Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
M |
Sequence Number |
30 |
|
Notes |
Date |
Text |
2007-07-02 15:11:07 | FAN SHUT-DOWN VIA DUCT OR AREA SMOKE DETECTOR IS | | REQUIRED IN ALL UNITS WHICH HAVE HPU-4 AS SHOWN ON | | EQUIPMENT SCHEDULE (M5.01) WITH A SUPERVISORY SIGNAL AT | | A CONSTANTLY ATTENDED LOCATION. | | ALSO, PLEASE PROVIDE DOCUMENTATION SHOWING HPU-5 WITHIN | | RANGE OF CFM'S REQUIRED ON FLOOR PLAN BASED ON ACTUAL | | E.S.P. IN UNTS D AND D1. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|