Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop P
Sequence Number 3
Notes
Date Text
2005-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW:
  
 4) SHT A2.10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY STORM DRAINS FOR
 THE 5TH FLOOR OPEN AREAS PER SECTIONS
 1106 & 1107. SHOW THE LOCATIONS FOR ALL
 PRIMARY AND SECONDARY DRAINS. RESPONSE
 NOTED, BUT NO CALCULATIONS WERE
 INDICATED OR FOUND. SECONDARY DRAINS
 WERE NOT LOCATED FOR ALL AREAS. SECTION
 104.2.1.
 10) ALL SHEETS FOR UNITS, SHOW THE
 OPENING SIZE FOR ALL W/C'S AND SHOW THE
 W/C TO BE 18" FROM THE CENTER LINE OF
 THE FIXTURE TO THE WALL WHERE
 APPLICABLE. RESPONSE NOTED, BUT NOT ALL
 UNITS SHOW THE REQUIREMENT. SECTION
 104.2.1. - ALL SHEETS WHERE NO PIPING
 LAYOUT IS SHOWN, INDICATE WHERE THE
 PIPING LAYOUT CAN BE LOCATED ON THAT
 SHEET. - DOOR SIZE NOT ASKED FOR.
 11) ALL SHEETS FOR UNITS, INDICATE
 SPECIFICATION "A" OR "B" AS REQUIRED BY
 THE FHA-98 DESIGN MANUAL FOR EACH UNIT.
 RESPONSE NOTED, BUT NOT UNITS SHOW
 SPECIFICATION "A" OR "B". SECTION
 104.2.1. - STILL NOT ALL UNITS SHOW THIS
 REQUIREMENT.
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND. - THIS WILL BE A FIELD
 INSPECTOR APPROVAL. IF COMMON USE AREA
 IS AVAILABLE TO TENANTS AND GUESTS, ALL
 REQUIREMENTS OF SECTION 11-4.24 WILL BE
 ADHERED TO.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW THE
 SQUARE FOOTAGE OF EACH AREA DRAINED WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS SHOWN ADDED TO THE ROOF AREA.
 ALSO SHOW THE AREA OF UPPER ROOFS
 DRAINING ONTO EACH AREA ADDED TO THE SF
 IN CALCULATIONS. SHOW THE LOCATION OF
 EACH SECONDARY ROOF DRAIN OR SCUPPER. -
 RESPONSE NOTED, BUT CALCULATIONS ALL
 SECONDARY DRAINS ECT. NOT FOUND. THESE
 CALCULATIONS WILL BE FOR THE 5TH FLOOR
 PRIMARY DRAINS AND SECONDARY DRAINS AS
 WELL. - PLEASE PROVIDE CALCULATIONS.
 18) SHT A4.71A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS IN AREAS OF ROOF
 WHERE SCUPPERS ARE NOT AVAILABLE.
 SECTION 1107. - RESPONSE NOTED, BUT
 INFORMATION NOT SHOWN. - STILL NO
 SECONDARY ROOF DRAINS SHOWN IN AREAS
 WITHOUT SCUPPERS.
 19) SHT A4.72A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS FOR DECK DRAIN
 AREAS. SECTION 1107. RESPONSE NOTED, BUT
 INFORMATION NOT LOCATED. - STILL NO
 SECONDARY ROOF DRAINS SHOWN IN AREAS
 WITHOUT SCUPPERS.
 20) SHT A4.73A INDICATE LOCATION OF
 SECONDARY ROOF DRAIN FOR ALL AREAS.
 SECTION 1107. - RESPONSE NOTED, BUT ALL
 DRAINS NOT SHOWN. - STILL NO SECONDARY
 ROOF DRAINS SHOWN IN AREAS WITHOUT
 SCUPPERS.
 51) ALL SANT. RISERS WITH WASH MACHINES
 REQUIRE A STANDPIPE, AND THE CLEANOUTS
 SHALL BE LOCATED 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1, 802.4, &
 708.10. - RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED. - STANDPIPES FOR W/M'S
 NOT SHOWN.
