Text |
2007-08-17 11:21:58 | REV 13R |
| THE FOLLOWING PAGES WERE REVIEWED AND PASSED: |
| M2.12, M2.25, M2.26C, M2.26E |
| |
| THE FOLLOWING PAGES WERE DENIED WITH COMMENTS: |
| M2.22, M2.26A, M2.26B, M2.26D, M2.26F |
| |
| ONE COPY OF PASSED PAGES WAS RETAINED FOR PERMIT |
| RECORDS. ONE COPY OF DENIDE PAGES WAS RED-LINED TO |
| ASSIST IN UNDERSTANDING THE LOCATION AND NATURE OF |
| WRITTEN REVIEW COMMENTS. |
| |
| 1. M2.22 UNIT D1: THERE IS NO RETURN GRILL IN THE |
| PLENUM. PLEASE CORRECT. |
| |
| 2. M2.26A- |
| UNITS C AND L: MISSING RETURNS IN BEDROOM #2. FBC,M |
| 601.4 |
| UNITS B5 AND B6: PLAN SHOWS 14X14 R/A IN CEILING OF |
| MASTER BEDROOM FOR WHAT PURPOSE? PLEASE CLARIFY. |
| |
| 3. M2.26B- |
| UNIT G1: CONTAINS NOTE FOR FLEX DUCT TO OFFSET DRYER |
| EXHAUST. FLEX DUCT SHALL NOT BE USED IN CONCEALED |
| SPACES. FBC,M 504.6. ALSO IN G1, 16X16 R/A GRILL IN |
| MASTER BEDROOM HAS NO DUCT OR PLENUM OR OTHER WAY FOR |
| AIR TO RETURN FROM ROOM. |
| UNIT D1, THERE IS NO RETURN GRILL IN PLENUM CEILING. |
| UNIT C2, 12X12 R/A FOR MASTER BEDROOM IS NOT LOCATED |
| WITHIN THE CEILING PLENUM SPACE. |
| |
| 4. M2.26D UNIT J: THERE IS NO DEFINED CEILING PLENUM |
| AREA SHOWN ON PLAN. PLEASE CORRECT. |
| |
| 5. M2.26F UNIT C1: NO FIRE RATING OR OPENING |
| PROTECTIVES ARE SHOWN WHERE THE PLENUM EXTENDS INTO THE |
| CORRIDOR. PLEASE CORRECT. |
| |