Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop P
Sequence Number 2
Notes
Date Text
2005-05-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
  
 FROM PREVIOUS REVIEW:
 3) SHT A2.10 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES PER TABLES 1003.2 AND
 403.1. SHOW SQUARE FEET FOR EACH COMMON
 USE ROOM. RESPONSE NOTED, BUT NOT
 INDICATED WHERE I CAN FIND THE
 CALCULATIONS. SECTION 104.2.1.
 4) SHT A2.10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY STORM DRAINS FOR
 THE 5TH FLOOR OPEN AREAS PER SECTIONS
 1106 & 1107. SHOW THE LOCATIONS FOR ALL
 PRIMARY AND SECONDARY DRAINS. RESPONSE
 NOTED, BUT NO CALCULATIONS WERE
 INDICATED OR FOUND. SECONDARY DRAINS
 WERE NOT LOCATED FOR ALL AREAS. SECTION
 104.2.1.
 10) ALL SHEETS FOR UNITS, SHOW THE
 OPENING SIZE FOR ALL W/C'S AND SHOW THE
 W/C TO BE 18" FROM THE CENTER LINE OF
 THE FIXTURE TO THE WALL WHERE
 APPLICABLE. RESPONSE NOTED, BUT NOT ALL
 UNITS SHOW THE REQUIREMENT. SECTION
 104.2.1.
 11) ALL SHEETS FOR UNITS, INDICATE
 SPECIFICATION "A" OR "B" AS REQUIRED BY
 THE FHA-98 DESIGN MANUAL FOR EACH UNIT.
 RESPONSE NOTED, BUT NOT UNITS SHOW
 SPECIFICATION "A" OR "B". SECTION
 104.2.1.
 12) SHT A4.41 KITCHEN SINK & JUICE BAR
 SINK IN COMMON AREAS SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT A DETAIL. RESPONSE NOTED, BUT NO
 DETAIL WAS FOUND.
 13) SHT A4.41 SUBMIT A DETAIL FOR THE
 TOILET ROOM IN THE COMMON AREA. SHOW
 COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19, 11-4.21, & 11-4.22 AND ALL
 SUBSECTIONS. ALSO SEE SECTION 2 OF THE
 FHA-98 DESIGN MANUAL. RESPONSE NOTED,
 BUT THE FOLLOWING INFORMATION IS NOT
 SHOWN ON THE DETAIL:
 A. FLUSH CONTROLS 11-4.16.5
 B. EXPOSED PIPES & SURFACES 11-4.19.4
 C. FAUCETS 11-4.19.5
 D. CURBS 11-4.21.7
 14) SHT A4.41 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1 FOR THE COMMON
 AREA. SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.15 AND ALL SUBSECTIONS
 ALSO SEE SECTION 410.1. RESPONSE NOTED,
 BUT NOT INDICATED WHERE DETAIL IS
 LOCATED.
 15) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW THE
 SQUARE FOOTAGE OF EACH AREA DRAINED WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS SHOWN ADDED TO THE ROOF AREA.
 ALSO SHOW THE AREA OF UPPER ROOFS
 DRAINING ONTO EACH AREA ADDED TO THE SF
 IN CALCULATIONS. SHOW THE LOCATION OF
 EACH SECONDARY ROOF DRAIN OR SCUPPER. -
 RESPONSE NOTED, BUT CALCULATIONS ALL
 SECONDARY DRAINS ECT. NOT FOUND. THESE
 CALCULATIONS WILL BE FOR THE 5TH FLOOR
 PRIMARY DRAINS AND SECONDARY DRAINS AS
 WELL. - PLEASE PROVIDE CALCULATIONS.
 18) SHT A4.71A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS IN AREAS OF ROOF
 WHERE SCUPPERS ARE NOT AVAILABLE.
 SECTION 1107. - RESPONSE NOTED, BUT
 INFORMATION NOT SHOWN.
 19) SHT A4.72A INDICATE LOCATION OF
 SECONDARY ROOF DRAINS FOR DECK DRAIN
 AREAS. SECTION 1107. RESPONSE NOTED, BUT
 INFORMATION NOT LOCATED.
 20) SHT A4.73A INDICATE LOCATION OF
 SECONDARY ROOF DRAIN FOR ALL AREAS.
 SECTION 1107. - RESPONSE NOTED, BUT ALL
 DRAINS NOT SHOWN.
 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE
 AND REQUIRE MORE INFORMATION. SOME
 SHEETS SHOW SANT., VENTS, WATER, COND.,
 T/P, OR ANOTHER UNIDENTIFIED LINE, BUT
 ALL DO NOT HAVE ALL INFORMATION
 REQUIRED. - RESPONSE NOTED, BUT
 INFORMATION IS STILL MISSING ON MANY
 SHEETS. SOME EXAMPLES NO SANT SHOWN TO
 WASH MACHINE IN UNIT 1, RISER NUMBERS
 ARE MISSING OR MISLABLED, SOME SANT.
 LINES NOT SHOWN, WATER LINES MISSING,
 ECT. RECHECK ALL UNITS TO MAKE SURE ALL
 PIPING, (SANT., WATER, COND, VENTS, P/T,
 PAN DRAINS, WASTE ARMS ECT ARE SHOWN)
 33) SHOW STACK NUMBERS FOR EACH STACK IN
 ALL UNIT SHEETS. SECTION 104.2.1.
 RESPONSE NOTED, BUT NOT ALL STACK
 NUMBERS ARE SHOWN, AND SOME STACK
 NUMBERS ARE NOT IN THE CORRECT LOCATION
 AS THE STACK.
 45) SHT P2.21 UNITS A1 & VV1 BATH #2
 SHOWERS ARE NOT VENTED. SECTION 901.2.1
 UNIT A1 WHAT TYPE OF VENT IS KITCHEN
 SINK UTILIZING. SECTION 901.2.1 -
 RESPONSE NOTED, BUT SHOWERS ARE NOT
 VENTED AND NO INFORMATION FOR THE
 KITCHEN VENT HAS BEEN GIVEN.
 46) SHT P2.39 HAS A REFERENCE TO SHT P2.
