Date |
Text |
2005-01-15 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 BUILDING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1) PLANS SHALL BE SIGNED/SEALED/DATED |
| BY |
| THE ARCHITECT/ENGINEER OF RECORD, AND |
| ALL TITLE BLOCK INFORMATION REQUIRED ON |
| ALL SHEETS. FAC 61G1-16.002-.003-.004 & |
| 61G15-23.002 & FS 481.219-.219 & |
| 471.025 |
| 2) SHT A2.01 PRIMARY ENTRY LEVEL SHALL |
| COMPLY WITH FHA-98 DESIGN MANUAL |
| REQUIREMENTS 1 THRU 7. |
| 3) SHT A2.10 SUBMIT CALCULATIONS FOR |
| MINIMUM FACILITIES PER TABLES 1003.2 |
| AND |
| 403.1. SHOW SQUARE FEET FOR EACH COMMON |
| USE ROOM. |
| 4) SHT A2.10 SUBMIT CALCULATIONS FOR |
| PRIMARY AND SECONDARY STORM DRAINS FOR |
| THE 5TH FLOOR OPEN AREAS PER SECTIONS |
| 1106 & 1107. SHOW THE LOCATION FOR ALL |
| PRIMARY AND SECONDARY DRAINS. |
| 5) SHTS A2.14, A2.15, A2.16, & A2.17. |
| APPLICATION STATES 20 STORY BLDG., BUT |
| PLANS INDICATE 21ST STORY AND HAS A |
| ROOF |
| LEVEL, POOL DECK LEVEL, ELEVATOR |
| MACHINE |
| ROOM LEVEL ECT. PLEASE CLARIFY. |
| 6) SHT A4.11 UNIT 1 DOOR SWING INTO THE |
| CLEAR FLOOR SPACE OF THE LAV. SECTION |
| 11-4.22.2. |
| 7) SHT A4.12 UNITS 5 & 6 DOOR SWING |
| INTO |
| THE CLEAR FLOOR SPACE OF THE LAV AND |
| W/C |
| SECTION 11-4.22.2. |
| 8) SHT A4.13 UNIT 12 DOOR SWING INTO |
| THE |
| CLEAR FLOOR SPACE OF THE W/C. |
| 11-4.22.2. |
| 9) SHT A4.15 UNIT 17 DOOR SWING INTO |
| THE |
| CLEAR FLOOR SPACE OF THE LAV. |
| 11-4.22.2. |
| 10) ALL SHEETS FOR UNITS. SHOW THE |
| OPENING SIZE FOR ALL W/C'S AND SHOW THE |
| W/C TO BE 18" FROM THE CENTER LINE OF |
| THE FIXTURE TO THE WALL WHERE |
| APPLICABLE |
| 11) ALL SHEETS FOR UNITS. INDICATE |
| SPECIFICATION "A" OR "B" AS REQUIRED BY |
| THE FHA-98 DESIGN MANUAL FOR EACH UNIT. |
| 12) SHT A4.41 KITCHEN SINK & JUICE BAR |
| SINK IN COMMON AREAS SHALL COMPLY WITH |
| SECTION 11-4.24 AND ALL SUBSECTIONS. |
| SUBMIT A DETAIL. |
| 13) SHT A4.41 SUBMIT A DETAIL FOR THE |
| TOILET ROOM IN THE COMMON AREA. SHOW |
| COMPLIANCE WITH SECTIONS 11-4.16, |
| 11-4.18, 11-4.19, 11-4.21 & 11-4.22 AND |
| ALL SUBSECTIONS. ALSO SEE SECTION 2 OF |
| THE FHA-98 DESIGN MANUAL. |
| 14) SHT A4.41 A DRINKING FOUNTAIN IS |
| REQUIRED PER TABLE 403.1 FOR THE COMMON |
| AREA. SUBMIT A DETAIL SHOWING |
| COMPLIANCE |
| WITH SECTION 11-4.15 AND ALL |
| SUBSECTIONS. - ALSO SEE SECTION 410.1. |
| 15) SHT SUBMIT CALCULATIONS FOR PRIMARY |
| AND SECONDARY ROOF DRAINS PER SECTIONS |
| 1106 & 1107 AND ALL SUBSECTIONS. SHOW |
| THE SQUARE FOOTAGE OF EACH AREA DRAINED |
| WITH 1/2 AREA OF ALL VERTICAL WALLS |
| INCLUDING PARAPETS SHOWN ADDED TO THE |
| ROOF AREA. ALSO SHOW THE AREA OF UPPER |
| ROOFS DRAINING ONTO EACH AREA ADDED TO |
| THE SF IN CALCULATIONS. SHOW THE |
| LOCATION OF EACH PRIMARY ROOF DRAIN AND |
| EACH SECONDARY ROOF DRAIN OR SCUPPER |
| FOR |
| EACH AREA BEING DRAINED FOR EACH ROOF. |
| 16) SHT A4.51 A 60" DIA. TURNING AREA |
| IS |
| REQUIRED IN A "U" SHAPED KITCHEN THAT |
| HAS A SINK, RANGE, OR COOKTOP AT IT'S |
| BASE. PAGE 7.9 FHA DESIGN MANUAL. |
| 17) SHTS A4.60 THRU A4.66 MORE |
| INFORMATION IS REQUIRED FOR THE |
| EXTENDED |
| TERRACES. WILL |
| A SCUPPER BE REQUIRED OR CAN THE WATER |
| DRAIN FROM THE TERRACES IN CASE OF |
| BLOCKAGE OF THE TERRACE DRAIN. SECTION |
| 104.2.1. |
| 18) SHT A4.71A INDICATE LOCATION OF |
| SECONDARY ROOF DRAINS IN AREAS OF ROOF |
| WHERE SCUPPERS ARE NOT AVAILABLE. |
| SECTION 1107. |
| 19) SHT A4.72A INDICATE LOCATION OF |
| SECONDARY ROOF DRAINS FOR DECK DRAIN |
| AREAS. SECTION 1107. |
| 20) SHT A4.73A INDICATE LOCATION OF |
| SECONDARY ROOF DRAINS FOR ALL AREAS. |
| SECTION 1107. |
| 21) SEPARATE PERMITS REQUIRED FOR POOL |
| AND SPA. SECTION 104.1.1. |
| 22) SHT A8.21 DETAIL B/A8.21 INDICATE |
| OPENING SIZE REQUIRED PER SECTION |
| 1107.3 |
| 23) IRRIGATION PLANS & PERMIT REQUIRED. |
| SECTION 104.2.1. |
| 23) SHT L-2 MORE INFORMATION IS |
| REQUIRED |
| FOR THE WATER FEATURES. INDICATE HOW |
| THE |
| FEATURES ARE DRAINED AND IF THERE IS A |
| WATER SERVICE FOR THESE FEATURES. |
| SECTION 104.2.1. |
| 24) THE FOLLOWING SHEETS SUBMITTED ARE |
| NOT SHOWN ON THE DRAWING INDEX. A4.71A, |
| A4.74A, A8.41B & A10.03. PLEASE |
| CORRELATE THE DRAWING INDEX WITH |
| SUBMITTED PLANS. |
| 25) THE FOLLOWING SHEETS ON THE DRAWING |
| INDEX WERE NOT SUBMITTED. A1.02, A3.11, |
| A3.12, A3.14, A3.15, A3.24, A4.14, |
| A5.01, A5.11, A6.53A, A6.56A, A8.12, |
| A8.13, A8.14, A9.22, A10.10, AND |
| LS0.00. |
| PLEASE SUBMIT ALL SHEETS INDICATED ON |
| THE DRAWING INDEX. SECTION 104.2.1. |
| 26) PLANS SUBMITTED ARE NOT COMPLETE. |
| MANY SHEETS APPEAR TO BE INCOMPLETE AND |
| THE FOLLOWING SHEETS SHOWN ON THE INDEX |
| WERE NOT SUBMITTED. P2.01, P2.05, P2.06, |
| P2.27, P2.29, P2.30, P2.31, P2.32, |
| P2.34, P2.35, P2.36, P2.62, P2.63, |
| P2.64, P2.65, P2.66, P2.67, P2.68, |
| P2.69, P3.03, P3.04, P3.05, P3.06, |
| P3.07, P3.08, P3.09, P3.10, P3.11, |
| P3.12, P3.13, AND P6.02. |
| 27) SUBMIT A STORM BLDG DRAIN ISOMETRIC |
| SHOWING ALL PIPE SIZES, AND SHOW THE |
| LOCATION OF ALL STORM RISER DIAGRAMS AS |
| THEY CONNECT TO THE BLDG. DRAIN AND SHOW |
| SQUARE FOOTAGE AS IT ACCUMULATES IN THE |
