Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop M
Sequence Number 1
Notes
Date Text
2005-01-18 00:00:00DENIED:
 1.THE FOLLOWING PLANS ARE INDICATED
 ON THE "INDEX" BUT WERE NOT INCLUDED:
 A1.02, A3.11, A3.12, A3.14, A3.15,
 A3.24, A4.14, A5.01, A5.11, A6.53A,
 A6.56A, A8.12, A8.13, A8.22, A8.23,
 A8.41A, A8.44, A9.22, A10.01, M1.14,
 M2.05, M2.07, M2.11, M2.19, M2.20,
 M2.33, M2.34, M2.35, M3.02, M4.00,
 M4.02, M4.03, M5.04, M6.01 THROUGH
 M6.09, M7.02.PLEASE NOTE, PLAN SHEET
 M7.02 IS MISSING BUT THERE ARE TWO
 M7.01 SHEETS THAT ARE NOT IDENTICAL,
 ONE
 MAY BE JUST MISMARKED.
  
 2.PLANS ARE NOT COMPLETE THEREFORE
 ADDITIONAL COMMENTS MAY ARRISE DUE TO
 THE RESPONSE TO 1ST REVIEW AND ANY NEW
 DETAILS ADDED.
  
 3.PLAN SHEET A1.03 GENERATOR RM.
 PLEASE PROVIDE ELEVATION FOR THE
 TERMINATION OF THE MUFFLER EXHAUST,
 SHOW
 CLEARANCES TO FRESH AIR INTAKES I.E.,
 DOORS, WINDOWS, LOUVERS, ETC.
  
 4.PROVIDE DETAILS FOR VENTILATION FOR
 THE GENERATOR ROOM.PLAN ALSO
 INDICATES
 A FUEL TANK.PROVIDE DETAILS FOR THE
 CAPACITY OF THE FUEL TANK, VENTING
 REQUIREMENTS AND FILL PIPE INFORMATION.
  
 5.PROVIDE SUBMTTIALS FOR THE
 GENERATOR
 AND FUEL TANK.
  
 6.PLAN SHEET 7.14 INDICATES TRASH
 CHUTE WITH THE SMOKE EXHAUST IN THE
 SAME
 SHAFT.PLEASE CLARIFY, INDICATE RATING
 OF SEPARATION.
  
 7.PLAN SHEET M1.05 (AND SUBSEQUENT
 SHEETS), INDICATE HPU-X OR EF-X.THESE
 ARE NOT IDENTIFIED ON THE RESPECTIVE
 EQUIPMENT SCHEDULES.
  
 8.EF-X DOES NOT INDICATE ANY
 TERMINATION, PLEASE CLARIFY.PLEASE
 NOTE, PER 2001 FBC(M)503.1 ARE REMOVED
 BY EVERY MECHANICAL EXHAUST SYSTEM
 SHALL
 BE DICHARGED TO THE OUTDOORS.
  
 9.PLANS DO NOT INDCLUDE DETAILS FOR
 COMMON AREAS.
  
 10. PLAN SHEETS M2.02, 2.03, 2.04, ETC,
 INDICATE DRYER EXHAUST & TOILET EXHAUST
 PENTRATING AND RUNNING THROUGH THE
 RETURN AIR PLENUM.PER 2001
 FBC(M)601.3, EXHAUST DUCTS UNDER
 POSITIVE PRESSURE SHALL NOT EXTEND INTO
 OR PASS THROUGH A RETURN AIR PLENUM.
  
 11.NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.PLEASE NOTE
 CONSTURCITON OF THE RETURN AIR PLENUM
 SHALL COMPLY WITH 2001 FBC(M) 603.8. THE
 DOOR TO THE MECHANICAL CLOSET HAVING A
 RETURN AIR PLENUM SHALL BE NON
 COMBUSTIBLE.
  
 12. PLANS INDICATE THE USE OF BOOSTER
 FANS FOR THE DRYER.PLEASE SUBMIT ALL
 DOCUMENTATION I.E., DRYER MANUFACTURER,
 BOOSTER FAN SUBMITTAL AND ENGINEERING
 DATA.THIS WILL BE REVIEWED UNDER 2001
 FBC 103.7.1, ALTERNATE MEANS AND
 METHODS
 AND WILL REQUIRE REVIEW AND APPROVAL BY
 THE BUILDING OFFICIAL/DIRECTOR.
  
 13.CW RISERS AND BRANCH LINES ARE NOT
 SIZED.(INCOMPLETE)
  
 14.PROVIDE SUBMITTALS FOR THE PUMPS,
 COOLING TOWERS, HEAT EXCHANGERS, HEAT
 PUMPS, EXHAUST FANS, AIR SEPARATOR,
 EXPANSION TANK AND ALL PERTINANT VALVES
 AND CONTROLS REQUIRED TO COMPLETE AND
 OPERATE SYSTEM.
  
 15.PROVIDE OUTSIDE AIR CALCULATIONS
 FOR ALL COMMON AREAS AS WELL AS THE
 RESIDENCE.SHOW COMPLIANCE WITH 2001
 FBC(M) TABLE 403.3 AND 402.
  
 16. CONDENSATE RISER ON PLAN SHEET
 P3.13
 & P3.14.PLAN SHEET P3.13 IS NOT IN
 THE
 SUBMITTAL AND PLAN SHEET P3.14 SHOWS A
 SANITARY RISER.
  
 17.PROVIDE PLANS FOR VENTILATION FOR
 ALL COMMON HABITABLE AREAS AS WELL AS
 NON HABITABLE (EQUIPMENT RMS,
 MECHANICAL
 ROOMS, ETC.)INDICATE ALL LOUVERS,
 DUCTS, EXAUST AND FRESH AIR INTAKES ON
 THE PLAN AND IDENTIFY ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  