2007-05-01 19:57:18BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 ARCHITECTURAL REVISION # 9
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 ALL SHEETS REVIEWED AND STAMPED EXCEPT SHEETS A4.32,
 A4.35, A3.36, A4.42, A4.53, A7.01, A7.05, A7.05A,
 A7.09, AND A7.12 WHICH ARE ALL DENIED PER THE COMMENT
 BELOW:
  
 1) FBC 1012.1.3ELEVATION CHANGE AT ELEVATOR VESTIBULE
 DOORWAY.SHEETS A4.32, A4.35, A3.36, A4.42, A4.53,
 A7.01, A7.05, A7.05A, A7.09, AND A7.12 ALL SHOW A 3/4
 INCH CHANGE IN FLOOR ELEVATION AT THE ELEVATOR
 VESTIBULE DOORWAY.THE ELEVATION CHANGE OF THE FLOOR
 SURFACES ON BOTH SIDES OF A DOOR SHALL NOT VARY BY MORE
 THAN 1/2 INCH AND ANY FLOOR LEVEL CHANGE MORE THAN 1/4
 INCH AT DOORWAYS SHALL BE BEVELED WITH A SLOPE NOT
 STEEPER THAN 1:2.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS