Plan Review Notes For Permit 04120353 |
Permit Number |
04120353 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-04-28 00:00:00 | 1) NOTE #1- EXIT PATH MAY REQUIRE | | STRIPING OR SOME OTHER APPROVED METHOD | | OF MARKING TO MAINTAIN A CLEAR AND | | UNOBSTRUCTED PATH OF TRAVEL. | | | | 2) NOTE #24- DOOR SWINGS ON STAIRS #7&8 | | APPEAR TO BE SWINGING IN THE WRONG | | DIRECTION. | | | | 3) NOTE #26- NO RESPONSE CAN BE FOUND | | REGARDING TWO FIRE DEPARTMENT | | CONNECTIONS. | | | | 4) NOTE #37- NO RESPONSE FOUND REGARDING | | SMOKE DETECTOR IN FIRE COMMAND ROOM. | | | | 5) NOTE #57- NO RESPONSE FOUND REGARDING | | SMOKE MANAGEMENT REQUIREMENTS. | | | | 6) NOTE #59- HOW WAS THE COMMENT | | REGARDING DIRECTION OF EGRESS ADDRESSED? | | | | | | 7) NOTE #58- NO RESPONSE FOUND | | | | 8) NOTES #60-64- NO RESPONSES FOUND. | | | | NOTE: WHEN RESPONDING TO REVIEW NOTES, | | PLEASE IDENTIFY THE SHEET NUMBER WITH | | REVISION CLOUDS TO HELP EXPEDITE THIS | | PROCESS. | | | | | | MIKE WENNERGREN, A/CAPTAIN | | WPBFR(561) 835-2910 OR 805-6722 |
|