 SECOND REVIEW
 **************NEW COMMENTS**************
 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS
 IN PLANTER WALLS AND REFER TO SHT A8.21
 FOR A DETAIL. NO DETAIL FOR THESE
 OPENINGS WAS LOCATED. PLEASE CLARIFY.
 SECTION 104.2.1. - NO WIDTH INDICATED
 4B) SHTS A4.71, A4.72, A4.73, & A4.74
 SHOW LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR AREAS THAT DO NOT HAVE
 SCUPPERS. SECTION 1107 - STILL AREAS
 WITH NO SECONDARY ROOF DRAINS.
 6B) SHT A5.11 SHOW ELEVATION FOR W/C
 AND LAVS IN USABLE BATHROOMS SHOWING
 OPENINGS FOR W/C, 18" OFF WALL TO
 CENTERLINE OF FIXTURE, AND HEIGHT OF LAV
 COUNTER TOPS AT 34". FHA-98 DESIGN
 MANUAL REQUIREMENT 7. - NOT ALL USABLE
 BATHROOMS SHOW THESE REQUIREMENTS.
 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT
 POWDER ROOM ON THE FLOOR PLAN DO NOT
 REFLECT NUMBERS SHOWN ON RISER DIAGRAM.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1. - RISERS 4,9,10,58,59
 ARE NOT SHOWN. RISER 8A ADDED, BUT NOT
 SHOWN ON SHTS P2.03 OR P-209 WITH RISER
 4,9,10,58,59 (203) & 4 & 9 (209)
 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1. - STILL DOES
 NOT REFLECT.
 21B) SHT P2.13 UNIT V MASTER BATH
 HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. SANT. OFFSET
 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 104.2.1. - NOW
 THE WATER CLOSET IS NOT VENTED AND THE
 FIXTURES FROM THE FLOOR ABOVE DISCHARGE
 THROUGH THE BATHROOM. THIS IS NOT
 ALLOWED PER SECTIONS 908.3 & 909.1
 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT
 THE RISER DIAGRAM AT THE MASTER BATH.
 PLEASE CORRELATE. SECTION 104.2.1. -
 VENT ROUTING STILL DOES NOT REFLECT
 RISER DIAGRAM VENTING.
 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1. - RISER #60 SHOWS W/M'S &
 KITCHEN SINKS, BUT FLOOR PLAN SHOWS
 POWDER ROOMS 2ND, 3RD, & 4TH FLOORS.
 PLEASE CORRELATE RISER & FLOOR PLAN. -
 FLOOR PLAN SHOWS RISER #11 DOWN TO MEZZ.
 LEVEL, THEN CONNECTING TO RISER 60, BUT
 RISERS DO NOT SHOW THIS. PLEASE
 CORRELATE RISERS AND FLOOR PLAN.
 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO
 REFLECT RISERS. SECTION 104.2.1. - NO
 NOTE INDICATING WHERE PIPING CAN BE
 LOCATED FOUND FOR UNIT "A"
 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. RISER 11
 - SHOW ALL PIPING TO REFLECT RISER
 DIAGRAM. SECTION 104.2.1. - NO NOTE
 INDICATING WHERE PIPING CAN BE LOCATED
 FOUND FOR UNIT "E1".
 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL
 PIPING TO REFLECT THE RISER DIAGRAMS.
 SECTION 104.2.1. - NO NOTE INDICATING
 WHERE PIPING CAN BE LOCATED FOUND FOR
 UNIT "G1".
 66B) SHT P2.35 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SHOW THE LOCATION OF
 RISER (45). SECTION 104.2.1. - NO NOTE
 INDICATING WHERE PIPING CAN BE LOCATED
 FOR UNIT "G".
 73B) SHT P2.39 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1. - RISER
 #54 DOES NOT REFLECT THE FLOOR PLAN.