| SYSTEM. SECTIONS 1106, 1107 & 104.2.1. |
| 28) SUBMIT STORM RISER DIAGRAMS SHOWING |
| ALL PIPE SIZES AND SQ.FT. SECTIONS 1106, |
| 1107 AND 104.2.1. |
| 29) SUBMIT A CONDENSATE BLDG DRAIN |
| ISOMETRIC SHOWING ALL PIPE SIZES. |
| SECTION 104.2.1. |
| 30) SUBMIT CONDENSATE RISER DIAGRAM. |
| SECTION 104.2.1 |
| 31) SUBMIT A SANITARY BLDG. DRAIN |
| ISOMETRIC. SHOW ALL PIPE SIZES, LOCATION |
| OF EACH RISER CONNECTING TO BLDG. DRAIN, |
| AND DFU'S AS THEY ACCUMULATE IN THE |
| SYSTEM. SECTION 104.3.1.1. |
| 32) SHEETS FOR UNIT TYPES ARE INCOMPLETE |
| AND REQUIRE MORE INFORMATION. SOME |
| SHEETS SHOW SANT., VENT, WATER, COND., |
| T/P, OR ANOTHER UNIDENTIFIED LINE, BUT |
| ALL DO NOT HAVE ALL INFORMATION |
| REQUIRED. |
| 33) SHOW STACK NUMBERS FOR EACH STACK IN |
| ALL UNIT SHEETS. SECTION 104.2.1. |
| 34) SHT P2.11 IS MISLABELED AS M2.11, OR |
| IT IS A MECH. SHEET. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| 34) SHT P2.02 UNIT 2, INDICATE WHERE LAV |
| RISER CONNECTS TO THE SANT. BRANCH LINE. |
| SECTION 104.2.1. |
| UNIT 3, THE VENT LINE IS SHOWN AS |
| SANT. |
| UNIT 4, NO SANT. TO W.M, NO VENT LINES |
| SHOWN. SECTION 104.2.1. |
| 35) SHT P2.03 ALL UNITS, NO VENT LINES |
| SHOWN, NO WATER LINES SHOWN. |
| UNIT 5, NO SANT. TO W/M. |
| UNIT 8, ONLY THE FIXTURES WITHIN THE |
| BATHROOM GROUP SHALL CONNECT TO THE |
| WET-VENTED HORIZONTAL BRANCH DRAIN. THE |
| KITCHEN SINK SHALL DISCHARGE DOWNSTREAM |
| OF THE WET VENT. SECTION 909.1 |
| 36) SHT P2.04 PIPING INCOMPLETE. SECTION |
| 104.2.1. |
| 37) SHT P2.07 PIPING INCOMPLETE. |
| 104.2.1 |
| 38) SHT P2.08 UNIT 4, LAV VENT SHOWN OUT |
| OF THE WALL. SEC 104.2.1. |
| 39) SHTS P2.09 & P2.10 PIPING |
| INCOMPLETE. NO WATER LINES. SEC |
| 104.2.1. |
| 40) SHT P2.12 PIPING INCOMPLETE. |
| UNIT 15 SHOWER NOT VENTED. SEC |
| 901.2.1. |
| 41) SHT P2.13 PIPING NOT COMPLETE. |
| SECTION 104.2.1. |
| 42) SHT P2.14 PIPING INCOMPLETE. |
| UNIT HH1 MASTER BATH DOUBLE LAV SHOWS |
| SANT PIPING FROM TWO DIFFERENT RISERS. |
| PLEASE CLARIFY. SEC 104.2.1. |
| TRASH CHUED LABELED AS PRIMARY AIR |
| SHAFT #3. PLEASE CLARIFY. 104.2.1. |
| 43) SHT P2.15 PIPING INCOMPLETE. |
| UNIT VV1 SHOWS VENT UNDER M/B TUB. |
| PLEASE CLARIFY. |
| UNIT A1 IS LAV IN M/B ON A SEPARATE |
| RISER STACK FROM OTHER M/B FIXTURES. |
| PLEASE CLARIFY. SECTION 104.2.1. |
| 44) SHTS P2.17 THRU P2.54 PIPING |
| INCOMPLETE. SECTION 104.2.1. |
| 45) P2.21 UNITS A1 & VV1 BATH #2 SHOWER |
| NOT VENTED. SECTION 901.2.1. |
| UNIT A1 WHAT TYPE OF VENT IS THE |
| KITCHEN SINK UTILIZING? SECTION 901.2.1 |
