Date |
Text |
2006-02-23 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| ARE NUMBERED AS PER THE BUILDING PLAN |
| REVIEW OF 11/11/05: |
| |
| 4) NOTE THAT THE NOTICE OF COMMENCEMENT, |
| IMPACT FEE RECEIPT AND SPECIAL INSPECTOR |
| AGREEMENT WILL BE REQUIRED BEFORE A |
| PERMIT CAN BE ISSUED: |
| (A) THE SUBMITTED NOTICE OF |
| COMMENCEMENTSTATES "...LIMITED TO |
| CONCRETE FOUNDATION PILES ONLY".A NEW |
| ONE MUST BE RECORDED |
| (B) THE IMPACT FEE PAYMENT RECEIPT MUST |
| BE SUBMITTED.THE IMPACT FEE STAMP IS |
| CURRENTLY ON THE VOIDED COPY OF SHEET |
| A0.00 AND HAS BEEN MARKED "KEEP FOR |
| IMPACT FEE STAMP".THAT SHEET SHOULD BE |
| ATTACHED TO ONE OF THE THREE PERMIT PLAN |
| SETS. |
| (C) THE SPECIAL INSPECTOR AGREEMENT WAS |
| SUBMITTED ON A 1994 VERSION OF THE FORM |
| WHICH IS NO LONGER IN USE.THIS WILL BE |
| DISCUSSED WITH WITH THE THRESHOLD |
| INSPECTOR PROGRAM MANAGER, HAROLD |
| PISKURA, TO DETERMINE IF IT ACCEPTABLE. |
| ALTERNATIVELY, PLEASE COLLECT A CURRENT |
| FORM (JULY 1, 2004 VERSION) FROM THIS |
| OFFICE, HAVE IT COMPLETED WITH ORIGINAL |
| SIGNATURES (NOTARIZED OR SEALED AS |
| APPROPRIATE) AND THEN SUBMIT IT. |
| |
| 10) PRODUCT APPROVALS: |
| (A) NONE OF THE SUBMITTED PRODUCT |
| APPROVALS INCLUDE THE STATEWIDE PRODUCT |
| APPROVAL OR LOCAL PRODUCT APPROVAL COVER |
| SHEET REQUIRED TO DEMONSTRATE COMPLIANCE |
| WITH FLORIDA ADMINISTRATIVE CODE RULE |
| 9B-72.FOR MORE DETAILS, SEE THE NOTE |
| AT THE END OF THE PRODUCT APPROVAL |
| COMMENTS. |
| (B) ROOF TILE. THE WIND UPLIFT |
| PRESSURES SHOWN ON ARCHITECTURAL PLAN, |
| SHEET A1.02, FOR THE TILED ROOF AREAS, |
| ARE UP TO 150 PSF (UPLIFT).SHEET 2 OF |
| THE SUBMITTED MONIER LIFETILE SPANISH |
| 'S' CONCRETE ROOF TILE PRODUCT APPROVAL |
| NOA# 02-1205.07 STATES THAT THE PRODUCT |
| IS FOR USE IN LOCATIONS WERE THE DESIGN |
| PRESSURES DO NOT EXCEED THOSE OBTAINED |
| BY CALCULATIONS IN COMPLIANCE WITH RAS |
| 127.SUBMIT CALCULATIONS (SEE RAS 127) |
| TO SHOW THAT THE PROPOSED ROOF TILE IS |
| SUITABLE FOR THE UPLIFT PRESSURES OF |
| THIS APPLICATION. |
| ALSO, SHEET A8.23. DETAILS 3, 4, AND 5 |
| REFER TO THE STRUCTURAL PLANS FOR |
| THICKNESS OF DENSE DECK AND ATTACHMENT |
| OF TILES.THIS INFORMATION COULD NOT BE |
| FOUND ON THE STRUCTURAL PLANS.SUBMIT |
| DETAILS. THE NOTES ON SHEET S-1.25 REFER |
| TO THE USE OF FIRE-RETARDANT TREATED |
| PLYWOOD WHICH IS IN CONFLICT WITH THE |