 (SEE SHT P3.21 SEALED 7-1-5) - THIS USED
 TO SHOW CORRECT FIXTURES, BUT WAS IN
 WRONG LOCATION. IT HAS BEEN CHANGED TO
 BATHROOM FIXTURES. PLEASE CLARIFY.
 74B) SHT P2.40 UNIT B1 SHOW PIPING TO
 REFLECT THE RISERS. SHOW RISER LOCATION
 AND RISER DESIGNATION NUMBERS. SECTION
 104.2.1. - SHOW KITCHEN SINK & W/M
 PIPING.
 77B) SHT P2.44 UNIT G1 SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 - NO NOTE INDICATING THE LOCATION OF THE
 PIPING HAS BEEN FOUND.
 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. (26)
 SECTION 104.2.1. - RISER #26 NOT FOUND.
 79B) SHT P2.45 UNITS B4 & G SHOW PIPING
 TO REFLECT RISER DIAGRAMS. SECTION
 104.2.1. - NO NOTES INDICATING THE
 LOCATION OF THE PIPING WAS FOUND.
 85B) SHT P2.55 INDICATE THE LOCATION FOR
 THE SECONDARY ROOF DRAINS. SECTION
 104.2.1. - SECONDARY ROOF DRAINS IN SOME
 LOCATIONS NOT SHOWN.
 88B) SHT P2.56 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107. - SECONDARY ROOF DRAINS IN SOME
 LOCATIONS NOT SHOWN.
 89B) SHT P2.57 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107. - SECONDARY ROOF DRAINS IN SOME
 LOCATIONS NOT SHOWN.
 93B) SHT P2.64 STORM DRAIN LAYOUT DOES
 NOT REFLECT RISER (2)(3) IN UNIT E,
 RISER (4)(5) IN UNIT B4, AND RISER
 (7)(8) IN UNIT D. SECTION 104.2.1. -
 3"PF 80SF MISSING FROM RISER UNIT E1.
 94B) SHT P2.64 STORM DRAIN LINE RUNNING
 EAST TO WEST AND CONNECTING TO RISER
 (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE
 LENGTH. SECTION 704.1 - NOT ADDRESSED,
 INDICATE ON PLANS.
 103B) SHTS P3.16 THRU P3.25 THE
 FOLLOWING SANITARY RISER DIAGRAMS WERE
 NOT LOCATED ON THE BUILDING DRAIN
 ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN),
 10, 59, 12, 13, 14, 17, 15, 18, 19, 20,
 21, 22, 72, 57, 75, 40, 41, 42, 37. -
 RISERS 12 THRU 22, 40 THRU 42 AND RISER
 75 HAVE NOT BEEN LOCATED ON THE BUILDING
 DRAIN ISOMETRIC AS NOTED IN THE COMMENT
 RESPONSE.
 108B) SHT P3.21 RISER 26/35 KITCHEN SINK
 NOT SHOWN, DOES NOT REFLECT THE FLOOR
 PLAN, WASH MACHINE/LAUNDRY SINK OFFSET
 TO THE RIGHT SIDE NOT TO THE LEFT,
 VENTING FROM LAV DOES NOT REFLECT FLOOR
 PLAN. SECTION 104.2.1. - RISER 26/35 NOT
 SPLIT AND RISER 26 NOT FOUND ABOVE THE
 5TH FLOOR. PLEASE CLARIFY.
 109B) SHT P3.22 RISER 55 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 - STILL DOES NOT REFLECT FROM THE 6TH
 FLOOR UP. PLEASE CORRELATE RISER & FLOOR
 PLAN.
 121B) SHT P3.28 RISER 68 INDICATE SHEET
 NUMBER FOR CONTINUATION OF RISER.
 SECTION 104.2.1. - RISER 54 OFFSET VENT
 REQUIRED, AND 4 FU MAX. ON 2" WET VENT.
 SECTION 915 AND TABLE 909.3. - RISER 7
 OFFSET VENTS REQUIRED. UPPER OFFSET,
 (2ND FLOOR),VENT SHALL BE CONNECTED TO
 THE VERTICAL STACK NOT THE BRANCH LINE.
