2005-04-08 00:00:00 | ************ UNSAT 2ND REVIEW ********* |
| |
| PLEASE SEE MANY NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| PLEASE ALSO SEE NEW NOTES DUE TO PLANS |
| CONTAINING MORE INFORMATION THAN |
| SUBMITTED ON PREVIOUS REVIEW. |
| |
| *************************************** |
| PLEASE SEE FIRST PART OF REVIEW IS A |
| DIRECT OVERVIEW OF PREVIOUS NOTES, NEW |
| NOTES WILL BE FOLLOWING. |
| *************************************** |
| |
| 1)NOTE: NOTE #1, OK, HOWEVER PLEASE SEE |
| NOTE #19 IN THIS AND PREVIOUS REVIEW. |
| |
| 2)NOTE: NOTE #2 NO, PLEASE SEE REQUIRED |
| WIND LOADING INFORMATION IS NOT NOTED ON |
| ELECTRICAL PLANS FOR POLES. IF THIS |
| INFORMATION IS PROVIDED ON ADDITIONAL |
| SHEETS FOR BLDG REVIEW, THIS IS FINE AND |
| REQUIRED, HOWEVER THIS INFORMATION WILL |
| NEED TO BE ELECTRICAL SHEET FOR |
| ELECTRICAL CONTRACTOR ETC. |
| WINB LOADING NOTE(S) SHOULD REFERENCE |
| FBC 140 MPH. |
| |
| 3)NOTE: NOTE #3 NO, PLEASE SEE SHEET |
| ATTACHED WHICH IS A PRINT OUT FROM |
| DBPR'S WEBSITE. PLEASE SEE LICENSE |
| INFORMATION PROVIDED ON TITLE BLOCKS FOR |
| ARCHITECTUAL FIRM DOES NOT APPEAR TO BE |
| ACCURATE. PLEASE SEE ATTACHED SHEET |
| WHICH SHOWS BC ARCHITECTS INC. WITH AN |
| ARCHITECTUAL BUS/FIRM LICENSE NUMBER OF |
| AA#0003360. PLEASE SEE TITLE BLOCKS FOR |
| ALL SHEETS AND FOR ALL TRADES APPEARS TO |
| INDICATE THIS FIRM LICENSE NUMBER AS |
| 0008129???. |
| PLEASE SEE FAC 61G1-16.004, FS 481.219. |
| PLEASE SEE THIS IS REQUIRED ON ALL |
| SHEETS AND FOR ALL TRADES WHEATHER OR |
| NOT COMMENT IS MADE BY OTHER |
| REVIEWER(S). |
| PLEASE SEE ENGINEERING FIRM'S TITLE |
| BLOCK HAS BEEN CORRECTED. |
| |
| 4)NOTE: NOTE #4, OK. NOTE ADDED FOR "NO |
| SWIMMING" AFTER DUSK. |
| |
| 5)NOTE: NOTE #5 OK. |
| |
| 6)NOTE: NOTE #6 OK, FIRE RATING VERIFIED |
| FOR DIRECT ACCESS TO MAIN ELECTRICAL |
| ROOM. HOWEVER, NOTES FOR SIGNAGE, MAPS |
| AND/OR DIRECTORY COULD NOT BE LOCATED ON |
| PLANS. |
| 230.2E 700.8A,701.9,702.8 ETC. |
| A SIGN SHALL BE PLACED AT THE SERVICE |
| ENTRANCE EQUIPMENT INDICATING TYPE AND |
| LOCATION OF ON-SITE EMERGENCY POWER |
| SOURCES. |
| PLEASE SEE ALL SIGNAGE REQUIRED TO BE 1" |
| MIN WITH CONTRASTING BACKGROUND. |
| SIGNAGE/MAPPINGALSO REQUIRED AT FIRE |
| COMMAND RM AND AT ACCESS DOOR CLOSEST TO |
| MAIN ELECTRICAL ROOM. |
| SIGNAGE FOR ALL ELECTRICAL ROOMS. |
| PLEASE ALSO SEE 110.16 |
| 110.16 FLASH PROTECTION. |