| ARCHITECTURAL PLANS AND IS NOT A |
| PERMITTED MATERIAL FOR USE IN |
| CONSTRUCTION TYPE I.AMEND THE |
| STRUCTURAL PLANS. |
| EITHER A STATEWIDE PRODUCT APPROVAL, OR |
| LOCAL PRODUCT APPROVAL, COVER SHEET |
| SHALL BE SUBMITTED WITH EACH COPY, SEE |
| COMMENT (A) ABOVE. |
| (C) MODIFIED BITUMEN ROOFING SYSTEM. |
| EITHER A STATEWIDE PRODUCT APPROVAL, OR |
| LOCAL PRODUCT APPROVAL, COVER SHEET |
| SHALL BE INCLUDED WITH EACH COPY OF THE |
| SUBMITTED JOHNS MANVILLE CORP. MODIFIED |
| BITUMEN ROOFING SYSTEM PRODUCT APPROVAL |
| NOA# 04-0401.04, SEE COMMENT (A) ABOVE. |
| (D) LOADING AREA SECTIONAL DOOR S28. |
| NO PRODUCT APPROVAL WAS SUBMITTED FOR |
| THIS DOOR.SUBMIT A PRODUCT APPROVAL |
| FOR THIS 14'-0" X 16'-0" SECTIONAL DOOR. |
| (E) TRASH TERMINATION/HOLDING/WASTE |
| CONTAINER ROOM DOORS.THESE DOORS ARE |
| ON THE PARKING GARAGE VEHICLE ENTRY |
| DRIVEWAY AND SO WILL BE SUBJECT TO WIND |
| PRESSURES.SHEET A9.11, DOOR SCHEDULE, |
| SHOWS EACH OF THESE DOORS AS A PAIR OF |
| 6' WIDE DOORS.NO PRODUCT APPROVAL WAS |
| SUBMITTED FOR A DOOR OF THIS WIDTH. |
| AMEND THE DOOR SCHEDULE OR SUBMIT AN |
| APPROPRIATE PRODUCT APPROVAL. |
| (F) STAIRWELL DOORS S1, R1 AND R15. |
| SHEET A9.11, DOOR SCHEDULE, SHOWS THESE |
| DOORS AS TYPE I, WHICH HAS A 10"X 10" |
| VISION PANEL.NO PRODUCT APPROVAL HAS |
| BEEN SUBMITTED FOR A HOLLOW METAL DOOR |
| WITH VISION PANEL.SUBMIT A PRODUCT |
| APPROVAL. |
| (G) STEAM ROOM DOOR.THIS DOOR IS |
| REFERENCED R14 ON SHEET A9.11 (DOOR |
| SCHEDULE).IS IT THE SAME DOOR THAT IS |
| CALLED UP AS DOOR R4 ON SHEET 4.72?THE |
| DOOR SCHEDULE SHOWS DOOR R14 AS TYPE R, |
| WHICH IS SHOWN AS "SUN-DOR-CO #SD-502". |
| THAT MANUFACTURER AND REFERENCE DOES NOT |
| CORRELATE WITH THE SUBMITTED ARCH |
| ALUMINUM MEDIUM STILE ALUMINUM DOOR |
| PRODUCT APPROVAL NOA# 01-1102.01. |
| CLARIFY THE DOOR REFERENCE NUMBER ON |
| SHEET A9.1 OR A4.72 AND REMOVE THE |
| INCORRECT DOOR MANUFACTURER REFERENCE |
| FOR DOOR R14. |
| (H) LOBBY GARAGE ENTRY DOOR P8.SHEET |
| A9.11, DOOR SCHEDULE, SHOWS THIS DOOR AS |
| TYPE S (SOLID CORE WOOD DOOR).SHEET |
| A4.14 SHOWS THE DOOR LEADING FROM THE |
| GARAGE INTO THE CONDITIONED SPACE.THE |
| GARAGE IS OPEN AT THE VEHICLE ENTRY |
| DRIVEWAYS, SO DOOR P8 WILL BE SUBJECT TO |
| WIND PRESSURES. SUBMIT A PRODUCT |
| APPROVAL FOR THIS DOOR TYPE OR REVISE |
| THE SHEET A4.14 AND THE DOOR SCHEDULE |
