2007-08-25 09:12:59REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P2.49 WATER SUPPLY FOR TRASH CHUTE WASH DOWN IS
 SHOWN CONNECTING TO THE CONDENSATE RISER DIAGRAM.--
 REVISION #8 NOT FOUND OR APPROVED. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 2. SHT P2.64 DECK DRAINS SHALL BE LOCATED AT AT THE LOW
 POINT OF THE DECK. MANY (APPROX. 14), ARE SHOWN IN
 LOCATIONS OTHER THAN THE LOW POINT. PLEASE CORRELATE
 WITH THE ARCHITECT TO MAKE SURE THE DECKS DRAIN
 PROPERLY. SECTION 1101.7.
  
 3. SHTS P3.01 & P3.02 THE WATER SUPPLY LINES TO THE
 TRASH CHUTE SHALL INCLUDE BACKFLOW PROTECTION PER
 SECTION 608.1 AND TABLE 608.1 AND SHALL HAVE A SHUT OFF
 VALVE AS REQUIRED IN SECTION 606.2(3).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731