2007-04-18 13:02:54 | BUILDING PLAN REVIEW | | PERMIT:04120353 | | ADD: 717 S. OLIVE AVE. | | CONT: KAST CONST. | | TEL: (561)835-3890 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW: SUBMITTALS. | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)THE DESIGN PRESSURES FOR THE SENERFLEX WALL STATED | | IN THE NOA #02-1022.17 ARE 65 PSF AND 90 PSF. THE | | DESIGN PRESSURES STATED ON THE STRUCTURAL DRAWINGS IS | | 120 PSF. SEE SHEET S-6.2 OF THE STRUCTURAL DRAWINGS. | | THE ES REPORT FOR THE SENERFLEX WALL SYSTEM (ADHERED) | | SEC. 4.1 AND 4.1.5 HAVE PRESSURES OF 30 PSF AND 54 PSF | | WHICH DOES MEET THE 120 PSF STATED ON THE DRAWINGS. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | |
|