| SWITCHBOARDS, PANELBOARDS, INDUSTRIAL |
| CONTROL PANELS, AND MOTOR CONTROL |
| CENTERS THAT ARE IN OTHER THAN DWELLING |
| OCCUPANCIES AND ARE LIKELY TO REQUIRE |
| EXAMINATION, ADJUSTMENT, SERVICING, OR |
| MAINTENANCE WHILE ENERGIZED SHALL BE |
| FIELD MARKED TO WARN QUALIFIED PERSONS |
| OF POTENTIAL ELECTRIC ARC FLASH HAZARDS. |
| THE MARKING SHALL BE LOCATED SO AS TO BE |
| CLEARLY VISIBLE TO QUALIFIED PERSONS |
| BEFORE EXAMINATION, ADJUSTMENT, |
| SERVICING, OR MAINTENANCE OF THE |
| EQUIPMENT. |
| SEE FIRE COMMENTS FOR "KNOW BOX" |
| LOCATIONS. |
| |
| 7)NOTE: NOTE #7,OK HOWEVER PLEASE SEE |
| SHEETS E 2.11,2.12, MANY ELECTRICAL |
| DEVICES/FIXTURES APPEAR TO BE SHOWN WITH |
| OUT CIRCUITS. ARE THESE MISPRINTED AND |
| REPEATED ON OTHER SHEETS. |
| |
| 8)NOTE: NOTE #8 NO, PLEASE SEE 620.23.24 |
| ETC. |
| PLEASE SEE ELEVATOR EQUIPMENT RMS. |
| A SEPARATE BRANCH CIRCUIT SHALL SUPPLY |
| THE MACHINE ROOM OR CONTROL |
| ROOM/MACHINERY SPACE OR CONTROL SPACE |
| LIGHTING AND RECEPTACLE(S). |
| A SEPARATE BRANCH CIRCUIT SHALL SUPPLY |
| THE HOISTWAY PIT LIGHTING AND |
| RECEPTACLE(S). |
| |
| 9)NOTE: NOTE #9 NO, PLEASE SEE RECETPS |
| WERE ADDED HOWEVER, ID SCALE IS CLOSE AS |
| INDICATED, SOME RECEPTS APPEAR TO BE |
| WITHIN THE RESTRICATED 10' AREA. |
| PLEASE SEE 620.22A3 |
| PLEASE ALSO SEE NEW NOTE FOR LIGHTING |
| AROUND POOLS. |
| |
| 10)NOTE: NOTE #10 OK, REFERENCES |
| CHANGED. |
| |
| 11)NOTE: NOTE #11 OK, HOWEVER PLEASE SEE |
| NEW NOTES FOR BATH/TUB/JACUZZI FIX. |
| |
| 12)NOTE: NOTE #12 NO, PLEASE SEE UNITS |
| ARE STILL SHOWN WITHOUT ACCESS TO |
| GARAGE. |
| AS PER CONVERSATION WITH MR. RAPL BAEZA, |
| NO ACCESS WAS GOING TO BE INSTALLED FROM |
| GARAGE IN DESIGN. |
| PLEASE SEE BLDG REVIEW COMMENTS BY MR. |
| ROBERT BROWN, ACCESSIBILTY FROM GARAGE |
| MAY BE REQUIRED. |
| IF SO, PLEASE SEE 210.70 AND LS101 5-8. |
| |
| 13)NOTE: NOTE #13 NO, PLEASE SEE GRADE |
| LEVEL ACCESS REQUIRES MEANS OF EGRESS |
| LIGHTING/CONTROL. PLEASE ALSO SEE |
| EXCEPTIONS. |
| |
| 14)NOTE: NOTE #14, OK, HOWEVER PLEASE |
| SEE NOTE #7. |
| |
| 15)NOTE: NOTE #15 OK FOR SD'S HOWEVER |
| PLEASE SEE NEW COMMENTS FOR CIRCUITING |
| AND ARC FAULT PROTECTION. |
| |
| 16)NOTE: NOTE #16 OK. |
| |
| 17)NOTE: NOTE #17 NO, PLEASE SEE 210.52D |
| FOR GFI REQUIRED WITHIN 3' OF SINK/LAV |
| EDGE. |
| PLEASE SEE PLANS AHVE SOME REDLINED AT |
| LOCATION(S) MISSING. |
| |
| 18)NOTE: NOTE #18 NO, PLEASE SEE |