 NO SHT P2 IS LOCATED. PLEASE CLARIFY
 SECTION 104.2.1. - RESPONSE NOTED, BUT
 THE REFERENCE IS STILL THERE. IN FACT
 THERE ARE AT LEAST 2 REFERENCES TO SHEET
 P2 ON THIS SHEET.
 50) SHT P2.57 WOMEN'S BATHROOM DOES NOT
 REFLECT THE SANT. RISER DIAGRAM. W/C IN
 WOMEN'S STALL MAX. 10' FROM POINT OF
 VENT TABLE 906.1. INDICATE THE USE OF
 THE FLOOR DRAIN FOR FIXTURE NEXT TO
 SHOWER IN THE MEN'S BATHROOM. SECTION
 104.2.1. - RESPONSE NOTED, BUT THE W/C
 IN THE WOMEN'S BATHROOM DOES NOT SHOW
 SANITARY PIPING FROM THE BRANCH LINE TO
 THE WATER CLOSET TO THE LAV AS SHOWN ON
 THE RISER DIAGRAM. ALSO THE FLOOR DRAIN
 IN THE MEN'S BATHROOM HAS NOT BEEN
 EXPLAINED BY THE RESPONSE "DRAWING
 CORRECTED"
 51) ALL SANT. RISERS WITH WASH MACHINES
 REQUIRE A STANDPIPE, AND THE CLEANOUTS
 SHALL BE LOCATED 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1, 802.4, &
 708.10. - RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
 64) BACKFLOW PROTECTION REQUIRED FOR THE
 POOL MAKE UP WATER. SUBMIT A DETAIL.
 SECTION 608.13.2. - RESPONSE NOTED, BUT
 BACKFLOW PROTECTION IS NOT IN THE SCOPE
 OF THE POOL CONTRACTOR UNLESS IT IS AN
 AIR GAP AT THE COLLECTOR TANK. PLEASE
 INDICATE METHOD OF BACKFLOW PROTECTION.
 65) BECAUSE PLANS ARE INCOMPLETE, MORE
 COMMENTS MAY BE FORTHCOMING WHEN PLANS
 ARE RESUBMITTED. - PLEASE RETURN THE
 PLUMBING PLANS WITH THE RED LINE NOTES
 WHEN RESUBMITTING TO HELP REVIEWING
 PLANS FOR THE SECOND TIME. - RESPONSE
 NOTED, BUT PLANS WERE NOT RETURNED. I
 WILL BE KEEPING THE RED LINE SET OF
 PLANS TO ASSIST IN THE THIRD REVIEW.
 ALSO IT SEEM THAT THE PLANS ARE NOT 100%
 COMPLETE AT THIS TIME AND MORE COMMENTS
 MAY FOLLOW ON THE THIRD REVIEW.
 **************NEW COMMENTS**************
 1B) SHT A4.43 PLANTERS SHOW 8"H OPENINGS
 IN PLANTER WALLS AND REFER TO SHT A8.21
 FOR A DETAIL. NO DETAIL FOR THESE
 OPENINGS WAS LOCATED. PLEASE CLARIFY.
 SECTION 104.2.1.
 2B) SHTS A4.41 THRU AR.44A SUBMIT DETAIL
 FOR SCUPPERS FOR TERRACES ON THE 5TH
 FLOOR. INDICATE HEIGHT AND WIDTH.
 SECTIONS 1107 & 104.2.1. - DETAILS #1
 PRECAST SCUPPER ON S.W. CORNER NOT SHOWN
 WHERE INDICATOR IS POINTING. WHERE IS A
 CUT SECTION FOR AREA ADJACENT TO
 STAIRWAY #5. NO SECONDARY DRAIN/SCUPPER
 SHOWN. SECTION 1107. - ALSO DETAIL #2 NO
 SECONDARY DRAIN/SCUPPER IN OPPOSITE
 CORNER.
 3B) A4.60 SUBMIT DETAIL FOR SCUPPERS ON
 THE 16TH FLOOR. SECTION 1107
 4B) SHTS A4.71, A4.72, A4.73, & A4.74
 SHOW LOCATION OF ALL SECONDARY ROOF
 DRAINS FOR AREAS THAT DO NOT HAVE
 SCUPPERS. SECTION 1107
 5B) SHT A5.11 DETAIL #9 INDICATES A
 SHOWER BATHROOM DETAIL NOT SHOWN ON THE
 DETAIL INDEX. PLEASE CLARIFY
 6B) SHT A5.11 SHOW ELEVATION FOR W/C
 AND LAVS IN USABLE BATHROOMS SHOWING
 OPENINGS FOR W/C, 18" OFF WALL TO
 CENTERLINE OF FIXTURE, AND HEIGHT OF LAV
 COUNTER TOPS AT 34". FHA-98 DESIGN
 MANUAL REQUIREMENT 7.
 7B) SHTS P2.01 & P2.02 PAN DRAIN LINES
 FROM THE WATER HEATERS SHALL TERMINATE
 OVER A SUITABLY LOCATED INDIRECT WASTE
 RECEPTOR OR FLOOR SINK OR EXTEND TO THE
 EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THA 6" OR MORE THAN 24" ABOVE
 THE ADJACENT GROUND SURFACE GROUND
 SURFACE. SECTION 504.8.2.
 8B) SHT P2.02 NO SANT. SHOWN TO WASH
 MACHINE FOR UNIT #1. SECTION 104.2.1.
 9B) SHT P2.02 FLOOR PLAN DOES NOT
 REFLECT THE RISER DIAGRAM 54/68 AT UNIT
 #3. SECTION 104.2.1.
 10B) SHT P2.02 UNIT #4 INDICATE RISER
 NUMBERS AT BATH #1. SECTION 104.2.1.
 11B) SHT P2.02UNIT #4 RISER NUMBERS BY
 THE WASH MACHINE DO NOT REFLECT THE
 NUMBERS SHOWN ON THE RISER DIAGRAM.
 PLEASE CORRELATE RISER & FLOOR PLAN
 RISER DESIGNATION. SECTION 104.2.1.
