Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-09-30 00:00:00 | ******DENIED****** | | | | 1) EXIT SIGN STILL APPEARS TO LEAD | | PERSONS INTO THE LOADING AREA. SHT | | E-2.01. PLEASE CLARIFY ARCHITECT'S | | RESPONSE. | | | | 2) FIRE PROTECTION PLANS HAVE BEEN | | SUBMITTED WITH THIS PERMIT. SEPARATE | | SHOP DRAWINGS AND PERMITS ARE REQUIRED | | FOR FIRE SPRINKLER AND FIRE ALARM | | SYSTEMS. | | | | 3) A COPY OF THE FIRST REVIEW HAS BEEN | | INCLUDED. PLEASE SUBMIT YOU RESPONSE | | LETTER TO THAT REVIEW THAT WAS COMPLETED | | ON 1/21/05. A RESPONSE LETTER COULD NOT | | BE FOUND WITH THIS SUBMITTAL. | | | | 4) ELECTRONIC SWITCHES, CHAIN AND LOCK | | REQUIRED ON DOUBLE CHECK DETECTOR | | ASSEMBLY. | | | | 5) SIGNS ARE REQUIRED IN STAIRWELLS THAT | | INDICATE TOP, FLOOR# AND ROOF ACCESS. | | | | 6) TACTILE SIGNAGE IS REQUIRED FOR EXIT | | DOORS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|