2006-11-14 19:35:09 | SUBMITTAL # 15815.4 REC'D 9/28/06 | | SUPPLY AND EXHAUST FANS | | | | ERRORS ON SUBMITTAL DATA AS FOLLOWS: | | | | 1. GEF-3 MODEL # ON SUBMITTAL DIFFERS FROM MODEL # ON | | PLAN. | | 2. GSF-P1 THRU P9 MAXIMUM SOUND LEVEL ON SUBMITTAL | | EXCEEDS MAXIMUM SOUND LEVEL ON PLAN. | | 3. SUBMITTALS ARE MISSING PAGES FOR SPF-5 AND SPF-6 4. | | EF-A AND EF-B SUBMITTAL DATA DOES NOT MATCH PLAN IN ANY | | CATEGORY. | | 5. EF-R4 MAXIMUM SOUND LEVEL ON SUBMITTAL EXCEEDS | | MAXIMUM SOUND LEVEL ON PLAN. | | 6. EF-P1-3,EF-P3-1,EF-5-1,EF-5-2 MODEL #S ON SUBMITTALS | | DO NOT MATCH PLAN. | | | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|