Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop M
Sequence Number 3
Notes
Date Text
2005-09-01 00:00:00DENIED:
 1.PLAN SHEET M1.13 & A2.15, PLAN
 INDICATES PAU-1 THROUGH 4 ARE LOCATED IN
 AREA THAT IS ENCLOSED.PLEASE PROVIDE
 MANUFACTURER'S INTALLATION/SUBMITALL
 DATA FOR REVIEW.OA PACKAGE UNITS ARE
 TYPICALLY LOCATED OUTDOORS.
  
 2.PLEASE CLARIFY RATIONALE FOR THE
 SPF-3 (STAIRWELL PRESSURIZATION) IS THIS
 DUCTED TO THE OA LOUVER?PLAN INIDCATES
 EF-R-2 (POOL DECK ATTIC) EXHAUSTING INTO
 THE SAME ROOM AS PAU-1 & SPF-3.PER
 2001 FBC(M)501.3, MECHANICAL EXHAUST
 SYSTEMS SHALL TERMINATE OUTDOORS AT A
 POINT WHERE IT CANNOT BE RECIRCULATED BY
 THE VENTILATING SYSTEM. FRESH AIR IS TO
 BE TAKEN FROM THE OUTDOORS WHICH
 ACCORDING TO THE DEFINITION; OUTDOORS,
 NOT ENCLOSED; HAVING NO ROOF.
 PLEASE VERFIY ALL AREAS WHERE OUTSIDE
  
 AIR LOUVERS ARE LOCATED.
  
 3.PLAN SHEET M2.01, DOMESTIC WATER
 PUMP ROOM AND THE FIRE PUMP ROOM
 INDICATE OUTSIDE AIR FROM THE GARAGE
 AREA & EXHAUST ALSO GOING INTO THE
 GARAGE AREA.PER 2001 FBC(M)401.5.1,
 OUTSIDE AIR INTAKES SHALL BE LOCATED A
 MINIMUM OF 10FT FROM PARKING LOTS,
 STREETS, ALLEYS, AND LOADING DOCKS.
  
 4.PLAN SHEET M2.01 REFERS TO THE ARCH
 DWGS., PLEASE SPECIFY SHEET NUMBER.
 PROVIDE DETAIL OF THE SEALED ENCLOSURE.
  
 5.PLAN SHEET M2.02 UNIT GENERAL NOTES
 #1; AKK TOILET EXHAUST RUNNING INSIDE
 PLENUMS SHALL BE WRAPPED.PLEASE
 CLARIFY, ONLY DRYER EXHAUST DUCTS WILL
 BE ENCLOSED SEPERATELY?PER 2001 FBC(M)
 601.3, EXHAUST DUCTS UNDER POSITIVE
 PRESSURE & VENTING SYSTEMS SHALL NOT
 EXTEND INTO OR PASS THROUGH PLENUMS.
 PLANS STILL INDICATE EXHAUST DUCT
 THROUGH PLENUMS WITHOUT THE NOTE
 INDICATING A SEPERATE ENCLOSURE.
  
 6.PLANS INDICATE DRYER BOOSTER FANS
 WERE DELETED IN LEIU OF A SPECIFIC
 DRYER.PLEASE NOTE, SPECIFIC DRYER TO
 BE INSTALLED AT FINAL INSPECTION.
 DRYERS THAT EXHAUST GREATER THAN 2,000
 CFM SHALL BE PROVIDED WITH MAKE-UP AIR,
 2001 FBC(M)504.5.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  