2007-10-25 18:28:12 | REVISION 16 |
| |
| FBC 2001 CODES W/ 2003 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE |
| AND PASSED: |
| M6.03 |
| |
| THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE |
| AND WERE DENIED WITH COMMENTS: |
| |
| M2.27: UNIT M, HER WALK-IN-CLOSET, THERE IS A RETURN |
| GRILL SHOWN IN THE CEILING AT A LOCATION WHERE THERE IS |
| NO PLENUM. WHAT IS THE PURPOSE OF THE GRILL? ALSO, |
| PLEASE VERIFY THAT IT IS THE INTENDED DESIGN FOR THERE |
| TO BE RETURNS IN CLOSETS AND LAUNDRY ROOM. BALANCED |
| RETURN FROM THESE AREAS IS NOT REQUIRED. THIS CONDITION |
| OCCURS ON OTHER PAGES AS WELL. |
| |
| M2.29: UNIT-S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO |
| BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3. |
| HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING |
| MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW |
| HOW THIS IS TO BE ACCOMPLISHED. |
| NOTE: UNIT-P1, HPU-1 AND HPU-6 REQUIRE FAN SHUT-DOWN BY |
| SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2. |
| |
| M2.32A: NOTE ON PLAN STATES "SHADED AREA IS A RETURN |
| AIR PLENUM (TYPICAL)." HOWEVER, THERE ARE NO SHADED |
| PLENUM AREAS ON PLAN. PLEASE CORRECT. FBC,M 602.2 |
| |
| M2.32C: UNIT P1, 12X8 RETURN TRANSFER FOR MASTER |
| BEDROOM IS TOO SMALL TO MEET THE BALANCED RETURN |
| EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT |
| DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE |
| REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE |
| DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED |
| BY THIS SECTION. |
| |
| M2.32C: UNIT R1, BEDROOM 3/DEN HAS NO RETURN. SHOW |
| BALANCED RETURN IN ACCORDANCE WITH FBC,M 601.4. |
| |
| M2.32C: UNIT S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO |
| BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3. |
| HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING |
| MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW |
| HOW THIS IS TO BE ACCOMPLISHED. ALSO, THE BRANCH DUCT |
| FEEDING BEDROOM 2 AND THE BATHROOM IS MISSING SIZE. |
| PLEASE CORRECT. FBC,M 601.1. |
| |