Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop M
Sequence Number 33
Notes
Date Text
2007-08-17 11:21:58REV 13R
 THE FOLLOWING PAGES WERE REVIEWED AND PASSED:
 M2.12, M2.25, M2.26C, M2.26E
  
 THE FOLLOWING PAGES WERE DENIED WITH COMMENTS:
 M2.22, M2.26A, M2.26B, M2.26D, M2.26F
  
 ONE COPY OF PASSED PAGES WAS RETAINED FOR PERMIT
 RECORDS. ONE COPY OF DENIDE PAGES WAS RED-LINED TO
 ASSIST IN UNDERSTANDING THE LOCATION AND NATURE OF
 WRITTEN REVIEW COMMENTS.
  
 1. M2.22 UNIT D1: THERE IS NO RETURN GRILL IN THE
 PLENUM. PLEASE CORRECT.
  
 2. M2.26A-
 UNITS C AND L: MISSING RETURNS IN BEDROOM #2. FBC,M
 601.4
 UNITS B5 AND B6: PLAN SHOWS 14X14 R/A IN CEILING OF
 MASTER BEDROOM FOR WHAT PURPOSE? PLEASE CLARIFY.
  
 3. M2.26B-
 UNIT G1: CONTAINS NOTE FOR FLEX DUCT TO OFFSET DRYER
 EXHAUST. FLEX DUCT SHALL NOT BE USED IN CONCEALED
 SPACES. FBC,M 504.6. ALSO IN G1, 16X16 R/A GRILL IN
 MASTER BEDROOM HAS NO DUCT OR PLENUM OR OTHER WAY FOR
 AIR TO RETURN FROM ROOM.
 UNIT D1, THERE IS NO RETURN GRILL IN PLENUM CEILING.
 UNIT C2, 12X12 R/A FOR MASTER BEDROOM IS NOT LOCATED
 WITHIN THE CEILING PLENUM SPACE.
  
 4. M2.26D UNIT J: THERE IS NO DEFINED CEILING PLENUM
 AREA SHOWN ON PLAN. PLEASE CORRECT.
  
 5. M2.26F UNIT C1: NO FIRE RATING OR OPENING
 PROTECTIVES ARE SHOWN WHERE THE PLENUM EXTENDS INTO THE
 CORRIDOR. PLEASE CORRECT.
  