 12B) SHT P2.03 UNIT 5 RISER NUMBERS AT
 POWDER ROOM ON THE FLOOR PLAN DO NOT
 REFLECT NUMBERS SHOWN ON RISER DIAGRAM.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 104.2.1.
 13B) SHT P2.03 UNIT 7 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAG. PLEASE
 CORRELATE RISER WITH FLOOR PLAN. SECTION
 104.2.1
 14B) SHT P2.06 RISER SOUTH OF ELEVATOR &
 STAIRWAY DOES NOT SHOW RISER #60.
 SECTION 104.2.1.
 15B) SHT P2.08 UNIT 3 BATH #2 DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE RISER & FLOOR PLAN. SECTION
 104.2.1.
 16B) SHT P2.10 UNIT 10 BATHROOM DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1.
 17B) SHT P2.12 UNIT 19 OFFSET FOR BATH
 #2 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 104.2.1.
 18B) SHT P2.12 UNIT 17 OFFSET DOES NOT
 REFLECT THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1.
 19B) SHT P2.12 UNIT 15 IDENTIFY RISER. -
 FLOOR PLAN DOES NOT REFLECT THE RISER
 DIAGRAM. PLEASE CORRELATE. SEC 104.2.1.
 20B) UNIT 14 BATH #2 VENT DOES NOT
 REFLECT RISER DIAGRAM. PLEASE CORRELATE.
 SECTION 104.2.1.
 21B) SHT P2.13 UNIT V MASTER BATH
 HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. SANT. OFFSET
 DOES NOT REFLECT THE RISER DIAGRAM.
 PLEASE CORRELATE. SECTION 104.2.1.
 22B) SHT P2.13 UNIT VV VENT AND SANT.
 STACK DO NOT REFLECT THE RISER DIAGRAM.
 VENT IS NOT SHOWN. PLEASE CORRELATE.
 SECTION 104.2.1.
 23B) SHT P2.14 UNIT H7 WHICH RISER DOES
 KITCHEN SINK DRAIN INTO. RISER DOES NOT
 REFLECT FLOOR PLAN AT THE WASH MACHINE.
 PLEASE CORRELATE. SECTION 104.2.1.
 24B) SHT P2.14 UNITS H1 & H2 DO NOT
 REFLECT THE DIAGRAM. PLEASE CORRELATE.
 SECTION 104.2.1.
 25B) UNIT P2.15 UNIT VV1 MASTER BATH
 DOES NOT REFLECT THE RISER DIAGRAM, AND
 DRY HORIZONTAL VENT IS NOT APPROVED.
 COMMENT RESPONSE INDICATES THAT OFFSET
 UNDER TUB IS BELOW THE FLOOR, BUT FLOOR
 PLAN SHOWS THE VENT FROM THE WATER
 CLOSET ABOVE THE SLAB CONNECTING INTO
 THIS VENT OFFSET. PLEASE CLARIFY. PLEASE
 CORRELATE. SECTIONS 905.3, 905.4 &
 104.2.1.
 26B) SHT P2.16 UNIT B7 DOES NOT REFLECT
 THE RISER DIAGRAM AT THE MASTER BATH.
 PLEASE CORRELATE. SECTION 104.2.1.
 27B) SHT P2.17 UNIT H4 TUB DRAIN LINE IS
 NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 104.2.1.
 28B) SHT P2.17 UNIT H3 POWDER ROOM RISER
 SHOWN AS SOIL STACK ON THE RISER
 DIAGRAM, BUT AS A VENT STACK ON THE
 FLOOR PLAN. - MASTER BATH LINE TO RIGHT
 OF WATER CLOSET, (RISER 37), SHOWN AS
 THE VENT LINE ON THE RISER DIAGRAM,
 WHICH WILL MAKE IT A DRY HORIZONTAL
 VENT. THIS IS NOT APPROVED BY SECTIONS
 905.3 & 905.4 - BATH #2 VENT NOT SHOWN
 ON THE FLOOR PLAN. SECTION 104.2.1.
 29B) SHT P2.18 UNIT V1 HORIZONTAL DRY
 VENT NOT APPROVED IN MASTER BATH AND
 POWDER ROOM. SECTIONS 905.3 & 905.4.
 30B) SHT P2.18 UNIT HD POWDER ROOM LAV
 ARM NOT SHOWN. SECTION 104.2.1.
 31B) SHT P2.18 UNIT H3 VENT LINE FOR
 MASTER BATH NOT SHOWN. SECTION 104.2.1.
 32B) SHT P2.18 UNIT H6 VENT LINE FOR
 MASTER BATH NOT SHOWN. SECTION 104.2.1.
 33B) SHT P2.19 UNIT V VENT LAYOUT DOES
 NOT REFLECT THE RISER DIAGRAM AT MASTER
 BATH. SECTION 104.2.1.
 34B) SHT P2.19 UNIT VV STACK & VENT FOR
 KITCHEN MISSING. SECTION 104.2.1.
 35B) SHT P2.19 UNIT B8 NO SANITARY OR
 VENT TO KITCHEN SINK. SECTION 104.2.1.
 36B) SHT P2.20 UNIT HH1 PIPING FOR
 KITCHEN SINK & POWDER ROOM MISSING.
 SECTION 104.2.1.
 37B) SHT P2.20 UNIT H7 INDICATE RISER
 NUMBER AND SANITARY DOES NOT REFLECT THE
 RISER DIAGRAM. SECTION 104.2.1.
 38B) SHT P2.20 UNIT H2 SHOW DWV PIPING
 TO REFLECT RISER DIAGRAM. SECTION
 104.2.1.
 38B) SHT P2.21 UNIT H1 SHOW DWV PIPING
 TO REFLECT RISER DIAGRAM. SECTION
 104.2.1.
 39B) SHT P2.21 UNIT A1 BATH #2 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 40B) SHT P2.22 UNIT B7 SHOW DWV PIPING
 TO REFLECT RISER DIAGRAM. SECTION
 104.2.1.
 41B) SHT P2.22 UNIT B7 BATH #2 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 42B) SHT P2.23 UNIT A1 SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 43B) SHT P2.24 UNIT HD SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 44B) SHT P2.24 UNIT H3 SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1. - RISER (24) DESIGNATION IN
 WRONG LOCATION. SECTION 104.2.1.