| ELECTRICLA PANELS NOT PERMITTED ON |
| CLOSETS. PLEASE SEE 110.26,408.7,240.24 |
| ETC. |
| PLEASE SEE 240.24OVER CURRENT |
| PROTECTION IS NOT TO BE LOCATED IN THE |
| VICINITY OF EASILY IGNITIBLE MATERIAL. , |
| SUCH AS IN CLOTHES CLOSETS. |
| PLEASE ALSO SEE NEW NOTES BAOUT CATV AND |
| TELEPHONE CABINETS. |
| |
| 19)NOTE: NOTE #19 NO, PLEASE SEE SOME |
| UNITS STILL SHOW A COUPLE OF ELECTRICAL |
| PANELS IN "LT GRAY". THIS APPEARS TO BE |
| MISPRINTS . PLEASE SEE UNIT HD FOR ONE. |
| |
| 20)NOTE: NOTE #20 OK, HOWEVER PLEASE SEE |
| NOTE #28 FOR 110.26 |
| |
| 21)NOTE: NOTE #21 OK. |
| |
| 22)NOTE: NOTE #22 NO, PLEASE SEE MANY |
| UNITS HAVE BEEN REDLINED FOR AREAS IN |
| QUESTION. PLEASE SEE 210.52C1-5 FOR |
| REQUIRED LOCATIONS OF GFI RECEPTS ALONG |
| KITCHEN COUNTERSPACES, INCLUDING |
| PENINSULARS AND " SEPARATE SPACES". |
| 210.52C2,4 |
| |
| 23)NOTE: NOTE #23 NO, CPULD NOT LOCATE |
| NOTE REQUESTED FOR SD PLACEMENT ON |
| PLANS. |
| PLEASE CLARIFY WHERE THIS IS. |
| PLEASE SEE NFPA-72 8-1.4.2 FOR THESE |
| LOCATIONS. |
| |
| 24)NOTE: NOTE #24 NO, PLEASE SEE GFI |
| RECEPTS WERE ADDED TOLOWER TERRACE |
| LEVELS BUT NONE TO UPPER TERRACES. |
| PLEASE SEE UPPER TERRACE ON ELECTRICAL |
| PLANS APPEAR TO BE SHOWN MUCH LARGER |
| THAN TERRACES SHOWN ON ARCH SHEETS. |
| THIS IS ONLY A NOTE AND LIGHTING OR GFI |
| RECEPTS ARE NOT REQUIRED ON THE SMALLER |
| OR LARGE TERRACES, HOWEVER OF THEY ARE |
| GOING TO BE INSTALLED, PLEASE SHOW ON |
| PLANS AT THIS TIME OR PLANS WILL BE |
| REQUIRED TO BE REVISED AT A LATER DATE. |
| |
| 25)NOTE: NOTE #25 YES/NO , GFI BRKR |
| NOTED AT PANEL SCHEDULES,HOWEVER A |
| POWER/RECEPT COULD NOT BE LOCATED ON |
| PLANS AT THESE UNITS. |
| PLEASE SHOW. |
| |
| 26)NOTE: NOTE #26NO. PLEASE SEE NO |
| INFORMATION EXCEPT THAT FIRE PUMP IS |
| GOING TO BE 250 HP. PLEASE SEE KEYNOTES |
| K-23 DOES NOT PROVIDE ENOUGH |
| INFORMATION. |
| PLEASE ALSO SEE NEW NOTES PERTAINING TO |
| FIRE PUMP/CONTROLLER ETC. |
| PLEASE SEE PREVIOUS REQUEST WAS TO HAVE |
| ALL MANUFACTURE SPEC SHEETS SUBMITTED |
| FOR FIRE PUMP, FIRE PUMP CONTROLLER, ETC |
| NONE COULD BE LOCATED IN SPECS, |
| SUBMITTALS??? |
| SEE NEW NOTES: |
| |
| 27)NOTE: NOTE #27 NO, PLEASE SEE ABOVE |
| NOTE. PLEASE SE NO SPECS FOR GENERATOR, |
| SUB BASE FUEL TANK ATS WERE SUBMITTED. |
| 215.5 |
| PLEASE SEE NEW NOTES FOLLOWING. |
| |
| 28)NOTE: NOTE #28 NO, PLEASE SEE NOTE |
| WAS ADDED TO ONE SHEET ONLY. PLEASE SEE |
