2006-09-07 00:00:00PROVISO:
  
 1.PLEASE REVISE CALCULATIONS FOR THE
 GARAGE VENTILATION.SHOW COMPLIANCE
 WITH 2001 FBC 411.4.2 & 2001 FMC 501.4.
  
 2.PLEASE INDICATE IF THE CO SENSORS
 WILL BE TIED TO THE EMERGENCY POWER.
  
 3.PLAN SHEET M2.04 - PLEASE VERIFY THE
 LENGTH OF THE DRYER EXHAUST, DUE TO THE
 RE-ROUTING OF THE DUCT.THIS COMMENT IS
 IN RESPONSE TO NARRATIVE NOTE #15.
  
 4.PLEASE NOTE, AIR HANDLER CLOSETS
 SERVE AS A PLENUM AND SHALL COMPLY WITH
 2001 FMC 602.2.1, MATERIALS EXPOSED
 WITHIN THE PLENUM SHALL BE
 NON-COMBUSTIBLE.THIS INCLUDES THE DOOR
 AND FRAME.
  
 5.DRYER EXHAUST SHALL NOT EXCEED THE
 MANUFACTURER'S SPECIFIED LENGTH OR
 COMPLY WITH 2001 FMC 504.6.
  