Date |
Text |
2005-12-31 00:00:00 | REVIEW STARTED, IN PROGRESS |
| ** SEE ALL NOTES BELOW FOR CONDITIONS ** |
| |
| |
| ** PLANS TO REMAIN IN "F" STATUS UNTILL |
| THE FOLLOWING NOTES ARE ADDRESSED TO |
| CHANGE PROJECT TO "P" (PASSED) STATUS. |
| |
| 1)NOTE: PLEASE SEE ONE SET IS MISSING |
| SHEET E1.05 |
| |
| 2)NOTE: PLEASE SEE ALL THREE SETS ARE |
| MISSING SHEETS E8.06-8.14 AS INDICATED |
| ON COVER SHEET.?? THESE WERE IN PREVIOUS |
| SETS? SEE PROVISO ALSO. |
| |
| 2)NOTE: PLEASE SEE PREVIOUS REVIEWS |
| WHICH REQUESTED ALL SUBMITTALS FOR ALL |
| EQUIPMENT SPECS: |
| PLEASE SEE THE FIRE PUMP AND FIRE PUMP |
| CONTROLLER SPECS WERE SUBMITTED, HOWEVER |
| THERE APPEARS TO BE ONLY ONE SET AND |
| THEY ARE LOCATED IN THE REPSONSE PACKAGE |
| BY THE ENGINEER. PLEASE SEE THE |
| "EQUIPMENT SPEC BOOKS" SHOULD CONTAIN |
| THREE SETS OF SAID SPECS FOR FP AND FPC. |
| |
| 3)NOTE: PLEASE ALSO SEE NOTES PERTAINING |
| TO "COLOR CODING SPEC SHEET" AND |
| BUS-DUCT SPEC SHEET" WHICH WERE TO BE |
| REVISED IN " JOBSITE SPEC BOOKS". THESE |
| SHEETS WERE REVISED, HOWEVER THE ONE |
| COPY OF THESE (BUS-DUCT) WAS SUBMITTED |
| IN THE SAME PACKAGE WITH THE ENGINEER'S |
| RESPONSES AND THE OTHER REVISED COPIES |
| OF COLOR CODING WERE SUBMITTED IN EQUIP |
| SPEC BKS.. |
| PLEASE SEE THREE COPIES OF THE REVISED |
| 16120-2 WERE PLACED IN EQIP SPEC BK |
| INSTEAD IF JOBSITE SPEC BOOK. |
| |
| ** PLEASE BRING IN SHEETSNEEDED TO |
| COMPLETE ALL THREE "JOBSITE SPEC BOOKS" |
| AND THE THREE COPIES OF "EQUIPMENT SPEC |
| BOOKS". |
| THESE BOOKS WILL BE STAMPED AT THAT |
| TIME. |
| |
| **************************************** |
| PLEASE SEE THE FOLLOWING WILL BE SET UP |
| AS A "PROVISO" WHICH WILL REQUIRE SOME |
| SHEETS TO BE REVISED "BEFORE ANY ROUGH |
| ELECTRICAL INSPECTION" OR 6 MONTHS WHICH |
| EVER COMES FIRST. |
| THESE ITEMS HAVE ALSO BEEN REDLINED ON |
| PLANS. |
| ITEMS FROM PREVIOUS REVIEWS AND |
| INFORMATION TO BE FORTH COMING. |
| |
| |
| ********** PROVISO/REVISION *********** |
| |
| 1)NOTE: PLEASE SEE MISSING RECEPTS IN |
| UNITS |
| "A", "G","D","HD". 210.52 |
| REDLINED |
| |
| 2)NOTE:PLEASE SEE SOME AREAS LABLED AS |
| "FOYER CONTAIN RECEPTS ON SMALL |
| APPLIANCE CIRCUITS. SEE 210.52B1 UNIT |
| G-1,E-1, VV1 |
| REDLINED. |
| |
| 3)NOTE:PLEASE SEE THE FOLLOWING UNITS |
| WHICH SMOKE DETECTORS ARE STILL SHOWN ON |
| MORE THAN ONE CIRCUIT. SEE UNIT #4, C-1 |
| REDLINED. |
| |
| 4)NOTE: PLEASE SEE UNIT "S" DINING RM |
| DESIGNATION REMOVED. |
| REDLINED |
| |
| 5)NOTE: PLEASE SEE SHEET 7.09 DOES NOT |
| CONTAIN THE FEEDER SCHEDULE FOR THE 225A |
| PANEL "N", THIS WAS REVISED ON 7.08. |
| REDLINED. |
| |
| 6)NOTE: PLEASE SEE PANEL SCHEDULE FOR |
| UNIT "D-2" WAS SUBMITTED, HOWEVER |
| CIRCUIT #15 FOR SD'S DOES NOT INDICATE |
| THE REQUIRED ARC FAULT PROTECTION NOTE. |
| REDLINED ON PANEL SCHEDULE, UNIT.210.12 |
| |
| 7)NOTE:POOL AREA LIGHTING TO MEET MIN |
| CLEARENCES PER 680.22 AND 411.4 |
