2007-10-25 18:28:12REVISION 16
  
 FBC 2001 CODES W/ 2003 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE
 AND PASSED:
 M6.03
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 AND WERE DENIED WITH COMMENTS:
  
 M2.27: UNIT M, HER WALK-IN-CLOSET, THERE IS A RETURN
 GRILL SHOWN IN THE CEILING AT A LOCATION WHERE THERE IS
 NO PLENUM. WHAT IS THE PURPOSE OF THE GRILL? ALSO,
 PLEASE VERIFY THAT IT IS THE INTENDED DESIGN FOR THERE
 TO BE RETURNS IN CLOSETS AND LAUNDRY ROOM. BALANCED
 RETURN FROM THESE AREAS IS NOT REQUIRED. THIS CONDITION
 OCCURS ON OTHER PAGES AS WELL.
  
 M2.29: UNIT-S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED.
 NOTE: UNIT-P1, HPU-1 AND HPU-6 REQUIRE FAN SHUT-DOWN BY
 SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2.
  
 M2.32A: NOTE ON PLAN STATES "SHADED AREA IS A RETURN
 AIR PLENUM (TYPICAL)." HOWEVER, THERE ARE NO SHADED
 PLENUM AREAS ON PLAN. PLEASE CORRECT. FBC,M 602.2
  
 M2.32C: UNIT P1, 12X8 RETURN TRANSFER FOR MASTER
 BEDROOM IS TOO SMALL TO MEET THE BALANCED RETURN
 EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT
 DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE
 REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE
 DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED
 BY THIS SECTION.
  
 M2.32C: UNIT R1, BEDROOM 3/DEN HAS NO RETURN. SHOW
 BALANCED RETURN IN ACCORDANCE WITH FBC,M 601.4.
  
 M2.32C: UNIT S, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED. ALSO, THE BRANCH DUCT
 FEEDING BEDROOM 2 AND THE BATHROOM IS MISSING SIZE.
 PLEASE CORRECT. FBC,M 601.1.
  