Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
B |
Sequence Number |
282 |
|
Notes |
Date |
Text |
2007-05-01 19:57:18 | BUILDING PLAN REVIEW | | *******DENIED******* | | ROBERT BROWN(561) 805 6652 | | E-MAIL: [email protected] | | | | ARCHITECTURAL REVISION # 9 | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | ALL SHEETS REVIEWED AND STAMPED EXCEPT SHEETS A4.32, | | A4.35, A3.36, A4.42, A4.53, A7.01, A7.05, A7.05A, | | A7.09, AND A7.12 WHICH ARE ALL DENIED PER THE COMMENT | | BELOW: | | | | 1) FBC 1012.1.3ELEVATION CHANGE AT ELEVATOR VESTIBULE | | DOORWAY.SHEETS A4.32, A4.35, A3.36, A4.42, A4.53, | | A7.01, A7.05, A7.05A, A7.09, AND A7.12 ALL SHOW A 3/4 | | INCH CHANGE IN FLOOR ELEVATION AT THE ELEVATOR | | VESTIBULE DOORWAY.THE ELEVATION CHANGE OF THE FLOOR | | SURFACES ON BOTH SIDES OF A DOOR SHALL NOT VARY BY MORE | | THAN 1/2 INCH AND ANY FLOOR LEVEL CHANGE MORE THAN 1/4 | | INCH AT DOORWAYS SHALL BE BEVELED WITH A SLOPE NOT | | STEEPER THAN 1:2. | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | END OF REVIEW COMMENTS | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | (561) 805 6652ROBERT BROWN | | E-MAIL: [email protected] | | | | | | |
|