 45B) SHT P2.24 UNIT H6 SHOW DWV PIPING
 TO REFLECT THE RISER DIAGRAM. SECTION
 104.2.1
 46B) SHT P2.25 UNIT L INDICATE THE
 LOCATION OF THE CONTINUATION OF RISERS
 (67) & (68). SECTION 104.2.1.
 47B) SHT P2.25 UNIT C OFFSET DOES NOT
 REFLECT THE RISER DIAGRAM, (6). SECTION
 104.2.1.
 48B) SHT P2.25 UNIT C SHOW RISER
 DESIGNATION NUMBER FOR RISER #5 BY W/M.
 SECTION 104.2.1.
 49B) SHT P2.25 UNIT C RWL #1 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 50B) SHT P2.25 UNIT B5 RISER (3)(56)(57)
 DOES NOT REFLECT THE RISER DIAGRAM.
 (KITCHEN DRAIN ARM NOT SHOWN). SECTION
 104.2.1.
 51B) SHT P2.25 UNIT B6 MASTER BATH DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 52B) SHT P2.26 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 53B) SHT P2.26 UNIT E1 RWL #4 DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 54B) SHT P2.27 UNIT A BATH #2 NOT VENTED
 NOT SANITARY TO RISER (25). SECTION
 104.2.1.
 55B) SHT P2.27 UNIT B1 SHOW RISER
 DESIGNATION NUMBERS FOR (29)(30)(31)(32)
 - VENT LINES NOT SHOWN - NO SANT. DRAIN
 LINE TO KITCHEN SINK. SECTION 104.2.1.
 56B) SHT P2.28 UNIT B1 NO VENT LINES
 SHOWN. SECTION 104.2.1.
 57B) SHT P2.28 UNIT B2 VENT LINES TO
 REFLECT RISERS DIAGRAM BATH #2 - MASTER
 BATH LAV DRAIN CONNECTION TO BRANCH IS
 SHOWN INSTALLED AGAINST THE FLOW.
 SECTION 706.3. - RISER #37 DESIGNATION
 SHOWN IN THE WRONG LOCATIONS. PLACE NEXT
 TO RISER. SECTION 104.2.1.
 58B) SHT P2.28 UNIT A SHOW ALL PIPING TO
 REFLECT RISERS. SECTION 104.2.1.
 59B) SHT P2.29 BOTH UNITS SHOW ALL
 PIPING TO REFLECT THE RISER DIAGRAMS.
 SECTION 104.2.1.
 60B) SHT P2.30 UNIT A BATH #2 DOES NOT
 REFLECT RISER DIAGRAM. SECTION 104.2.1.
 61B) SHT P2.31 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 62B) SHT P2.32 UNIT E1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. RISER 11
 - SHOW ALL PIPING TO REFLECT RISER
 DIAGRAM. SECTION 104.2.1.
 63B) SHT P2.32 UNITS D1 & G1 SHOW ALL
 PIPING TO REFLECT THE RISER DIAGRAMS.
 SECTION 104.2.1.
 64B) SHT P2.33 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 65B) SHT P2.34 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 66B) SHT P2.35 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SHOW THE LOCATION OF
 RISER (45). SECTION 104.2.1.
 67B) SHT P2.36 ALL UNITS SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 68B) SHT P2.36 UNIT C1 SHOW RISER
 DESIGNATION #(49). SECTION 104.2.1.
 69B) UNIT E KITCHEN PIPING DOES NOT
 REFLECT THE RISER DIAGRAM. SECTION
 104.2.1.
 70B) SHT P2.36 UNIT E KITCHEN SINK
 PIPING DOES NOT REFLECT THE RISER
 DIAGRAM. SECTION 104.2.1
 71B) SHT P2.37B) UNITS B5 & B6 MASTER
 BATH DOES NOT REFLECT THE RISER DIAGRAM
 AT LAVS NEXT TO THE WATER CLOSET.
 SECTION 104.2.1.
 72B) SHT P2.38B) UNIT G1 SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1.
 73B) SHT P2.39 ALL UNITS SHOW PIPING TO
 REFLECT RISERS. SECTION 104.2.1.
 74B) SHT P2.40 UNIT B1 SHOW PIPING TO
 REFLECT THE RISERS. SHOW RISER LOCATION
 AND RISER DESIGNATION NUMBERS. SECTION
 104.2.1.
 75B) SHT P2.41 UNITS B & D SHOW PIPING
 TO REFLECT THE RISERS. SECTION 104.2.1.
 76B) SHT P2.42 UNIT A SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 77B) SHT P2.44 UNIT G1 SHOW PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 78B) SHT P2.45 UNIT R1 FLOOR PLAN DOES
 NOT REFLECT THE RISER DIAGRAM. (26)
 SECTION 104.2.1.
 79B) SHT P2.45 UNITS B4 & G SHOW PIPING
 TO REFLECT RISER DIAGRAMS. SECTION
 104.2.1.
 80B) SHT P2.46 UNIT P SHOW PIPING TO
 REFLECT RISER (36) AT BATH #2. SECTION
 104.2.1.
 81B) SHT P2.47 UNIT U DOES NOT REFLECT
 RISER (44) BATH #2. SECTION 104.2.1.
 82B) SHT P2.48 SHOW PIPING FOR 2 LAVS.
 SECTION 104.2.1.
 83B) SHT P2.51 SHOW ALL PIPING TO
 REFLECT RISER DIAGRAMS. SECTION 104.2.1.
 84B) SHT P2.52 UNIT R VENT MISSING BATH
 #2 LAV. SECTION 104.2.1.
 85B) SHT P2.55 INDICATE THE LOCATION FOR
 THE SECONDARY ROOF DRAINS. SECTION
 104.2.1.
 86B) SHT P2.55 OVERFLOW SHALL DRAIN FROM
 COOLING TOWERS TO STORM - DRAIN FROM
 COOLING TOWERS TO SANITARY. PLEASE
 INDICATE ON PLANS. SECTION 104.2.1.
 87B) SHT P2.55 5" REQUIRED FOR STORM
 DRAIN DOWNSTREAM OF 4" R.D. @ 520 SF.