 SECTION 915. - RISER 3, 56, 57 OFFSET
 VENT REQUIRED SECTION 915 - DOES NOT
 SHOW KITCHEN SINK 5TH FLOOR SECTION
 104.2.1. - MISLABELED AS RISER 51 -
 SECTION 104.2.1. - WASH MACHINE GROUND
 FLOOR REQUIRES THAT CLEANOUT IS 4' AFF.
 SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT
 BASE, HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. VENT SHALL BE
 CONNECTED AT THE BASE OF THE STACK.
 SECTION 903.4 - THESE RISERS ARE
 INDICATED AS 4, 9, 10, 58, & 59. PLEASE
 CORRELATE. SECTION 104.2.1. - OFFSET
 SHALL CONNECT ABOVE THE BRANCH LINE. FIG
 915.2. - RISER 58 SOME FIXTURES ARE
 MISLABELED, ON NOT LABELED AT ALL.
 SECTION 104.2.1. - VENT TERMINATION FOR
 2ND FLOOR BATHROOM NOT SHOWN. SECTION
 104.2.1. - RISER 4/9 MISLABELED FIXTURE.
 SECTION 104.2.1, WASH MACHINES, KITCHEN
 SINKS, AND BATHROOMS SHALL NOT DRAIN
 PAST THE VENT FOR THE BATHROOM ON THE
 MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE
 MEZZ. LEVEL DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - SECOND FLOOR
 POWDER ROOM DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - BATHROOM GROUPS
 FOR THE THIRD AND FORTH FLOORS NOT SHOWN
 ON RISER 4. SECTION 104.2.1. ** - WASH
 MACHINE GROUND FLOOR STILL REQUIRES THE
 CLEANOUT TO BE LOCATED 4' ABOVE THE
 FLOOR. - NEW RISER 8A VENT SHOWS
 CONNECTING INTO RISER 8. THIS IS NOT
 REFLECTED ON RISER 8. PLEASE CORRELATE
 RISERS.
 124B) SHT P3.30 RISER 77 DOES NOT
 REFLECT THE FLOOR PLAN, WASH MACHINES
 NOT SHOWN. - RISER 47 OFFSET VENTS
 REQUIRED, 5TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN, NO KITCHEN SINK SHOWN. -
 RISER 49 OFFSET VENTS REQUIRED. - RISER
 49 DOES NOT REFLECT THE FLOOR PLAN, LAV
 MISSING IN MASTER BATH 2ND FLOOR, OFFSET
 VENTS REQUIRED, 2ND FLOOR INDICATED
 DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT
 REFLECT THE FLOOR PLAN. - RISER 50 DOES
 NOT REFLECT THE FLOOR PLAN ON THE 2ND
 FLOOR AND THE 5TH FLOOR, OFFSET VENTS
 REQUIRED, FIXTURE MISLABELED, 4 FU MAX.
 ON 2" WET VENT, DRY HORIZONTAL VENT NOT
 APPROVED. SECTIONS 104.2.1, 915, & TABLE
 909.3 - 5TH FLOOR UPPER OFFSET VENT NOT
 SHOWN.
 125B) SHT P3.31 RISER 24 DOES NOT
 REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU
 MAX. ON 2" WET VENT, OFFSET VENTS
 REQUIRED, DRY HORIZONTAL VENT NOT
 APPROVED. - RISER 54 OFFSET VENTS
 REQUIRED. - RISER 26 OFFSET VENTS
 REQUIRED. - RISER 27/28 OFFSET VENTS
 REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES
 NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ
 LEVEL. - RISER 55/28/84 RISER
 DESIGNATION NUMBER DOES NOT REFLECT THE
 FLOOR PLAN, (SHOW AS 55/73/84), PLEASE
 CLARIFY, DOES NOT REFLECT THE FLOOR PLAN
 NO WASH MACHINES SHOWN, OFFSET VENTS
 REQUIRED. SECTIONS 104.2.1, 915, & TABLE
 909.3. ** - RISER 27/28 STILL DOES NOT
 REFLECT THE FLOOR PLAN AS THE MEZZ.
