2006-11-12 13:34:47SUBMITTAL FOR GAMMA U.S.A. DOOR/WINDOW DESIGN AND
 PRODUCT APPROVAL PACKAGE.
  
 GAMMA U.S.A. PLAN SHEET 1.04 STATES THAT NO PRESSURES
 COULD BE FOUND, IN THE WIND LOAD STUDY REPORT, FOR THE
 "SOUTH COURTYARD ELEVATION", AND LOADS OF +90/-90 PSF
 WERE USED.FIGURE 7 AND FIGURE 12 OF THE RWDI REPORT
 DO SHOW THE LOADS FOR SOUTH COURTYARD ELEVATION,
 HOWEVER THEY ARE LESS THAN +90/-90 PSF, SO RE-DESIGN IS
 NOT NECESSARY.
  