| SPECIFICS NOTES FOR 110.26 WILL BE |
| REQUIRED ON ALL SHEETS SHOWING |
| ELECTRICAL ROOMS AND ELECTRICAL CLOSETS. |
| |
| PLEASE SEE THIS NOTE SHOULD REFLECT "ALL |
| ELECTRICAL ROOMSAND ELECTRICAL CLOSETS |
| SHALL MEETS ALL THE REQUIREMENTS OF |
| 110.26 AND ALL OTHER REQUIREMENT OF |
| 2002 NEC" PLEASE SEE WE ARE HAVING MANY |
| ISSUES WHERE WIDTHS ARE BEING MET, |
| HOWEVER HEIGHT REQUIREMENTS ARE NOT. |
| SEE NEW NOTES ALSO. |
| |
| 29)NOTE: NOTE #29 OK. |
| |
| 30)NOTE: NOTE #30 NO, PLEASE SEE MORE |
| THAN ONE "K" NOTE LOCATED ON KEYNOTES DO |
| NOT CORRELATE OR SHOWN "BLANK" OR NOTED |
| AS NOT BEING USED, HOWEVER PLANS DO NOT |
| MATCH THESE. |
| PLEASE SEE K26,K35, ETC. |
| PLEASE SEE NEW NOTES FOR F AND K NOTES |
| WHICH DO NOT CORRELATE WITH PLANS. |
| PLEASE SEE NEW NOTES: |
| |
| 31)NOTE: NO, PLEASE SEE RESPONSE LTR |
| MENTIONS "WILL COMPLY" HOWEVER PLEASE |
| SEE NEW NOTES PERTAINING TO NOTES ON |
| PLANS AND SPECS. |
| |
| 32)NOTE: NOTE #32 OK, NOTE ADDED , GEN |
| WILL NOT BE SEPARATELY DEREVED. THIS |
| WILL BE VERIFIED ONCE MANUFACTURE SPECS |
| ARE SUBMITTED. |
| SEE NEW NOTES ALSO; |
| |
| 33)NOTE: NOTE #33 OK, HOWEVER PLEASE SEE |
| NEW NOTES PERTAINING TO FEEDER SIZES. |
| |
| 34)NOTE: NOTE #34 NO, PLEASE SEE RISER |
| DIAGRAM STILLDOES NOT INCLUDE A |
| REDUCED "KEYED NOTES" OR RECDUCED |
| "FEEDER SCHEDULE FOR REFERENCE WITHOUT |
| HAVING TO TURN BACK AND FORTH FROM RISER |
| DIAGRAM PAGE TO E-6.13. |
| 215.5. |
| PLEASE SEE NEW NOTES FOR250.30 |
| PLEASE SEE RISER INDICATES 3000A |
| BUS-STAB INTO FPL VAULT FEEDING 4000A |
| MAINS?? PLEASE CORRELATE. |
| PLEASE SEE RISER SHOWS 3000A MAIN |
| FEEDING 4000A BUS-DUCT THEN CHANGES BACK |
| TO 3000A BUS DUCT?? |
| |
| 35)NOTE: NOTE #35 OK, HOWEVER SEE NEW |
| NOTES FOR CORRELATIONOF METER CENTERS |
| AND LOAD CALCULATIONS/ EQUIPMENT. |
| |
| 36)NOTE: NOTE # 36 OK, OVEN ADDED, |
| RANGES CHANGED. |
| |
| 37)NOTE: NOTE #37 PLEASE SEE "FEEDER |
| HOME RUN SCHEDULE" WAS ADDED TO MOST |
| SHEETS CONTAINING PANEL SCHEDULE, BUT |
| SEE PLANS FOR MISSING DETAIL. PLEASE |
| ALSO SEE NEW NOTES PERTAINING TO PANELS |
| SIZES. |
| |
| 38)NOTE: NOTE #38 NO, PLEASE SEE |
| PANELS STILL SHOWN AS 200A WITH 225A OCP |
| FEEDING PANEL(S). PLEASE SEE THE 250A |
| OCP WAS REMOVED. |
| |
| 39)NOTE: NOTE #39 NO, PLEASE SEE WATER |
| HEATERS SHOWN WITH 2P50A OCP FOR 4500VA |
| UNITS ON #10 AWG. |
| PLEASE ALSO SEE 6KW WITH 30A OCP. |