 TABLE 1106.3
 88B) SHT P2.56 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107.
 89B) SHT P2.57 INDICATE LOCATION OF ALL
 SECONDARY ROOF DRAINS. SECTIONS 104.2.1
 & 1107.
 90B) SHT P2.57 RWL #6 3" PD @ 80 SF NOES
 NOT REFLECT THE RISER DIAGRAM. - 3" PD @
 50 SF DOES NOT REFLECT THE RISER
 DIAGRAM. - PIPE SIZE DOWNSTREAM OF 3" PD
 @ 280 SF REQUIRES A MINIMUM OF 5" PIPE.
 SECTION 104.2.1.
 91B) SHT P2.57 FLOOR PLAN DOES NOT
 REFLECT THE RISER DIAGRAM. WOMENS HDCP
 TOILET LAV. RISER (25) IS A DRY VENT
 WHICH IS NOT APPROVED. SECTIONS 905.3 &
 905.4. SECTION 104.2.1.
 92B) SHT P2.58 RWL #7 DOWNSTREAM OF 3"DD
 @ 125 SF 5" REQUIRED. 4" SHOWN. TABLE
 1106.3. - 3"PD @ 220 SF DOES NOT REFLECT
 RISER SHOWN AND 211 SF. PLEASE CORRELATE
 - RWL #8 3"PD @ 88 SF DOES NOT REFLECT
 RISER DIAGRAM SHOW AS 80 SF. PLEASE
 CORRELATE. SECTION 104.2.1.
 93B) SHT P2.64 STORM DRAIN LAYOUT DOES
 NOT REFLECT RISER (2)(3) IN UNIT E,
 RISER (4)(5) IN UNIT B4, AND RISER
 (7)(8) IN UNIT D. SECTION 104.2.1.
 94B) SHT P2.64 STORM DRAIN LINE RUNNING
 EAST TO WEST AND CONNECTING TO RISER
 (4)(5) SHALL SLOPE 1/4"/FT THE ENTIRE
 LENGTH. SECTION 704.1
 95B) SHT P3.00 SANITARY RISER DIAGRAM
 FOR TOILET ROOM POOL DECK, DRY
 HORIZONTAL VENT NOT APPROVED. SECTIONS
 905.3 & 905.4.
 96B) SHT P3.00 SANITARY RISER DIAGRAM
 FOR TOILET ROOM POOL DECK, FLOOR DRAIN
 BY SHOWER NOT APPROVED FOR INDIRECT
 WASTE. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 97B) SHT P3.00 DOMESTIC WATER RISER
 DIAGRAM POOL DECK TOILET ROOMS, LANAI
 LEVEL PUBLIC TOILETS, & WATER RISER
 DIAGRAM 5TH FLOOR PUBLIC AREA, THE WATER
 SUPPLY IS MISSING FOR 1 LAV, POOL DECK
 TOILET ROOMS, AND FULL OPEN VALVES ARE
 REQUIRED ON EVERY WATER DOWN-FEED PIPE.
 SECTION 606.1(4).
 98B) SHTS P3.05 THRU P3.15 ALL UNIT
 WATER RISER DIAGRAMS, DELETE ALL AIR
 CHAMBERS AS THEY ARE NOT APPROVED.
 SECTION 604.9. - ALL WATER LINES TO THE
 REF. ICE MAKERS ARE REQUIRED TO HAVE A
 WATER HAMMER ARRESTOR. SECTION 604.9. -
 SOME UNITS SHOW A SEPARATE WATER LINE TO
 THE REF. ICE MAKER AND A LINE UNDER THE
 KITCHEN SINK FOR THE REF. ICE MAKER.
 PLEASE CLARIFY AS THEY DO NOT REFLECT
 THE RISER DIAGRAM IN MOST CASES. RISERS
 DO NOT SHOW TWO LINES TO THE ICE MAKER.
 - SOME RISERS ARE MISSING SUPPLY LINES
 TO FIXTURES. SECTION 104.2.1.
 99B) SHT P3.16 RISER (4) OFFSET ON 16TH
 FLOOR NOT SHOWN. - RISER (5) TIE OFFSET
 VENT IN AS SHOWN IN EXAMPLE ON ATTACHED
 SHEET. (FIG. 915.2)
 100B) SHT P3.17 RISER (6) TIE OFFSET
 VENT IN AS SHOWN IN EXAMPLE ON ATTACHED
 SHEET. (FIG 915.2) - 5TH FLOOR PLUMBING
 PIPE LAYOUT IS NOT SHOWN. (DIFFERENT
 FROM TYPICAL - NO OFFSET SHOWN. - RISER
 (56) TIE OFFSET VENT IN AS SHOWN IN
 EXAMPLE ON ATTACHED SHEET. (FIG. 915.2)
 - RISER (8) DOES NOT REFLECT THE FLOOR
 PLAN 5TH FLOOR, NOR DOES IT REFLECT THE
 FLOOR PLAN 6TH THRU 15TH FLOORS FOR THE
 LAVS. SECTION 104.2.1.
 101B) SHT P3.18 RISER (69) DOES NOT
 REFLECT THE FLOOR PLAN. - RISER (10)
 DOES NOT REFLECT THE FLOOR PLAN 17TH
 THRU 21ST FLOOR. - RISER (11) NO BRANCH
 LINES FROM 4TH FLOOR THRU 15TH FLOOR.
 PLEASE CLARIFY. SECTION 104.2.1.
 102B) ALL RISERS THAT HAVE OFFSET VENTS,
 THE CONNECTION FROM THE WASTE STACK TO
 THE VENT STACKS SHALL BE BY AN UPRIGHT
 WYE FITTING NOT A SANT. TEE FITTING AS
 SHOWN ON SOME RISERS, AND SHALL BE
 CONNECTED ON THE UPPER SECTION AS SHOWN
 ON ATTACHED SHEET. (FIG 915.2)
 103B) SHTS P3.16 THRU P3.25 THE
 FOLLOWING SANITARY RISER DIAGRAMS WERE
 NOT LOCATED ON THE BUILDING DRAIN
 ISOMETRIC. 1, 2, 16, 8, (2 #8'S SHOWN),
 10, 59, 12, 13, 14, 17, 15, 18, 19, 20,
 21, 22, 72, 57, 75, 40, 41, 42, 37.
