2007-06-18 09:47:17FBC 2001
  
 SUBMITTAL #05100.02. ONLY SOME OF THE INFORMATION
 SUBMITTED WILL BE APPROVED. THOSE ITEMS WHICH ARE
 APPROVED WILL BE STAMPED. THE OTHER ITEMS WILL BE
 RETUNED. THE SUBMITTALS BY KENNETH J. PAGANO, PE #58131
 ARE OK.THE INFORMATION BY SCOTT L. SCHURWAN PE
 #31867, IS MISSING THE PRINTED NAME AND NUMBER/THE DATE
 AND THE SIGNATURE ON SOME OF THE SUBMITTALS WERE
 STAMPED WHICH IS NOT ACCEPTABLE. SEE F.A.C.
 61G15-23.002(1)A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS, FINAL BID DOCUMENTS BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 (2) A COVER OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL
 ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX SO THAT THE USER WILL BE AWARE OF EACH
 PORTION OF THE SPECIFICATION FOR WHICH EACH
 PROFESSIONAL ENGINEER IS RESPONSIBLE. SEE F.A.C.
 61G15-23.002
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  