| PLEASE SEE MIN OCP IS 125% AND MAX OCP |
| IS 150%. |
| PLEASE SEE 422.13,422.11,240.4, 310.16 |
| ETC. |
| |
| *************************************** |
| NEW NOTES FOR REVIEW. |
| |
| 40)NOTE: PLEASE SEE MIN REQUIREMENTS FOR |
| ELECTRICAL LIGHT FIXTURES FORM SWIMMING |
| POOL. IF SCALE IS USED AS INDICATED ON |
| PLANS, SOME FIXTURES SHOWN AS CLOSE AS |
| 3' FROM WATER'S EDGE. |
| PLEASE SEE 680.22 AND PREVIOUS NOTES FOR |
| RECEPT PLACEMENT. |
| |
| 41)NOTE: PLEASE CLARIFY MANY |
| ELECTRICAL/GENERATOR RMS CONTAIN EM LT |
| FIXTURES ON EM CIRCUIT BUT YET THESE ARE |
| ALSO BATTERY BACK UP? PLEASE SEE THEN |
| ARE MANY ELECTRICAL RMS WHICH DO NOT |
| CONTAIN BATTERY BACK UP? |
| THIS IS ONLY A NOTE. |
| |
| 42)NOTE: PLEASE SEE MANY UNITS, 5,6,8 |
| ETC FOR REQUIRED RECEPTS PER 210.52. |
| PLEASE SEE 2' OF WALL SPACES INT |
| KITCHENS, BEDROOMS(EVEN IF BEHIND |
| DOORS). |
| PLEASE SEE MANY REDLINED AT LOCATIONS ON |
| PLANS. |
| |
| 43)NOTE: PLEASE SEE MOST DRYER LOCATIONS |
| INDICATE A MANUAL SWITCH FOR DRYER |
| "BOOST FAN" YET MANY DO NOT CONTAIN THIS |
| SAME SW? |
| HOWEVER, PLEASE SEE NOTES LOCATED ON |
| EACH SHEET WHICH MENTIONS THAT THESE |
| WILL BE AUTOMATICALLY INTERCONNECTED? |
| PLEASE SEE MECHANICAL NOTES FOR THIS |
| SAME ITEM. IT APPEARS INTERCONNECTING |
| ANY DEVICES IN THESE FANS/ DRYERS MAY |
| VOIDED WARRANTIES AND/OR VOIDED LISTINGS |
| FROM MANUFACTURE. |
| |
| 44)NOTE: PLEASE SEE AS MENTIONED ON |
| ORIGINAL NOTES, ARC FAULT PROTECTION |
| REQUIRED PER 2002 NEC 210.12, HOWEVER |
| THERE ARE NUMEROUS AREAS IN MOST UNITS |
| IN WHICH CIRCUITING FOR LIGHTING ETC |
| DOES NOT HAVE THE "* " ON THE CIRCUIT |
| #'S ON PANEL SCHEDULE FOR THE |
| PROTECTION. |
| PLEASE SEE ALL "OUTLETS" INCLUDING SD'S, |
| LTS, FANS AND RECEPTS REQUIRED THIS. |
| PLEASE SEE MANY OF THESE CIRCUIT #'S |
| HAVE BEEN REDLINED ON PLANS, BUT NOT |
| ALL. |
| |
| 45)NOTE: PLEASE SEE SOME UNITS ARE |
| SHOWING FIXTURES IN SOME UTILITY/CLOTHES |
| CLOSETS WHICH DO NOT APPEAR TO MEET |
| 410.8 FOR MIN CLEARENCE. PLEASE VERIFY. |
| |
| 46)NOTE:PLEASE VERIFY FIXTURE |
| CLEARENCE OVER TUBS/HYDRO ETC. AN |
| ELEVATION IS NOT SHOWN FOR MIN CLEARENCE |
| AND WE HAVE ENCOUNTERED MANY WHICH FALL |
| BELOW MIN CLEARENCE EVEN FOR A RECESSED |
| LT WITH AN ENCLOSED COVER. |
| THIS IS ONLY A NOTE: |
| |
| 47)NOTE: SEE PREVIOUS/UPPER NOTES, UNIT |
| # H-7 FOR MISSING GFI W/IN 3' OF SINK. |
| 210.52 |
| |
