Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop B
Sequence Number 3
Notes
Date Text
2005-11-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 5/19/05:
  
 4) INFORMATIVE. NOTE THAT THE NOTICE OF
 COMMENCEMENT, IMPACT FEE RECEIPT AND
 SPECIAL INSPECTOR AGREEMENT WILL BE
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
  
 5) FBC* 104.2.4SITE SURVEY. THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 THIS TIME NO SURVEY DRAWING WAS
 SUBMITTED.A SIGNED AND SEALED SURVEY
 DRAWING PREPARED BY A LICENSED
 SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES).
  
 8) FBC* 1804.2.2SHEET S-0, GENERAL
 NOTES - FOUNDATIONS.THIS COMMENT HAS
 NOT BEEN ADDRESSED.SUBMIT THREE
 COPIES OF ARDAMAN & ASSOCIATES SOIL
 REPORT DATED 7/28/04 AS REFERENCED
 UNDER THE 'FOUNDATION' NOTE.
  
 9) FBC 13-103.1.2THIS COMMENT HAS NOT
 BEEN ADDRESSED.SHEET 2 OF THE
 SUBMITTED ENERGY CODE COMPLIANCE FORMS
 MUST BE SIGNED BY THE BUILDING OWNER,
 THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY
 THE OWNER.ALSO THE ARCHITECT'S LICENSE
 NUMBER MUST BE ADDED IN THE SPACE
 PROVIDED ON SHEET 2 AND ALL OF THE
 PROJECT INFORMATION ITEMS ON SHEET 1
 SHALL BE ENTERED.
  
 10) PRODUCT APPROVALS.THIS COMMENT HAS
 NOT BEEN ADDRESSED. SUBMIT PRODUCT
 APPROVALS FOR THE WINDOWS, STOREFRONTS,
 EXTERIOR DOORS AND ROOFING PRODUCTS.
  
 25) NFPA 823-2.4.3.1THE COMMENT
 RESPONSE REFERING TO APPROVAL BY THE
 CONSTRUCTION BOARD OF ADJUSTMENTS AND
 APPEALS (CBAA) IS NOTED.PLEASE SUBMIT
 A COPY OF THE CBAA FINAL DECISION, FOR
 THE PERMIT FILE,SO THAT IT MAY BE
 DEEMED UNNECESSARY, FOR THIS PROJECT
 ONLY, TO PROVIDE A MINIMUM 6" CLEARANCE
 BETWEEN THE OPEN CHUTE LOADING DOOR AND
 CLOSED SERVICE OPENING ROOM DOOR.
  
 37) FBC 1601.1SHEET A8.24,
 ARCHITECTURAL TRIM.SUBMITTAL OF
 DETAILS FOR ATTACHMENT OF MOULDINGS,
 ORNAMENTAL PANELS AND BANDS, AND OTHER
 ARCHITECTURAL TRIM IS NOTED BUT THE
 DETAILS DO NOT STATE THE HORIZONTAL
 SPACING OF THE 'TAPCONS'.AMEND THE
 DETAILS TO SHOW THE FASTENER SPACING.
  
 42) FBC 11.4.6.3SHEETS A2.04 THROUGH
 A2.09.ALL ACCESSIBLE PARKING SPACES
 SHALL BE MIN. 12'-0" WIDE.THE PLANS
 ONLY SHOW THE VAN ACCESSIBLE SPACES TO
 COMPLY WITH THIS REQUIREMENT.ALL OF
 THE REMAINING ACCESSIBLE SPACES ARE
 SHOWN AS ONLY 8'-6" WIDE.AMEND THE
 PLANS.
  
 43) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
2005-10-21 00:00:00****PLAN REVIEW IN PROGRESS****