Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop P
Sequence Number 17
Notes
Date Text
2006-08-23 00:00:001. SUBMITTAL #15047.01 PIPE
 IDENTIFICATION AND VALVE TAGS (OK)
 2. SUBMITTAL #15181.01 CRETE SLEEVES
 (OK)
 3. SUBMITTAL #15400.04 WASHING MACHINE
 BOX (OK)
 4. SUBMITTAL #15410.04 DUTCH BOY SOLDER
 MSDS SHEETS (OK)
 5. SUBMITTAL #15410.05 SOLDER PASTE FLUX
 (DENIED)
 A) THE SUBMITTAL FOR OATLY PASTE FLUX
 #5 DOES NOT SHOW COMPLIANCE FBC-2004,
 PLUMBING, SECTION 605.14.3 AND 605.15.4
 FLUX CONFORMING TO ASTM B 813 SHALL BE
 APPLIED, PLEASE SUBMIT MANUFACTURER
 SHEET FOR SAID SUBMITTAL CONFORMING TO
 ASTM B 813 OR PLEASE SUBMIT ANOTHER.
 6. SUBMITTAL #15430.07 HOSE BIBBS (OK)
 7. SUBMITTAL #15430.08 TRAP PRIMERS AND
 WATER ARRESTERS (OK)
 "EXCEPTION"
 A)SEMI CAST TRAP PRIMER TLPC (DENIED)
 MORE INFORMATION REQUIRED, PLEASE SUBMIT
 MANUFACTURER SHEETS WITH SAID SUBMITTAL
 CONFORMING TO FBC-2004 PLUMBING, CHAPTER
 10.
 8. SUBMITTAL #15455.02 DRAINAGE PIPE AND
 FITTINGS (OK)
 9. SUBMITTAL #15455.03 VENT THROUGH ROOF
 FLASHINGS (OK)
 10. SUBMITTAL #15484.01 OATLY CHEMICALS
 MSDS SHEETS (OK)
 11. SUBMITTAL #15484.03 HERCULES PIPE
 DOPE (OK)
 12. SUBMITTAL #15499.01 PLUMBING PIPE
 INSULATION (OK)
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721