 LEVEL.
 130B) SHT P3.36 GROUND FLOOR DOES NOT
 REFLECT THE FLOOR PLAN, (FD IN TRASH
 ROOM NOT SHOWN, KITCHEN SINK - W/M AREA,
 AND VENTING), INDICATE WHY 10 FU FOR
 CLEANOUT AT END OF RUN. - RISER 71
 OFFSET VENTS REQUIRED, NO PIPING FOR 3RD
 FLOOR, NO KITCHEN SINK ON 4TH FLOOR,
 INDICATE FLOOR LEVEL TOP OF RISER. -
 RISER 37 VENT STACK SHALL CONNECT AT THE
 BASE OF THE STACK, NO HORIZONTAL DRY
 VENT, OFFSET VENT REQUIRED, 5TH FLOOR
 DOES NOT REFLECT THE FLOOR PLAN, FIXTURE
 MISLABELED AND 4 FU MAX. ON 2" WET VENT
 4TH FLOOR, UNABLE TO FIND CONTINUATION
 OF RISER. - RISER 36 SHOWS TYPICAL
 PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR
 PLANS ARE DIFFERENT. SECTIONS 104.2.1.
 915, 903.4, 905.3, 905.4. ** - FLOOR
 DRAIN IN TRASH ROOM NOT SHOWN IN THE
 KITCHEN SINK - W/M AREA. ALSO SHOW
 VENTING. - STILL UNABLE TO LOCATE
 CONTINUATION OF RISER 37.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 **************NEW COMMENTS**************
  
 1C) SHT P2.03 RISER 8A NOT SHOWN WITH
 RISERS 4,9,10,58,59. SECTION 104.2.1.
 2C) SHT P2.09 RISER 8A NOT SHOWN WITH
 RISERS 4,9,10,58,59 DOWN & 4,9 UP.
 SECTION 104.2.1.
 3C) ALL SHEETS FOR UNITS, WHERE THERE IS
 NO PIPING SHOWN IN ANY PORTION OF A
 UNIT, INDICATE, (AT UNIT ON PLANS),
 WHERE THE CAN BE LOCATED. THIS INCLUDES
 ALL PIPING SYSTEMS. SECTION 104.2.1.
 4C) SHT P2.39 UNIT B3 RISER 54 FLOOR
 PLAN DOES NOT REFLECT THE RISER DIAGRAM.
 - RISER 55 UNIT B1 NO REVENT TO RISER 27
 SHOWN ON FLOOR PLAN. SECTION 104.2.1.
 5C) SHT P2.40 UNABLE TO LOCATE RISER 56.
 SECTION 104.2.1.
 6C) SHT P3.16 RISER 5/53 INDICATES ON
 15TH FLOOR VENT FROM RISER 5, BUT NO
 CONNECTION AT 15TH FLOOR SHOWN ON RISER
 5. PLEASE CLARIFY. SECTION 104.2.1.
 7C) SHT P3.19 RISERS 14 & 17 OFFSET
 VENTS REQUIRED. SECTION 915. - SHOWS
 15TH FLOOR W/M ABOVE 21ST FLOOR. PLEASE
 CLARIFY. SECTION 104.2.1.
 8C) SHT P3.28 RISER 1,2,68 & 54,4
 CONNECT VENT STACK TO BASE OF SANT.
 STACK. SECTION 903.4. - RISER 7 3RD &
 4TH FLOOR TUB MISLABELED AS SHOWER.
 SECTION 104.2.1. - RISER 8 VENT STACK
 CHANGED TO SOLID LINE OF A SANT. LINE.
 SECTION 104.2.1. - RISER 56 UPPER OFFSET
 VENT REQUIRED AT 5TH FLOOR OFFSET.