| 48)NOTE: PLEASE SEE UNIT A-1 WHICH |
| INDICATES A THIRD SMALL APPL CIRCUIT , |
| HOWEVER THIS COULD NOT BE LOCATED ON |
| PLANS? |
| |
| 49)NOTE: PLEASE SEE UNIT V-1 THIS |
| APPEARS TO HAVE "ALL" DEVICES SHIFTED |
| AND REVIEW FOR PLACEMENT FOR THESE |
| DEVICES CAN NOT BE DONE AT THIS TIME. |
| |
| 49)NOTE: PLEASE SEE MANY CLOTHES CLOSETS |
| CONTAINING COMBUSTIBLES ARE SHOWN WITH |
| CATV AND TELEPHONE CABINETS. PLEASE SEE |
| IF THESE UNITS WILL REQUIRE ANY "LV |
| PLUG-IN" TYOE TRANSFORMERS THEN THESE |
| RECEPTS WHICH ARE NOT SHOWN AT THIS TIME |
| WOULD ONLY BE ALLOWED DIRECTLY OVER |
| DOORS. |
| PLEASE SEE PLANS DO NOT INDICATE ANY LV |
| ALARM PANELS AT THIS TIME AND SAME WOULD |
| BE REQUIED IF LOCATED IN A CLOTHES |
| CLOSET. THIS IS ONLY A NOTE: |
| |
| 50)NOTE: PLEASE SEE 2002 210.8B3 FOR |
| KITCHENS IN OTHER THAN DWELLING UNITS. |
| THIS WOULD BE FOR "HOUSE KITCHEN". |
| |
| 51)NOTE: PLEASE SEE SOME UNITS WHICH DO |
| NOT SHOW DEVICES, MENTIONS TO SEE OTHER |
| SIMILAR UNITS, HOWEVER PLEASE SSE SOME |
| ARE MSSING OR DO NOT CORRELATE. |
| PLEASE SEE "B" UNIT, 3.23, "D-1"AND |
| "D" UNIT ON 3.25. |
| |
| 52)NOTE: PLEASE SEE FIRE COMMAND ROOM |
| LAYOUT DO NOT NOT CORRLETATE FOR LAYOUT |
| AND EQUIPMENT IN ROOMS AS NOTED. |
| 8.05,4.01 |
| |
| 53)NOTE: PLEASE SEE RISER AND PLANS DO |
| NOT INDICATE ANY INFORMATION FOR |
| DISC/BRKRS/OCP LOCATED ON GENERATOR FOR |
| FEED/FEEDS TO GUTTER AND ON TO |
| DISCONNECTS LOCATE DIN GEN RM. |
| 215.5 COMPLIANCE CAN NOT BE VERIFIED AT |
| THIS TIME. |
| |
| 54)NOTE: PLEASE SEE GROUND FUALT |
| PROTECTION FOR SHN CAN NOT BE VERIFIED. |
| CAN NOT LOCATE ON PLANS, RISER OR PANEL |
| DETAIL/SCHEDULE. |
| PLEASE SEE 240, GROUND-FAULT PROTECTION |
| OF EQUIPMENT SHALL BE PROVIDED IN |
| ACCORDANCE WITH THE PROVISIONS OF 230.95 |
| FOR SOLIDLY GROUNDED WYE ELECTRICAL |
| SYSTEMS OF MORE THAN 150 VOLTS TO GROUND |
| BUT NOT EXCEEDING 600 VOLTS |
| PHASE-TO-PHASE FOR EACH INDIVIDUAL |
| DEVICE USED AS A BUILDING OR STRUCTURE |
| MAIN DISCONNECTING MEANS RATED 1000 |
| AMPERES OR MORE. |
| |
| 55)NOTE: PLEASE SEE K-27 MENTIONS TO SEE |
| TRANSFORMER GROUNDING DETAIL, HOWEVER |
| THIS COULD NOT BE LCOATED ON PLANS.? |
| PLEASE SHOW EITHER A TYPICAL DETAIL OR |
| SHOW EACH. 250.30,215.5 |
| |
| 56)NOTE:PLEASE SEE KEYNOTE K-31, |
| MENTIONS PER NAMEPLATE, HOWEVER |
| DISCONNETC SIZES ETC, ARE REQUIRED AT |
| THIS TIME A S MIN. 215.5 |
| PLEASE ALSO SEE K-NOTE FOR ELEVATOR |
