2008-03-15 21:01:21 | PG. E2.02THE TWO A/CS IN P1 SHOW OCP THAT |
| VIOLATES THE NAMEPLATE OF THE UNITS PLEASE CORRECT OCP |
| FOR UNITS |
| |
| PG. E2.02SHOWS TWO SWITCHES TO FIXTURES ABOVE, |
| ARE THESE FIXTURES IN THE SAME ROOM? PLAN IS |
| CONFUSING. |
| |
| PG. E4.01 COMMUNICATION ROOM SHOW TAILS TO |
| EQUIPMENT, HOW DO YOU KNOW TAILS WILL BE LARGE ENOUGH |
| (AMPEREAGE)? |
| YOU WILL NEED TO SUPPLY |
| EQUIPMENT DETAILS FOR SIZING BRANCH CIRCUITS.ALSOL |
| NEED TO SHOW EQUIPMENT ON PLANS. |
| |
| PG. E6.01LOOKING AT REV1 FOR THE GENERATOR SHOWS |
| TWO BREAKERS BUILTIN, ON JOB ONE WAS ADDED TO |
| GENERATOR, PLEASE HAVE GENERATOR RELISTED TO SHOW ONE |
| INTERNAL |
| AND ONE EXTERNAL. |
| |
| PG. E6.08, E6.09SHOWS TWO 4" CONDUITS STUBBING INTO |
| THE CORIDOOR CEILING, DO YOU WANT ACCESS PANELS IN THE |
| CORIDOOR CEILING TO BE ABLE TO ACCESS PIPES? |
| SHOWS A 20 DEDICATED |
| CIRCUIT TO COMMUNICATIONS PANEL IN BEDROOM CLOSET. THIS |
| NEEDS TO BE AFCI PROTECTED.210.12 |
| SHOWS A CADWELL PLATE FOR |
| GROUNDING, IS THIS JUST A TYPE OR ARE THE WIRES TO BE |
| CADWELDED TO THIS BAR? |
| |
| PG. E7.14TRANSFORMER THAT FEEDS LGHE IS PROTECTED ON |
| PRIMARY BY 3 POLE 25A BREAKER, AND SECONDARY HAS 100A. |
| THERE IS NOT A 100A AVAILABLE ON THE SECONDARY SIDE |
| PRIMARY HAS ROOM FOR 2.7 AMPERES. I WILL LOOK INTO THIS |
| FURTHER AND GET BACK TO YOU BUT I DON'T FEEL THAT THE |
| SECONDARY SHOULD BE PROTECTED BY 100A MAIN |
| WHEN THERE IS NO ROOM FOR FUTURE |
| EXPANSION.IF LOAD GOES TO 100% THE 25AMP MAIN SHOULD |
| TRIP. |