 104B) SHTS P3.27 THRU P3.36 THE
 FOLLOWING RISERS SHOWN ON THE BUILDING
 DRAIN ISOMETRIC WERE NOT FOUND. 67, 83,
 53, 68, 51, 58, 84, 85, 86, 87, 89, 90,
 91, 84, 73, 33, 34, 74, 81.
 105B) SHT P3.21 SANT. RISER #23 SHOWS
 16TH FLOOR THEN 15TH FLOOR ABOVE.
 106B) SHT P3.21 SANT. RISERS 24, & 36
 INDICATE WHERE RISER #25 WILL CONNECT TO
 THESE RISERS. PLEASE CLARIFY AND
 INDICATE SHEET WHERE RISER #25 IS
 LOCATED. SECTION 104.2.1.
 107B) SHT P3.21 RISER 71 INDICATE HOW
 RISER 54 TIES INTO THIS RISER AS IT IS
 NOT SHOWN ON PREVIOUS FLOORS. SECTION
 104.2.1.
 108B) SHT P3.21 RISER 26/35 KITCHEN SINK
 NOT SHOWN, DOES NOT REFLECT THE FLOOR
 PLAN, WASH MACHINE/LAUNDRY SINK OFFSET
 TO THE RIGHT SIDE NOT TO THE LEFT,
 VENTING FROM LAV DOES NOT REFLECT FLOOR
 PLAN. SECTION 104.2.1.
 109B) SHT P3.22 RISER 55 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 110B) SHT P3.22 RISER 29/31, RISER 31
 NOT SHOWN 17TH TO 21ST FLOOR, MASTER
 BATH 15TH FLOOR MAXIMUM 4 FU MAX. ON 2"
 WET VENT. SECTION 104.2.1. & TABLE
 909.3.
 111B) SHT P3.22 RISER 30/32 ONLY RISER
 32 IS SHOWN. NO 16TH FLOOR PIPING SHOWN,
 ONLY 4 FU MAX. ON 2" WET VENT. SECTION
 104.2.1. AND TABLE 909.3.
 112B) SHT P3.23 RISER 38 ONLY 4 FU MAX.
 ON 2" WET VENT. TABLE 909.3.
 113B) SHT P3.24 SANT. RISER 77 16TH
 FLOOR DOES NOT REFLECT THE FLOOR PLAN,
 AND NO FIXTURE BRANCH LINES OR FIXTURES
 SHOWN FOR FLOORS 6 THRU 15. SECTION
 104.2.1.
 114B) SHT P3.24 RISER 76 ONLY 4 FU MAX.
 ON 2" WET VENT. TABLE 909.3
 115B) SHT P3.24 RISER 44 OFFSET VENT
 REQUIRED. SECTION 915
 116B) SHT P3.25 RISER 47 16TH FLOOR DOES
 NOT REFLECT THE FLOOR PLAN. NO SHOWER ON
 RISER. SECTION 104.2.1.
 117B) SHT P3.25 RISER 49 OFFSET VENT
 SHALL BE CONNECTED ABOVE THE BRANCH LINE
 PRIOR TO OFFSET. SECTION 915 - 16TH
 FLOOR 4 FU MAX. ON 2" WET VENT. TABLE
 909.3. - 15TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN. SECTION 104.2.1.
 118B) SHT P3.26 RISER 66 15TH FLOOR 4 FU
 MAX. ON 2" WET VENT. TABLE 909.3.
 119B) SHT P3.27 DRY HORIZONTAL VENT NOT
 APPROVED. SECTIONS 905.3 & 905.4. - 4 FU
 MAX. ON 2" WET VENT. TABLE 909.3 - NO
 VENT TERMINATION SHOWN FOR AREA AT LEFT
 SIDE OF BLDG DRAIN. - NO VENT SHOWN FOR
 LAV AT MEZZ. LEVEL. SECTION 901.2.1. -
 OFFSET VENT REQUIRED FOR RISER (6).
 SECTION 915. - CLEANOUT REQUIRED 4' AFF
 FOR W/M. SECTION 708.10. - VENTS FOR
 KITCHEN SINKS DO NOT REFLECT THE FLOOR
 PLAN. (NOT SHOWN ON FLOOR PLAN). SECTION
 104.2.1. - INDICATE SHEET NUMBER FOR THE
 CONTINUATION OF RISERS 53, 67/83 UNABLE
 TO LOCATE. SECTION 104.2.1.
 120B) EVERY VENT STACK SHALL CONNECT TO
 THE BASE OF THE DRAINAGE STACK. SECTION
 903.4
 121B) SHT P3.28 RISER 68 INDICATE SHEET
 NUMBER FOR CONTINUATION OF RISER.
 SECTION 104.2.1. - RISER 54 OFFSET VENT
 REQUIRED, AND 4 FU MAX. ON 2" WET VENT.
 SECTION 915 AND TABLE 909.3. - RISER 7
 OFFSET VENTS REQUIRED. UPPER OFFSET,
 (2ND FLOOR),VENT SHALL BE CONNECTED TO
 THE VERTICAL STACK NOT THE BRANCH LINE.
 SECTION 915. - RISER 3, 56, 57 OFFSET
 VENT REQUIRED SECTION 915 - DOES NOT
 SHOW KITCHEN SINK 5TH FLOOR SECTION
 104.2.1. - MISLABELED AS RISER 51 -
 SECTION 104.2.1. - WASH MACHINE GROUND
 FLOOR REQUIRES THAT CLEANOUT IS 4' AFF.
 SECTION 104.2.1. - RISERS 4, 9, 58, 9 AT
 BASE, HORIZONTAL DRY VENT NOT APPROVED.
 SECTIONS 905.3 & 905.4. VENT SHALL BE
 CONNECTED AT THE BASE OF THE STACK.
