Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
B |
Sequence Number |
378 |
|
Notes |
Date |
Text |
2008-02-01 16:07:25 | REVIEW: FBC 2001SUBMITTAL #05100.01 | | ACTION: DENIED 2-1-08 | | | | 1) 106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS THAT | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND | | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. SUBMIT PRODUCT | | APPROVAL FOR THE ?HARDISOFFIT?. IN THE PRODUCT APPROVAL | | PACKAGE CIRCLE ALL ITEMS AND TABLES APPLICABLE TO THE | | INSTALLATION OF THE PRODUCT. | | | | 2) PROVIDE THE FASTENER SPACING WHICH WILL MEET THE | | DESIGN PRESSURES FOR THOSE AREAS WHERE THE | | ?HARDISOFFIT? WILL BE INSTALLED. ALL INFORMATION | | SUBMITTED FOR OUR RECORD RETENTION PROGRAM SHALL BE | | CLEAR, LEGIBLE AND NO ?WHITE-OUT? CHANGES ALLOWED. THE | | INFORMATION FOR THE ?HARDISOFFIT? IS ILLEGIBLE WPB | | AMENDMENTS 106.1.3. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | (561)805-6726 | | [email protected] |
|