| 46) SHT P2.39 HAS A REFERENCE TO SHT |
| P2. |
| NO SHT P2. IS LOCATED. PLEASE CLARIFY. |
| SECTION 104.2.1. |
| 47) SHT 2.44 UNIT S MASTER BATH WATER |
| CLOSET, MAX 10' FROM POINT OF VENT. |
| TABLE 906.1. |
| 48) SHT P2.50 UNTI P2 LAUNDRY SINK SHALL |
| NOT DISCHARGE INTO THE WET VENT FOR THE |
| BATHROOM FIXTURES. SECTION 909.1. |
| 49) SHT P2.53 UNIT 0 BATH #2 KITCHEN |
| SINK SHALL NOT DISCHARGE INTO THE WET |
| VENT. SECTION 909.1. |
| 50) SHT 2.57 WOMEN'S BATHROOM DOES NOT |
| REFLECT THE SANT. RISER DIAGRAM. W/C IN |
| WOMEN'S STALL MAX. 10' FROM POINT OF |
| VENT. TABLE 906.1. INDICATE USE OF FLOOR |
| DRAIN FOR FIXTURE NEXT TO SHOWER IN |
| MEN'S BATHROOM. SECTION 104.2.1. |
| 51) ALL SANT. RISERS WITH WASH MACHINES, |
| REQUIRE A STANDPIPE AND THE CLEANOUT |
| SHALL BE LOCATED 4' ABOVE THE FLOOR FOR |
| ACCESS. SECTIONS 1002.1, 802.4 & |
| 708.10. |
| 52) SHT P3.01 DOMESTIC WATER RISER |
| DIAGRAMS. AIR CHAMBERS ARE NOT APPROVED. |
| DELETE FROM RISERS. SECTION 604.9. |
| 53) SHT 3.14 RISER 21 MAX 4 FIXTURE |
| UNITS ON 2" WET VENT. TAB 909.3 |
| 54) SHT PE.15 RISERS 27/34 OFFSET VENT |
| REQUIRED. SECTION 915. |
| RISERS 55/56 IDENTIVY FIXTURE BY |
| KITCHEN SINK. SEC 104.2.1 |
| RISER 28 OFFSET VENT REQUIRED. 915. |
| RISERS 29/31 OFFSET VENT REQUIRED. 915 |
| - MASTER BATH 21ST FLOOR MAX 4 FU ON 2" |
| WET VENT. TABLE 909.3. FLOORS 6 THRU 15, |
| MAXIMUM 4 FU ON 2" WET VENT. TAB 909.3. |
| RISERS 30/32 OFFSET VENT REQUIRED. |
| 915. |
| MAX 4 FU ON 2" WET VENT. TAB 909.3 |
| RISER 38 OFFSET VENT REQUIRED. SEC 915 |
| MAX. 4 FU ON 2" WET VENT TAB 909.3. |
| 55) SHT P3.16 RISERS 39.75 OFFSET VENT |
| REQUIRED SEC 915. |
| RISER 39 MAX. 4 FU ON 2" WET VENT. |
| TABLE 909.3. |
| RISER 59 OFFSET VENT REQD. SEC 915. |
| RISER 11 OFFSET VENT REQD. SECTION |
| 915. |
| RISER 12 OFFSET VENT REQD. SEC 915. - |
| INDICATE WHICH FLOOR/FLOORS THE SANT. IS |
| FOR ABOVE THE 15TH FLOOR. - MAX 4 FU ON |
| 2" WET VENT. TABLE 909.3 |
| 56) SHT P3.17 RISER 23 OFFSET VENT |
| REQUIRED. SECTION 915. |
| RISER 24 OFFSET VENT REQD. SEC. 915. - |
| MAX. 4 FU ON 2" WET VENT. TABLE 909.3 |
| RISERS 26/35 OFFSET VENT REQD. SEC. 915 |
| - FIXTURE MISLABELED AS KITCHEN SINK IN |
| BATHROOM GROUP. SECTION 104.2.1. |
| 57) SHT P3.18 RISER 70 OFSET VENT REQD. |
| SECTION 915. - MAX 4 FU ON 2" WET VENT. |
| TABLE 909.3. |
| RISER 15 MAX. 4 FU ON 2" WET VENT. |
| TABLE 909.3 |
| RISER 18 ABOVE 21ST FLOOR STATES VENT |
| BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY |
| SECTIONS 104.2.1. & 903.1. |
| RISER 19 ABOVE 21TH FLOOR STATES VENT |
