Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
E |
Sequence Number |
29 |
|
Notes |
Date |
Text |
2008-01-24 12:55:27 | ** DENIEDREVIEW OF REVISIONS. ** | | | | THIS REVIEW STOP WILL REMAIN IN FAIL STATUS EVEN AS | | SOME SHEETS WERE OK. | | | | ** PLEASE KNOW THE FOLLOWING SHEETS SUBMITTED UNDER | | REVISION 19 ARE OK. | | SHEETS, 3.11, 7.13 AND 7.16 ARE OK AND STAMPED. | | RETAINED ONE FOR FILE SET. | | | | | | 1) NOTE: PLEASE SEE SHEETS 1.03A AND 1.04 A ARE NOT | | PART OF THE BASE BUILDING AND WILL REQUIRE THIS LOW | | VOLTAGE WORK FOR SOUND SYSTEM TO BE SUBMITTED UNDER | | SEPARATE PERMIT. | | | | 2) NOTE: PLEASE SEE SHEET 3.06 CAN NOT BE STAMPED BASED | | ON ITEMS FROM FIRE REVIEW COMMENTS ON 1/23/08. | | THIS SHEET IS OK WITH ELECTRICAL HOWEVER WILL HAVE | | COMMENTS FROM FIRE REVIEW. | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|