| (SHEET A9.11).NOTE THAT THIS DOOR IS |
| ALSO REQUIED TO BE 1-1/2 HOUR FIRE |
| RATED. |
| (I) LOUVERS, SHEET A8.44.NO PRODUCT |
| APPROVALS WERE SUBMITTED FOR THE |
| LOUVERS.SUBMIT APPROPRIATE PRODUCT |
| APPROVALS. |
| (J) WINDOW, STORE FRONT AND SLIDING |
| GLASS DOOR PRODUCT APPROVALS.IN |
| ADDITION TO THE COMMENTS BELOW, PLEASE |
| NOTE THAT, ACCORDING TO THE WIND |
| PRESSURES STATED ON ARCHITECTURAL PLAN |
| SHEET A1.02, SOME OF THESE PRODUCTS WILL |
| BEREQUIRED TO HAVE A DESIGN PRESSURE |
| RATING OF UP TO +100 PSF (POSITIVE) AND |
| -140 PSF (NEGATIVE).IT WOULD APPEAR |
| THAT THE SUBMITTED PRODUCT APPROVALS |
| WERE NOT CHECKED, PRIOR TO SUBMITTAL, TO |
| ENSURE THAT THE PROPOSED PRODUCTS CAN |
| WITHSTAND THE STATED WIND PRESSURES FOR |
| THIS BUILDING.PLEASE CHECK THE DESIGN |
| PRESSURE RATING OF ALL PRODUCT |
| APPROVALS, PRIOR TO SUBMITTAL. |
| (K) WINDOW WALL.THE SUBMITTED GAMMA |
| U.S.A. SERIES 50.2 SMALL MISSILE IMPACT |
| WINDOW WALL PRODUCT APPROVAL NO. 03-0345 |
| AND SERIES 61 LARGE MISSILE IMPACT |
| WINDOW WALL PRODUCT APPROVAL NO. 03-0348 |
| BOTH STATE, ON THEIR RESPECTIVE COVER |
| SHEETS, THAT THEY ARE "ONE-TIME PRODUCT |
| APPROVAL" APPLICATIONS FOR A PROJECT |
| CALLED "JADE RESIDENCE" 1331 BRICKELL |
| BAY DR, MIAMI, FL.THESE PRODUCT |
| APPROVALS ARE NOT VALID FOR OTHER |
| PROJECTS.SUBMIT VALID PRODUCT |
| APPROVALS. |
| (L) WINDOW WALL.THE DRAWING SHEETS 1 |
| TO 8 SUBMITTED AS PART OF THE GAMMA |
| U.S.A. SERIES 50.4A SMALL MISSILE IMPACT |
| WINDOW WALL PRODUCT APPROVAL NOA# |
| 04-1006.01 ARE NOT COPIES OF THE ONES |
| REVIEWED BY MIAMI-DADE CODE |
| COMPLIANCE OFFICE (BCCO).UNLIKE THE |
| DRAWINGS INCLUDED WITH THIS PRODUCT |
| APPROVAL ON THE MIAMI-DADE BCCO WEBSITE, |
| THEY DO NOT HAVE THE MIAMI-DADE BCCO |
| APPROVAL STAMP.SUBMIT PRODUCT |
| APPROVALS WITH DRAWINGS THAT INCLUDE THE |
| PRODUCT CERTIFICATION AGENCY STAMP OF |
| APPROVAL.ALSO, SEE COMMENT (J) ABOVE |
| AND COMMENT (A) ABOVE. |
| (M) WINDOW WALL WITH TILT WINDOW. |
| SUBMITTAL OF FENESTRATION TESTING |
| LABORATORY (FTL) REPORT 02-0729.01, FOR |
| GAMMA U.S.A SERIES 55.2 WINDOW WALL WITH |
| TILT WINDOW, IS NOTED BUT THIS IS NOT A |
| PRODUCT APPROVAL. SUBMIT A PRODUCT |
| APPROVAL FROM AN APPROVED PRODUCT |
| CERTIFICATION AGENCY, SEE COMMENT (A) |
| ABOVE. |
| (N) GAMMA U.S.A SERIES 73 SLIDING GLASS |
