Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
B |
Sequence Number |
309 |
|
Notes |
Date |
Text |
2007-06-24 16:39:54 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | SUBMITTAL ON 6/5/07 FOR ENGINEERING CALCS FOR | | ADDITIONAL FASTENERS, WITHOUT SHIMS, TO ADDRESS FIELD | | VARIATIONS ON WINDOW AND SGD HEAD AND JAMB GAPS. | | | | 1)FBC 1606.1ALL FASTENER LOCATIONS SHALL | | INCORPORATE SHIMS TO REDUCE FASTENER ROTATION, AND | | REDUCE THE RISK OF FASTENERS BACKING OUT DUE TO CYCLIC | | WIND LOADING. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | |
|