| CONTROLLER. |
| |
| 57)NOTE: PLEASE SEE GUTTER SHOWN AT |
| GENERATOR ROOM REFERENCES TO MEET 366. |
| PLEASE SEE FBC 104.2.1, CODES FOR |
| SPECIFIC DESIGNS ARE NOT TO BE REFERNECD |
| IN WHOLE OR IN-PART. PLEASE SHOWN MIN |
| GUTTER SIZE. |
| PLEASE ALSO SEE NO CONDUCTORS SIZES ARE |
| SHOWN, NO CONDUIT SIZES AND NO OCP |
| (PREVIOUS NOTE) ARE SHOWN TO VERIFY |
| COMPLIANCE. 310.16,215.5 240.4 ETC. |
| |
| 58)NOTE: PLEASE SEE K-24, K25, NO SIZE |
| FOR CONDUIT, FEEDER ETC FROM FIRE PUMP |
| CONTROLLER TO FIRE PUMP. PLEASE SEE |
| PLANS INDUCATE A "MAGNETIC TYPE" BRKR, |
| HOWEVER NO SIZE IS GIVEN? |
| 215.5,310.16 ETC. |
| PLEASE SEE PREVIOUS NOTES. |
| |
| 59)NOTE: PLEASE SEE "SPEC BOOK", 16465 |
| 2.2C WHICH MENTIONS ALUM BUS-DUCT. |
| PLEASE SEE PREVIOUS NOTES IN REFERENCE |
| TO EQUIPMENT GROUNDING METHOD OF |
| BUS-DUCT. DOES THIS BUS-DUCT CONTAIN A |
| SEPARATE ALUM BUS FOR GROUNDING? OR IS |
| THE EQUIPMENT GROUNDING THAT IS GOING TO |
| BE USED "PART" OF THE BUS-DUCT. |
| PLEASE ALSO PLACE NOTE ON PLANS FOR |
| REQUIRED CURBS FOR FLOOR PENATRATIONS. |
| PER 368.6BFLOOR PENETRATIONS SHALL |
| COMPLY WITH (1) AND (2): |
| BUSWAYS SHALL BE PERMITTED TO BE |
| EXTENDED VERTICALLY THROUGH DRY FLOORS |
| IF TOTALLY ENCLOSED (UNVENTILATED) WHERE |
| PASSING THROUGH AND FOR A MINIMUM |
| DISTANCE OF 1.8 M (6 FT) ABOVE THE FLOOR |
| TO PROVIDE ADEQUATE PROTECTION FROM |
| PHYSICAL DAMAGE. |
| IN OTHER THAN INDUSTRIAL ESTABLISHMENTS, |
| WHERE A VERTICAL RISER PENETRATES TWO OR |
| MORE DRY FLOORS, A MINIMUM 100 MM (4 |
| IN.) HIGH CURB SHALL BE INSTALLED AROUND |
| ALL FLOOR OPENINGS FOR RISER BUSWAYS TO |
| PREVENT LIQUIDS FROM ENTERING THE |
| OPENING. THE CURB SHALL BE INSTALLED |
| WITHIN 300 MM (12 IN.) OF THE FLOOR |
| OPENING. ELECTRICAL EQUIPMENT SHALL BE |
| LOCATED SO THAT IT WILL NOT BE DAMAGED |
| BY LIQUIDS THAT ARE RETAINED BY THE |
| CURB. |
| |
| 60)NOTE: PLEASE SEE "SPEC BOOK" 16120 |
| 2.3A5, PLEASE SEE COLOR CODING FOR |
| 277/480V SHALL BE BROWN, PURPLE, YELLOW. |
| 215.8 LOCAL AMENDMENTS. |
| |
| 61)NOTE: THIS IS ONLY A NOTE: PLEASE SEE |
| LOAD ON HGMN SHOWN AT 197A'S WITH 200A |
| BRKR FEEDING THIS. |
| |
| 62)NOTE: PLEASE SEE PLANS INDICATE "SHN" |
| FEEDING"H5MN" WITH 125A BRKR, YET H5MN |
| IS ONLY 100A'S.? |
| PLEASE ALSO SEE RISER , APPEARS TO SHOW |
| THIS AS "H5MH"? |
| |
| 63)NOTE: PLEASE SEE DPHRN 150A BRKR TO |
| 100A FEEDERS (F-19). |
| |