| DOOR. SUBMITTAL OF FENESTRATION TESTING |
| LABORATORY (FTL) REPORT 03-0821.01, IS |
| NOTED BUT THIS IS NOT A PRODUCT |
| APPROVAL. SUBMIT A PRODUCT APPROVAL FROM |
| AN APPROVED PRODUCT CERTIFICATION |
| AGENCY, SEE COMMENT (A) ABOVE. |
| (O) GAMMA U.S.A SERIES 76 ALDORA |
| ALUMINUM SLIDING GLASS DOOR.THE |
| DRAWING SHEETS 1 TO 8 SUBMITTED AS PART |
| OF THE PRODUCT APPROVAL NOA# |
| 04-1006.03 ARE NOT COPIES OF THE ONES |
| REVIEWED BY MIAMI-DADE CODE COMPLIANCE |
| OFFICE (BCCO).UNLIKE THE DRAWINGS |
| INCLUDED WITH THIS PRODUCT APPROVAL ON |
| THE MIAMI-DADE BCCO WEBSITE, THEY DO NOT |
| HAVE THE MIAMI-DADE BCCO APPROVAL STAMP. |
| SUBMIT PRODUCT APPROVALS WITH DRAWINGS |
| THAT INCLUDE THE PRODUCT CERTIFICATION |
| AGENCY STAMP OF APPROVAL.ALSO, SEE |
| COMMENT (J) ABOVE AND COMMENT (A) ABOVE. |
| |
| NOTE: FL. ADMIN CODE RULE 9B-72 (IN |
| EFFECT SINCE OCTOBER 1, 2003) REQUIRES |
| THAT PRODUCTS HAVE STATEWIDE, LOCAL OR |
| SITE-SPECIFIC PRODUCT APPROVAL.THE |
| SUBMITTAL SHOULD INCLUDE THE STATEWIDE |
| PRODUCT APPROVAL NUMBER (FL###), |
| AVAILABLE FROM THE DEPT OF COMMUNITY |
| AFFAIRS PRODUCT APPROVAL WEBSITE WWW. |
| FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX |
| FOR PRODUCTS WHICH DO NOT HAVE STATEWIDE |
| PRODUCT APPROVAL, LOCAL PRODUCT APPROVAL |
| CAN BE ACHIEVED IF THERE IS A QUALITY |
| ASSURANCE PROGRAM IN PLACE WITH A STATE |
| APPROVED QUALITY ASSURANCE ENTITY. |
| LOCAL PRODUCT APPROVAL WILL ALLOW A |
| PRODUCT TO BE USED, IN ACCORDANCE WITH |
| THE TEST CRITERIA, THROUGHOUT THE |
| JURISDICTION OF WEST PALM BEACH. |
| LOCAL AND SITE SPECIFIC PRODUCT APPROVAL |
| APPLICATION FORMS ARE AVAILABLE FROM |
| THIS OFFICE.APPROVED QUALITY ASSURANCE |
| ENTITIES ARE LISTED ON THE DCA WEBSITE: |
| FLORIDABUILDING.ORG/PR/PR_ORG_SRCH.ASPX |
| |
| 25) NFPA 823-2.4.3.1REFUSE CHUTE. |
| THIS COMMENT HAS NOT BEEN ADDESSED. THE |
| COMMENT RESPONSE REFERING TO APPROVAL BY |
| THE CONSTRUCTION BOARD OF ADJUSTMENTS |
| AND APPEALS (CBAA) IS NOTED.PLEASE |
| SUBMIT A COPY OF THE CBAA FINAL |
| DECISION, FOR THE PERMIT FILE,SO THAT |
| IT MAY BE DEEMED UNNECESSARY, FOR THIS |
| PROJECT ONLY, TO PROVIDE A MINIMUM 6" |
| CLEARANCE BETWEEN THE OPEN CHUTE LOADING |
| DOOR AND CLOSED SERVICE OPENING ROOM |
| DOOR. |
| |
| 43) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL INFO |
| TELEPHONE: (561) 805 6652ROBERT BROWN |
| E-MAIL: [email protected] |