| BACK DOWN TO 15TH FLOOR. PLEASE CLARIFY |
| SECTIONS 104.2.1. & 903.1. |
| 58) SHT P3.19 RISER 1 OFFSET VENT |
| REQUIRED. SECTION 915. |
| RISERS 2/55 SOIL STACK AND VENT STACK |
| ARE CROSSED. - OFFSET VENT REQUIRED. |
| SECTION 915. |
| RISER 3 VENT STACK SHALL CONTINUE AND |
| NOT TIE BACK INTO THE SOIL STACK. |
| SECTION 903.1 |
| RISER 4 MAX 4 FU ON 2" WET VENT. |
| 909.3. |
| RISER 5 OFFSET VENT REQUIRED. SEC 915. |
| 59) SHT P3.20 RISER 6 OFFSET VENT |
| REQUIRED. SECTION 915. - MAX 4 FU ON 2" |
| WET VENT. TABLE 909.3. |
| RISER 54 MAX 4 FU ON 2" WET VENT. TABLE |
| 909.3. |
| RISER 7 OFFSET VENT REQUIRED. SEC 915. |
| MAX. 4 FU ON 2" WET VENT. TABLE 909.3. |
| RISER 8 OFFSET VENT REQUIRED. SEC 915. |
| MAX 4 FU ON 2" WET VENT. TABLE 909.3. |
| 60) SHT P3.21 RISER 40 OFFSET VENT |
| REQUIRED. SECTION 915. |
| RISER 41 OFFSET VENT REQD. SEC 915. |
| RISER 44 OFFSET VENT REQD. SEC 915. - |
| INDICATE IF THERE ARE BRANCH LINES |
| CONNECTING TO STACK ON THE 17TH THRU |
| 20TH FLOORS. SECTION 104.2.1. |
| RISER 76 MAX 4 FU ON 2" WET VENT. TABLE |
| 909.3. |
| 61) SHT P3.22 RISER 45 OFFSET VENT REQD. |
| SECTION 915. - INDICATE IF THERE ARE |
| BRANCH LINES CONNECTING TO THE STACK ON |
| THE 17TH THRU 20TH FLOORS. SEC 104.2.1. |
| RISER 46 OFFSET VENT REQD. SEC 915. - |
| MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| 909.3 |
| RISER 47 OFFSEC VENT REQD. SEC 915. - |
| MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| 909.3 |
| RISER 49 OFFSET VENT REQD. SEC 915. - |
| MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| 909.3 |
| 62) SHT P3.23 RISER 63 MAXIMUM 4 FU ON |
| 2" WET VENT. TABLE 909.3 |
| RISER 43 OFFSET VENT REQD. SEC 915. - |
| MAXIMUM 4 FU ON 2" WET VENT. TABLE |
| 909.3 |
| RISER 60 WASH MACHINE AND KITCHEN SINK |
| SHALL CONNECT TO THE SANT. STACK NOT THE |
| VENT STACK. SECTION 104.2.1. |
| 63) SHT P6.01 COOLING TOWER MAKE UP |
| DETAIL, INDICATE METHOD FOR REQUIRED |
| BACKFLOW PROTECTION. SECTION 608.13.2. - |
| WATER HEATER PIPING DETAIL, THERMAL |
| EXPANSION CONTROL REQUIRED. SECTION |
| 607.3.2. - TRASH CHUTE PIPING DIAGRAM. |
| INDICATE METHOD FOR REQUIRED BACKFLOW |
| PROTECTION. SECTION 608.13.2. |
| 64) BACKFLOW PROTECTION REQUIRED FOR THE |
| POOL MAKE UP WATER. SUBMIT A DETAIL. |
| SECTION 608.13.2. |
| 65) BECAUSE THE PLANS ARE INCOMPLETE, |
| MORE COMMENTS MAY BE FOURTHCOMMING WHEN |
| THE PLANS ARE RESUBMITTED. - PLEASE |
| RETURN THE PLUMBING PLANS WITH THE RED |
| LINE NOTES WHEN RESUBMITTING TO HELP |
| REVIEWING PLANS FOR SECOND REVIEW. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |