Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop M
Sequence Number 36
Notes
Date Text
2007-10-25 16:29:37MECH REVISION 14
  
 FBC 2001 CODES W/ 2003 SUPPLEMENTS
  
 THE FOLLOWING PAGES WERE NOT REVIEWED BECUASE THEY WERE
 SUPERCEDED PRIOR TO REVIEW OF REV 14:
 M2.06 SUPERCEDED BY REV15
 M4.02 SUPERCEDED BY REV15
 M6.03 SUPERCEDED BY REV16
  
 THE FOLLOWING PAGES WERE REVIEWED FOR CODE COMPLIANCE
 AND PASSED:
 M2.01
 M2.02
 M2.03
 M2.04
 M2.07
 M2.09
 M2.10
 M2.11
 M2.12
 M2.13 REV.12
 M2.17 REV.12
 M2.26B
 M2.26D
 M2.26F
 M4.01
 M4.03
 M5.01
 M6.01
  
 THE FOLLOWING PAGE(S) WERE REVIEWED FOR CODE COMPLIANCE
 AND DENIED WITH COMMENTS:
  
 M2.08: 6X6 SUPPLY DUCT FROM HPU-P3-4 IS PASSING THROUGH
 A RATED WALL. NOTE ON PLAN CLAIMS AN EXCEPTION TO THE
 REQUIREMENT FOR A FIRE DAMPER PER FBC,M 607.1.3.
 HOWEVER, UNDER EXCEPTION #3 THE DUCT IS REQUIRED TO BE
 INSTALLED ABOVE A CEILING. THE STORAGE AREAS DO NOT
 HAVE A CEILING, THEREFORE A FIRE DAMPER IS REQUIRED AT
 THIS DUCT PENETRATION OF THE RATED WALL.
  
 M2.26A: UNIT C, RETURN TRANSFER (8IN. ROUND) IN BEDROOM
 2 IS TOO SMALL TO MEET THE BALANCED RETURN EXCEPTIONS
 UNDER FBC,M 601.4. IF TRANSFERS ARE NOT DESIGNED TO
 MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT
 FNAL INSPECTION TO VERIFY PRESSURE DIFFERENTIALS ARE
 LESS THAN 0.01 INCHES W.C AS REQUIRED BY THIS SECTION.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]