| 64)NOTE: PLEASE CORRELATE LOADS SHOWN ON |
| "HRHN" AND TWO OTHER LOADS SHOWN ON |
| "LRHN" |
| 215.5 |
| |
| 65)NOTE: PLEASE CORRELATE F-7, F-9 TO |
| DPHE ON PANEL AND RISER. |
| PLEASE SEE NO FEEDER SHOWN K? FOR HGMN |
| ON RISER. |
| |
| 66)NOTE: PLEASE CORRELATE "P-4" METER |
| CENTER LOAD ANALYSIS AND NOT SHOWN ON |
| ANY "SWITCH BOARD"? |
| PLEASE ALSO SEE 2-W NEEDS TO CORRELATE |
| WITH "SMCW". PLEASE ALSO SEE "MW" NOT |
| SHOWN?? |
| 215.5 |
| |
| 67)NOTE: PLEASE SEE "FUEL NOTE" MENTIONS |
| 277 GALS OF FUEL PER HR??? RUNNING A MIN |
| OF 2.? HRS. |
| PLEASE CLARIFY THIS NOTE: PLEASE SEE |
| SIZING, CONSUMPTION OF GEN ETC CAN NOT |
| BE VERIFIED. PLEASE SEE PREVIOUS NOTES |
| PERTAINNG TO INFORMATION REQUIRED FOR |
| GENERATOR ETC. |
| |
| 68)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| AIC RATINGS SHOULD BE NOTED ON ALL |
| EQUIPMENT. |
| |
| 69)NOTE: PLEASE SEE ALL INFORMATION FOR |
| AS SHOWN ON PLANS FOR LIGHTNING |
| PROTECTION SYSTEMCAN BE INCLUDED UNDER |
| BASE BLDG'S ELECTRICAL PERMIT. HOWEVER |
| ANY CHANGES IN SYSTEM WOULD NEED |
| REVISION. THIS SYSTEM WILL BE THE |
| RESPONSIBILITY OF THE ELECTRICAL |
| CONTRACTOR. IF THIS WORK IS "SUBBED' |
| OUT, A SEPARATE PERMIT MUST BE PULLED BY |
| LIGHTNING PROTECTION CONTRACTOR. SINCE |
| THESE PLANS CONTAIN INFORMATION FOR |
| SYSTEM, SUB CONTRACTOR MAY REFERENCE |
| THESE PLANS AND A MIN $50 PERMIT FEE |
| WILL BE DUE. |
| |
| 70)NOTE: PLEASE ALSO SEEIF ALL |
| INFORMATION FOR FIRE PUMP, FIRE PUMP |
| CONTROLLER,GENERATOR, ATS, ETC IS NOT |
| SUBMITTED FOR REVIEW WITH BASE BLDG |
| PLANS, ALL OF THESE ITEMS WILL BE |
| REQUIRED TO BE UNDER SEPARATE PERMIT |
| ALONG WITH ALL FEES BASED ON VALUE OF |
| ALL OF THOSE ITEMS. |
| PLEASE SEE FIRE REVIEW COMMENTS. |
| |
| 71)NOTE: PLEASE SEE MANY OF THE ABOVE |
| ITEMS ARE REDLINED ON PLANS FOR AREAS OF |
| NOTES. NOT "ALL" ITEMS ARE REDLINED. |
| |
| 72)NOTE: PLEASE REMOVE ALL OLD/VOIDED |
| SHEETS FROM SETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. |
| PLEASE SEE "ONE" SET OF ALL OLD/VOIDED |
| REMOVED SHEETS SHOULD BE SUBMITTED FOR |
| REFERENCE ONLY. |
| |
| 73)NOTE: PLEASE KNOW, AS NOTED IN SOME |
| NOTES, DUE TO SOME INFORMATION MISSING |
| ON PLANS AND WITH PLANS, A COMPLETE |
| REVIEW FOR CODE COMPLIANCE CAN NOT BE |
| DONE AT THIS TIME. |
| PLEASE BE SURE TO INCLUDE ALL |
| INFORMATION AS REQUESTED/NEEDED. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |