Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
P |
Sequence Number |
29 |
|
Notes |
Date |
Text |
2007-08-25 09:12:59 | REVISION DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SHT P2.49 WATER SUPPLY FOR TRASH CHUTE WASH DOWN IS | | SHOWN CONNECTING TO THE CONDENSATE RISER DIAGRAM.-- | | REVISION #8 NOT FOUND OR APPROVED. PLEASE CLARIFY. | | SECTION 104.2.1. | | | | 2. SHT P2.64 DECK DRAINS SHALL BE LOCATED AT AT THE LOW | | POINT OF THE DECK. MANY (APPROX. 14), ARE SHOWN IN | | LOCATIONS OTHER THAN THE LOW POINT. PLEASE CORRELATE | | WITH THE ARCHITECT TO MAKE SURE THE DECKS DRAIN | | PROPERLY. SECTION 1101.7. | | | | 3. SHTS P3.01 & P3.02 THE WATER SUPPLY LINES TO THE | | TRASH CHUTE SHALL INCLUDE BACKFLOW PROTECTION PER | | SECTION 608.1 AND TABLE 608.1 AND SHALL HAVE A SHUT OFF | | VALVE AS REQUIRED IN SECTION 606.2(3). | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|