Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop M
Sequence Number 37
Notes
Date Text
2007-10-25 18:10:05REVISION 15
  
 FBC 2001 CODES W/ 2003 SUPPLEMENTS
  
 THE FOLLOWING PAGES WERE NOT REVIEWED AS PART OF REV15
 BECAUSE THEY WERE SUPERCEDED PRIOR TO REVIEW:
 M2.27 SUPERCEDED BY REV16
 M2.29 SUPERCEDED BY REV16
 M2.32A SUPERCEDED BY REV16
 M2.32C SUPERCEDED BY REV16
 M6.03 SUPERCEDED BY REV16
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 AND PASSED:
 M2.05
 M2.06
 M2.19
 M2.19B
 M2.20A
 M2.28
 M3.02
 M3.03
 M3.04
 M4.02
  
 THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE
 AND DENIED WITH COMMENTS:
  
 M2.18: TOILET AND DRYER EXHAUST IN UNIT V1 ARE
 TERMINATING AT "CUBE CORE" GRILLS. ARE THESE LISTED FOR
 USE ON DRYER EXHAUST? WHERE WILL THE BACKDRAFT DAMPER
 FOR THE DRYER EXHAUST BE LOCATED? WHY IS THERE AN
 INLINE BACKDRAFT DAMPER IN THE TOILET EXHAUST DUCT?
 THERE IS NO DETAIL FOR THIS TYPE OF TERMINATION AT
 DRYER AND TOILET EXHAUST. THIS IS THE SECOND TIME THIS
 INFORMATION IS BEING REQUESTED. SHOW COMPLIANCE WITH
 FBC,M 401.5 AND 504.4.
  
 M2.20: MECHANICAL CLOSET FOR HPU-5-3 IS SHOWN AS A
 PLENUM. DISCHARGE EXHAUST DUCT FOR EF-5-2 IS ROUTED
 THROUGH THIS PLENUM. EXHAUST DUCTS UNDER POSITIVE
 PRESSURE SHALL NOT BE LOCATED IN A PLENUM IN ACCORDANCE
 WITH FBC,M 601.3. SHOW HOW THIS DUCT IS TO BE ISOLATED
 FROM PLENUM.
  
 M2.30: UNIT-P, HPU-1 AND HPU-5 REQUIRE FAN SHUT DOWN BY
 SMOKE DETECTOR IN ACCORDANCE WITH FBC,M 606.2.2.
  
 M2.31: UNIT-T, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED.
  
 M2.32: UNIT-U, 12X6 RETURN DUCT IN BEDROOM 2 DOES NOT
 ATTACH TO PLENUM. HOW WILL RETURN AIR GET FROM BEDROOM
 TO PLENUM? SHOW COMPLIANCE WITH FBC,M 601.4. ALSO, WHY
 US THERE A RETURN IN THE LAUNDRY ROOM? BALANCED RETURN
 IS NOT REQUIRED FROM THIS AREA UNDER THIS SECTION.
  
 M2.32B: UNIT P2, SUPPLY FLEX IN BEDROOM 2 IS MISSING
 SIZE. PLEASE CORRECT. FBC,M 601.1
  
 M2.23D: UNIT P, RETURN TRANSFERS FROM MASTER BEDROOM
 AND BEDROOM 2 ARE TOO SMALL TO MEET THE BALANCED RETURN
 EXCEPTIONS UNDER FBC,M 601.4. IF TRANSFERS ARE NOT
 DESIGNED TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE
 REQUIRED AT FNAL INSPECTION TO VERIFY PRESSURE
 DIFFERENTIALS ARE LESS THAN 0.01 INCHES W.C AS REQUIRED
 BY THIS SECTION. ALSO, NOTE ON PLAN CALLS FOR EXHAUST
 DUCT TO BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M
 601.3. HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE
 CEILING MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM.
 PLEASE SHOW HOW THIS IS TO BE ACCOMPLISHED.
  
 M2.32D: UNIT R, RETURN TRANSFER FOR MASTER BEDROOM IS
 TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS UNDER
 FBC,M 601.4. IF TRANSFERS ARE NOT DESIGNED TO MEET
 THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT FNAL
 INSPECTION TO VERIFY PRESSURE DIFFERENTIALS ARE LESS
 THAN 0.01 INCHES W.C AS REQUIRED BY THIS SECTION.
  
 M2.32D: UNIT S, THE RETURN TRANSFER FOR BEDROOM 2 IS
 GOING INTO THE BATHROOM, THEREFORE THE AIR IS NOT BEING
 RETURNED TO THE HPU. PLEASE CORRECT AND SHOW COMPLIANCE
 WITH FBC,M 601.3. ALSO, THE PLENUM AREA ABOVE THE
 CEILING IS NOT DEFINED ON THE FLOOR PLAN. PLEASE
 CORRECT. FBC,M 602.2
  
 M2.32E: UNIT T, NOTE ON PLAN CALLS FOR EXHAUST DUCT TO
 BE BOXED OUT OF PLENUM TO COMPLY WITH FBC,M 601.3.
 HOWEVER, THIS MAY NOT BE FEASIBLE WHEN THE CEILING
 MOUNTED EXHAUST FAN IS ALSO IN THE PLENUM. PLEASE SHOW
 HOW THIS IS TO BE ACCOMPLISHED.
  
 M2.32F: UNIT U, 12X6 RETURN DUCT IN BEDROOM 2 IS NOT
 ATTACHED TO PLENUM. PLEASE CORRECT AND SHOW COMPLIANCE
 WITH FBC,M 601.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  
  