| SOME FIXTURES SHOWN CLOSER THAN |
| PERMITTED. |
| REDLINED. |
| |
| 8)NOTE:PLEASE SEE LS101 7.8.1.3 (1) |
| WHICH REQUIRES A MIN OF 10FT |
| CANDLES(108LUX) IN STAIR TOWERS. THIS |
| LEVEL OF LIGHTING IS REQUIRED ON THE |
| WALKING SURFACES DURING NOMRAL POWER |
| CONDITIONS.(1FT CANDLE IN EMERGENCY |
| CONDITIONS. PHOTO-METRICS WILL BE |
| REQUIRED OF STAIR- |
| TOWERS. |
| |
| PLEASE SEE LS101 7.9.2.2 WHICH MENTIONS |
| IN THE EVENT OF THE TRIPPING OF ANY |
| SINGLE MEANS OF OCP WSHOULD NOT LEAVE |
| ANY EGRESS AREA IN TOTAL DARKNESS. |
| PLEASE ALSO SEE A MIN OF SOME SORT OF |
| BATTERY BACK UP FIXTURE FOR CORRIDOR'S |
| AND PARKING GARAGE WILL BE REQUIRD TO |
| PROVIDE MEANS OF EGRESS AT A LIGHTING |
| LEVEL OF 1FT CANDLE. |
| |
| 9)NOTE: PLEASE SEE 230.95,707.7D,700.26 |
| ETC. |
| PLEASE SEE A 4-POLE ATS WILL BE |
| REQUIRED. |
| PLEASE KNOW, THE GFP IS NOT REQUIRED ON |
| THE EMERGENCY/ GENERATOR SIDE OF THE EM |
| DISTRIBUTION SYSTEM, HOWEVER PLEASE SEE |
| THE ABOVE REFERENCES WHICH DO REQUIRE GF |
| SENSING. PLEASE SEE THE FOLLOWING IS |
| TAKEN DIRECTLY FROM ASCO DOCUMENTS |
| FORWARD TO ME. |
| "WHERE GROUND FAULTPROTECTION IS |
| TRIGGERED BY THE CODE AND AN ALTERNATE |
| POWER SUPPLY IS INCLUDED,SWITCHING OF |
| THE NEUTRAL BECOMES NECESSARY.THE |
| SERVICE IS LARGER THAN 1,000 AMPS. |
| CONSEQUENTLY, GROUNDFAULT PROTECTION |
| IS REQUIRED AT THE MAIN SERVICE |
| DISCONNECT AT A MINIMUM. IF ITIS |
| INSTALLED THERE AND THE GENERATOR |
| NEUTRAL GROUNDING WAS THROUGH A SOLID |
| CONNECTION TO THE MAIN SERVICE NEUTRAL, |
| A GROUND FAULT WHEN THE GENERATOR IS |
| FEEDING THE LOAD WILL CAUSE THE MAIN |
| SERVICE DISCONNECT TO OPEN. THIS WILL |
| NOTDISCONNECT THE ARCING FAULT FROM |
| THE GENERATOR. COORDINATION IS THUS |
| LOST." |
| PLEASE KNOW, IF THE MAIN IS IN THE |
| OPENING POSITION WHEN POWERM COMES BACK |
| ON, THE SENSING OF THE FPL WOULD CAUSE |
| THE ATS TO SWITCH BACK, HOWEVER THERE |
| WOULD NOT BE ANY POWER THROUGH THE |
| ELECTRICAL SYSTEM AS THE MAIN FOR THE EM |
| SYSTEM WOULD HAVE TRIPPED/OPENED. |
| PLEASE REVISE RISER AND REVISE NOTES TO |
| REFERENCE A 4-POLE TRANSFER SWITCH AND |
| INDICATING THE SEPARATELY DERIVED |
| SYSTEM. |
| |
| |
| **PLEASE SEE THE ABOVE REDLINES/PROVISO |
| ITEMS WILL NEED TO BE ADDRESSED BEFORE |
| ANY ROUGH ELECTRICAL INSPECTION IS |
| SCHEDULED. |
| ** PLEASE KNOW, ELECTRICAL PERMIT MAY BE |
| PLACED IN A "HOLD" STATUS UPON 6 MONTHS |
| TIME TABLE AND "PROVISO" HAS NOT BEEN |
| SUBMITTED. |
| |
| ** PLEASE KNOW, ANY OTHER |
| REVISIONS/DESIGN CHANGES MAY ALSO BE |
| SUBMITTED AT THAT TIME. |
| |
| |
| ** PLEASE CALL TO GO OVER SUCH ITEMS |
| LISTED ABOVE TO HELP IN EXPEDITING THIS |
| PROJECT TO A "P" STATUS. |
| |
| IF THERE ARE ANY QUESTIONS, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| ? |
2005-12-30 00:00:00 | REVIEW IN PROGRESS, FINISH FOR 12/30 |
| WILL CONTINUE ON 12/31 |
2005-12-25 00:00:00 | IN ELECTRIC FOR REVIEW. |