2007-02-22 18:58:17REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1. SHT P2.52 UNIT TYPES S1 & R ARE INDICATING SUPPLYING
 WATER TO THE ROOF LEVEL FOR THE SHOWER, DRINKING
 FOUNTAIN AND HOSE BIBB AT THE POOL AREA. THIS IS NOT
 APPROVED AND THE WATER FOR COMMON AREA USAGE SHALL BE
 SUPPLIED FROM COMMON AREA WATER SUPPLY, NOT FROM THE
 DWELLING UNITS. SECTIONS 608.1 & 103.6 AND TABLE
 608.1.
  
 2. SHT P2.58 4" DD & 3" SANT. LINE NOT INDICATED ON
 PREVIOUS REVISIONS. SECOND SHOWER LINE BEHIND ELEVATORS
 AS INDICATED ON SHT P2.52 NOT SHOWN. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 3. SHT P3.05 UNIT S & S1 SHOWS SHOWER, HOSE BIBB &
 DRINKING FOUNTAIN WATER SUPPLY FROM DWELLING UNIT.
 WATER SUPPLY SHALL BE CONNECTED TO THE COMMON AREA
 WATER SUPPLY. SECTIONS 608.1, 103.6 AND TABLE 608.1.
  