 SECTION 915. - RISER 8A VENT SHOWN TO
 TIE INTO RISER 8 VENT LINE. NOT SHOWN ON
 RISER 8 VENT. PLEASE CLARIFY.
 9C) SHT P3.30 RISER 48/50 CONNECT VENT
 STACK TO THE BASE OF THE SANT. STACK.
 SECTION 903.5. - UPPER OFFSET VENT
 REQUIRED 5TH FLOOR. SECTION 915. - RISER
 48 NOT SHOWN ON PREVIOUS FLOOR PLAN
 SHEET FROM GROUND FLOOR THRU 2ND FLOOR.
 - INDICATE WHAT SHEET THE CONTINUATION
 OF EACH RISER WILL BE FOUND ON. SECTION
 104.2.1.
 10C) SHT P3.21 WERE IS THE CONTINUATION
 OF RISERS 33, 74, & 81 ABOVE THE 6TH
 FLOOR AND RISER 71 BELOW THE 6TH FLOOR?
 SECTION 104.2.1.
 11C) SHT P3.31 RISERS 26 & 27/28 CONNECT
 VENT STACKS TO BASE OF SANT. STACK.
 SECTION 903.5.
 12C) SHT P2.34 OFFSET SHOWN ON FLOOR
 PLAN TO RISERS 81 & 74. PLEASE INDICATE
 WHERE ON THE RISER DIAGRAM THAT IS
 LOCATED. SECTION 104.2.1.
 13C) SHT P3.23 OFFSET AT MEZZ. LEVEL FOR
 RISER 33/55 DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - REVENTS FROM
 W/M TO RISER 33/55 ARE MISLABELED.
 SECTION 104.2.1. - REVENT AT TOP OF
 STACK "A" INDICATE "TO STACK VENT 56",
 BUT NOT SHOWN ON STACK VENT 56. PLEASE
 CLARIFY. SECTION 104.2.1.
 14C)SHT P3.34 RISER 61 CONNECT VENT
 STACK TO BASE OF SANT. STACK. SECTION
 903.5. - GROUND FLOOR DOES NOT REFLECT
 THE FLOOR PLAN. SECTION 104.2.1. - RISER
 INDICATES TYPICAL 3RD THRU 5TH FLOORS,
 BUT RISER 43 ONLY CONNECTS ON THE 5TH
 FLOOR. INDICATE ON PLANS. - RISER 43
 CONNECT VENT STACK TO BASE OF SANT.
 STACK. 903.5 - DOES NOT REFLECT FLOOR
 PLAN. - SECTION 104.2.1. - TABLE 909.3
 INDICATE ALL PIPE SIZES. - RISER 64
 RISER INDICATES TYPICAL 3RD THRU 5TH
 FLOOR, BUT RISER 45 ONLY CONNECTS ON 5TH
 FLOOR. INDICATE ON PLANS. SECTION
 104.2.1.
 15C) SHT P3.35 SHOW PIPE SIZES FOR
 TYPECAL 3RD/4TH FLOORS RISER 38.- MAX 10
 BRANCH INTERVALS TO THE RELIEF VENT.
 RECHECK INTERVALS. SECTION 914.
 16C) SHT P3.37 INDICATE 1/4"FT SLOPE
 ENTIRE RUN UPSTREAM OF 10"@1/4"FT SLOPE
 22306SF (RWL 4/5) & UPSTREAM OF 15"
 62210SF (RWL 2/3) TO HORIZONTAL OFFSET.
 SECTION 704.1.
 17C) SHT P3.38 3" PD 80SF MISSING FROM
 RWL 2/3 AT 5TH FLOOR. SECTION 104.2.1.
 18C) SHT P3.39 INDICATE 1/4"/FT SLOPE
 THE ENTIRE RUN UPSTREAM OF 15"@1/4"/FT
 54050SF UP TO HORIZONTAL OFFSET
 DOWNSTREAM OF RWL 7. SECTION 704.1.
 19C) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B).
 THIS IS GIVEN AS A NOTICE ONLY.
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  