAGE LS1.03.
  
 9. PLEASE VERIFY DOOR SWINGS IN
 HORIZONTAL EXITS SHOWN ON PAGE LS1.03.
  
 10. EXIT SIGNS ON POOL DECK SHALL NOT
 EXCEED 100 FEET. PLEASE SEE LS1.10.
  
 11. PLEASE PROVIDE FLAMESPREAD DATA ON
 "THERMOCON SPRAY -ON INSULATION SHOWN ON
 PAGE A4.02.
  
 12. THE "3-0 WIDE PEDESTRIAN PASS GATE
 MUST BE LABELED AS AN EXIT. WHEN THE
 VEHICULAR SECTIONAL GATE IS DOWN ONLY
 ONE EXIT APPEAR VISIBLES FROM THE THAT
 SPECIFIC PARKING AREA. PLEASE SEE A4.11.
  
 13. PLEASE EXPLAIN CARD READERS SHOWN ON
 PAGE A4.14. WILL THEY POSE ANY PROBLEMS
 WITH REGARDS TO EXITING.
  
 14. CARD READERS NOTED IN SEVERAL PLACES
 ON DOOR SCHEDULE. PLEASE NOTE ON THE
 PLANS HOW THESE DEVICES WILL NOT
 INTERFERE WITH EXITING REQUIREMENTS.
  
 15. MECHANICAL ACCESS SPACES SHOWN ON
 SEVERAL A PAGES. PLEASE PROVIDE DETAILS.
  
 16. POOL DECK FLOOR HAS A DOOR THAT
 OPPOSES ONE OF THE POOL PUMP ROOM DOOR.
 PLEASE SEE PAGE A7.05A
  
 17. MORE DETAILS NEEDED ON NON-RATED
 METAL MESH PARTITION SHOWN ON PAGE
 A7.03.
  
 18. ON SOME OF THE REFLECTED CEILING
 PLANS, SMOKE DETECTORS APPEAR TO BE
 DIRECTLY NEXT TO HVAC DIFFUSERS. THE
 MINIMUM THREE FOOT RULE IS TO APPLY.
  
 NOTE: MECHANICAL DRAWINGS WILL BE NEXT
 SET OF DRAWINGS TO BE REVIEWED BY THIS
 OFFICE.