 SECTION 903.4 - THESE RISERS ARE
 INDICATED AS 4, 9, 10, 58, & 59. PLEASE
 CORRELATE. SECTION 104.2.1. - OFFSET
 SHALL CONNECT ABOVE THE BRANCH LINE. FIG
 915.2. - RISER 58 SOME FIXTURES ARE
 MISLABELED, ON NOT LABELED AT ALL.
 SECTION 104.2.1. - VENT TERMINATION FOR
 2ND FLOOR BATHROOM NOT SHOWN. SECTION
 104.2.1. - RISER 4/9 MISLABELED FIXTURE.
 SECTION 104.2.1, WASH MACHINES, KITCHEN
 SINKS, AND BATHROOMS SHALL NOT DRAIN
 PAST THE VENT FOR THE BATHROOM ON THE
 MEZZ. LEVEL. SECTION 908.3 - DWV FOR THE
 MEZZ. LEVEL DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - SECOND FLOOR
 POWDER ROOM DOES NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1. - BATHROOM GROUPS
 FOR THE THIRD AND FORTH FLOORS NOT SHOWN
 ON RISER 4. SECTION 104.2.1.
 122B) ALL SANITARY RISER DIAGRAMS, SHOW
 ALL PIPE SIZES. SIZES ARE MISSING ON
 SOME PIPES. SECTION 104.2.1. & TABLE
 710.1(1).
 123B) SHT P3.29 RISER 69 4 FU MAX. ON 2"
 WET VENT. TABLE 909.3 - RISER 11 DOES
 NOT REFLECT THE FLOOR PLAN - AND NO
 BRANCH LINES FROM 4TH FLOOR THRU 15TH
 FLOOR. - OFFSET VENTS REQUIRED - RISER
 60 OFFSET VENT REQUIRED - GROUND FLOOR
 AT RISER 11/60 DOES NOT REFLECT THE
 FLOOR PLAN - RISER 86 SECOND FLOOR DOES
 NOT REFLECT THE FLOOR PLAN - SHOW
 DESIGNATION NUMBER FOR RISER 88 - RISER
 89 4 FU MAX. ON 2" WET VENT - 89/90/91
 MEZZ. LEVEL BATHROOM DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 104.2.1. & 915
 TABLE 909.3.
 124B) SHT P3.30 RISER 77 DOES NOT
 REFLECT THE FLOOR PLAN, WASH MACHINES
 NOT SHOWN. - RISER 47 OFFSET VENTS
 REQUIRED, 5TH FLOOR DOES NOT REFLECT THE
 FLOOR PLAN, NO KITCHEN SINK SHOWN. -
 RISER 49 OFFSET VENTS REQUIRED. - RISER
 49 DOES NOT REFLECT THE FLOOR PLAN, LAV
 MISSING IN MASTER BATH 2ND FLOOR, OFFSET
 VENTS REQUIRED, 2ND FLOOR INDICATED
 DOWNSTREAM OF MEZZ. - RISER 65 DOES NOT
 REFLECT THE FLOOR PLAN. - RISER 50 DOES
 NOT REFLECT THE FLOOR PLAN ON THE 2ND
 FLOOR AND THE 5TH FLOOR, OFFSET VENTS
 REQUIRED, FIXTURE MISLABELED, 4 FU MAX.
 ON 2" WET VENT, DRY HORIZONTAL VENT NOT
 APPROVED. SECTIONS 104.2.1, 915, & TABLE
 909.3
 125B) SHT P3.31 RISER 24 DOES NOT
 REFLECT THE FLOOR PLAN 4TH FLOOR, 4 FU
 MAX. ON 2" WET VENT, OFFSET VENTS
 REQUIRED, DRY HORIZONTAL VENT NOT
 APPROVED. - RISER 54 OFFSET VENTS
 REQUIRED. - RISER 26 OFFSET VENTS
 REQUIRED. - RISER 27/28 OFFSET VENTS
 REQUIRED, 4 FU MAX. ON 2" WET VENT, DOES
 NOT REFLECT THE FLOOR PLAN AT/BELOW MEZZ
 LEVEL. - RISER 55/28/84 RISER
 DESIGNATION NUMBER DOES NOT REFLECT THE
 FLOOR PLAN, (SHOW AS 55/73/84), PLEASE
 CLARIFY, DOES NOT REFLECT THE FLOOR PLAN
 NO WASH MACHINES SHOWN, OFFSET VENTS
 REQUIRED. SECTIONS 104.2.1, 915, & TABLE
 909.3.
 126B) SHT P3.32 RISER 29/30/31/32 OFFSET
 VENTS REQUIRED, FIXTURE MISLABLED,
 FIXTURE BRANCH LINE SHALL NOT CONNECT TO
 THE HORIZONTAL OFFSET. - RISER 34 DOES
 NOT REFLECT THE FLOOR PLAN, OFFSET VENTS
 REQUIRED. - RISER 33/35 OFFSET VENTS
 REQUIRED, LAV VENTS 2ND THRU 4TH FLOOR
 DO NOT REFLECT THE FLOOR PLAN. - RISER
 56/74/81 OFFSET VENTS REQUIRED, KITCHEN
 SINK VENTS DO NOT REFLECT THE FLOOR PLAN
 2ND THRU 4TH FLOORS. - RISER 56 NO
 HORIZONTAL DRY VENT, DOES NOT REFLECT
 THE FLOOR PLAN 2ND & 3RD FLOORS, (W/M'S)
 SECTIONS 104.2.1, AND 711.2.
 127B) SHT P3.33 SANT. ISOMETRIC SHOWS
 TWO HORIZONTAL DRY VENTS, LEFT OF RISER
 61. THESE ARE NOT APPROVED. PER SECTIONS
 905.3 & 905.4. - WASH MACHINE LEFT OF
 RISER 61 DOES NOT REFLECT THE FLOOR
 PLAN, - RISER 61 OFFSET VENT REQUIRED,
 DOES NOT REFLECT THE FLOOR PLAN - RISER
 23 INDICATES TWO 4TH FLOORS, LAV ARMS DO
 NOT REFLECT THE FLOOR PLAN, OFFSET VENTS
 REQUIRED. - RISER 25 EXTRA BRANCH LINE
 CONNECTED TO STACK BELOW 2ND FLOOR NOT
 APPROVED, OFFSET VENTS REQUIRED, DOES
 NOT REFLECT THE FLOOR PLAN 5TH FLOOR, NO
 3RD FLOOR PIPING SHOWN, TUB MISSING 4TH
 FLOOR, 4 FU MAX. ON 2" WET VENT.
 SECTIONS 104.2.1, 915, 905.3, 905.4,
 706.3 & TABLE 909.3.
 128B) SHT P3.34 RISER 60 DOES NOT
 REFLECT THE FLOOR PLAN, UPRIGHT WYE
 REQUIRED AT VENT STACK CONNECTION TO THE
 WASTE STACK. - RISER 62 DOES NOT REFLECT
 THE FLOOR PLAN. - RISER 45 DOES NOT
 REFLECT THE FLOOR PLAN, - RISER 64 DOES
 NOT REFLECT THE FLOOR PLAN. - RISER 44
 VENT SHALL CONNECT TO BASE OF STACK,
 LABEL ALL FIXTURES. - RISER 76 DOES NOT
 REFLECT THE FLOOR PLAN, CONNECT VENT
 STACK TO BASE OF SANT. STACK, RISER
 SHOWS CONDITION ON 2ND FLOOR THAT IS
 ACTUALLY ON THE 5TH FLOOR ONLY, DRY
 HORIZONTAL VENT NOT APPROVED. - RISER 46
 SHOW ALL PIPE SIZES. SECTIONS 104.2.1,
 905.3, 905.4,
 129B) SHT P3.35 RISER 38 OFFSET VENTS
 REQUIRED, RELIEF VENT REQUIRED, RISER
 DOES NOT REFLECT THE FLOOR PLAN, (NO
 PIPING SHOW FOR 3RD THRU 5TH FLOORS -
 SHOWER MISSING IN BATHROOM), - GROUND
 FLOOR WASH MACHINE MISLABELED AS SHOWER,
 CLEANOUT SHALL BE 4' AFF AT W/M. -
 IDENTIFY OTHER RISER AT END OF RUN.
 SECTIONS 104.2.1, 915, 914, 708.10.
 130B) SHT P3.36 GROUND FLOOR DOES NOT
 REFLECT THE FLOOR PLAN, (FD IN TRASH
 ROOM NOT SHOWN, KITCHEN SINK - W/M AREA,
 AND VENTING), INDICATE WHY 10 FU FOR
 CLEANOUT AT END OF RUN. - RISER 71
 OFFSET VENTS REQUIRED, NO PIPING FOR 3RD
 FLOOR, NO KITCHEN SINK ON 4TH FLOOR,
 INDICATE FLOOR LEVEL TOP OF RISER. -
 RISER 37 VENT STACK SHALL CONNECT AT THE
 BASE OF THE STACK, NO HORIZONTAL DRY
 VENT, OFFSET VENT REQUIRED, 5TH FLOOR
 DOES NOT REFLECT THE FLOOR PLAN, FIXTURE
 MISLABELED AND 4 FU MAX. ON 2" WET VENT
 4TH FLOOR, UNABLE TO FIND CONTINUATION
 OF RISER. - RISER 36 SHOWS TYPICAL
 PIPING FOR 3RD & 4TH FLOORS, BUT FLOOR
 PLANS ARE DIFFERENT. SECTIONS 104.2.1.
 915, 903.4, 905.3, 905.4.
 131B) SHT P3.37 CHECK ADDITION FOR
 SQUARE FOOTAGE AT DRAINS. 4" @ 1665 SF
 TO BE A MINIMUM OF 5" PIPE RWL 4 TABLE
 1106.3. SOME FITTINGS NOT DIRECTING
 STORM WATER IN DIRECTION OF FLOW. - SHOW
 SF FOR TD'S GROUND FLOOR DRAINAGE RISER.
 132B) SHT O3.38 CHECK ADDITION ON RWL
 2&3. IS 3" PD 680SF OR 80 SF? PLUS CHECK
 ADDITION OF PD'S & DD'S = 963 SF BUT
 2320 SF SHOWN. 5TH FLOOR RISER 2/3 DOES
 NOT REFLECT THE FLOOR PLAN. DD @603 SF &
 PD @ 1018 SF NOT SHOWN. PLEASE CLARIFY.
 SECTION 104.2.1.
 133B) SHT P3.39 RECHECK ADDITION OF SF
 AS IT ACCUMULATES IN THE SYSTEM, SOME
 DRAIN SF DOES NOT REFLECT ROOF PLAN SF
 AT DECK DRAINS, & PLANTER DRAINS, PIPE
 SIZING NOT CORRECT, SHOW SF AS IT
 ACCUMULATES IN THE SYSTEM, SHOW SLOPE OF
 PIPE REQUIRED. SECTION 104.2.1, 1106, &
 1107.
 134B) THE FOLLOWING UNITS WERE NOT
 LOCATED. "C2", 'D2" & "BT" PLEASE
 INDICATE LOCATION FOR THESE UNITS.
 135B) THE FOLLOWING WATER RISER DIAGRAMS
 WERE NOT FOUND: SHTS P2.16/P2.22 "B7",
 SHTS P2.29 "B", SHT P2.33 "J1", P2.35
 "B", P2.41 "B", P2.46 "S1", P2.52 "S1"
 135B) PLANS STILL SEEM TO BE INCOMPLETE
 AND MORE COMMENTS MAY BE FORTHCOMING
 WHEN PLANS ARE RESUBMITTED. RED LINE
 PLANS WERE REQUESTED TO BE RETURNED TO
 HELP THE REVIEW PROCESS FOR THE SECOND
 REVIEW. THESE WERE NOT RETURNED. I WILL
 BE KEEPING THE RED LINE SET OF PLANS IN
 ORDER TO HELP THE REVIEW PROCESS ON NEXT
 RESUBMIT.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION. -
 THIS ALSO WAS NOT DONE WHEN PLANS WERE
 RESUBMITTED. MOST RESPONSE NOTES WERE NO
 MORE THAN A FEW WORDS AND NO INDICATION
 OF WHERE CORRECTION COULD BE FOUND,
 RESULTING IN MANY HOURS REVIEWING THE
 PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]