2005-01-18 00:00:00 | DENIED: |
| 1.THE FOLLOWING PLANS ARE INDICATED |
| ON THE "INDEX" BUT WERE NOT INCLUDED: |
| A1.02, A3.11, A3.12, A3.14, A3.15, |
| A3.24, A4.14, A5.01, A5.11, A6.53A, |
| A6.56A, A8.12, A8.13, A8.22, A8.23, |
| A8.41A, A8.44, A9.22, A10.01, M1.14, |
| M2.05, M2.07, M2.11, M2.19, M2.20, |
| M2.33, M2.34, M2.35, M3.02, M4.00, |
| M4.02, M4.03, M5.04, M6.01 THROUGH |
| M6.09, M7.02.PLEASE NOTE, PLAN SHEET |
| M7.02 IS MISSING BUT THERE ARE TWO |
| M7.01 SHEETS THAT ARE NOT IDENTICAL, |
| ONE |
| MAY BE JUST MISMARKED. |
| |
| 2.PLANS ARE NOT COMPLETE THEREFORE |
| ADDITIONAL COMMENTS MAY ARRISE DUE TO |
| THE RESPONSE TO 1ST REVIEW AND ANY NEW |
| DETAILS ADDED. |
| |
| 3.PLAN SHEET A1.03 GENERATOR RM. |
| PLEASE PROVIDE ELEVATION FOR THE |
| TERMINATION OF THE MUFFLER EXHAUST, |
| SHOW |
| CLEARANCES TO FRESH AIR INTAKES I.E., |
| DOORS, WINDOWS, LOUVERS, ETC. |
| |
| 4.PROVIDE DETAILS FOR VENTILATION FOR |
| THE GENERATOR ROOM.PLAN ALSO |
| INDICATES |
| A FUEL TANK.PROVIDE DETAILS FOR THE |
| CAPACITY OF THE FUEL TANK, VENTING |
| REQUIREMENTS AND FILL PIPE INFORMATION. |
| |
| 5.PROVIDE SUBMTTIALS FOR THE |
| GENERATOR |
| AND FUEL TANK. |
| |
| 6.PLAN SHEET 7.14 INDICATES TRASH |
| CHUTE WITH THE SMOKE EXHAUST IN THE |
| SAME |
| SHAFT.PLEASE CLARIFY, INDICATE RATING |
| OF SEPARATION. |
| |
| 7.PLAN SHEET M1.05 (AND SUBSEQUENT |
| SHEETS), INDICATE HPU-X OR EF-X.THESE |
| ARE NOT IDENTIFIED ON THE RESPECTIVE |
| EQUIPMENT SCHEDULES. |
| |
| 8.EF-X DOES NOT INDICATE ANY |
| TERMINATION, PLEASE CLARIFY.PLEASE |
| NOTE, PER 2001 FBC(M)503.1 ARE REMOVED |
| BY EVERY MECHANICAL EXHAUST SYSTEM |
| SHALL |
| BE DICHARGED TO THE OUTDOORS. |
| |
| 9.PLANS DO NOT INDCLUDE DETAILS FOR |
| COMMON AREAS. |
| |
| 10. PLAN SHEETS M2.02, 2.03, 2.04, ETC, |
| INDICATE DRYER EXHAUST & TOILET EXHAUST |
| PENTRATING AND RUNNING THROUGH THE |
| RETURN AIR PLENUM.PER 2001 |
| FBC(M)601.3, EXHAUST DUCTS UNDER |
| POSITIVE PRESSURE SHALL NOT EXTEND INTO |
| OR PASS THROUGH A RETURN AIR PLENUM. |
| |
| 11.NO COMBUSTIBLES ALLOWED IN THE |
| RETURN AIR PLENUM.PLEASE NOTE |
| CONSTURCITON OF THE RETURN AIR PLENUM |
| SHALL COMPLY WITH 2001 FBC(M) 603.8. THE |
| DOOR TO THE MECHANICAL CLOSET HAVING A |
| RETURN AIR PLENUM SHALL BE NON |
| COMBUSTIBLE. |
| |
| 12. PLANS INDICATE THE USE OF BOOSTER |
| FANS FOR THE DRYER.PLEASE SUBMIT ALL |
| DOCUMENTATION I.E., DRYER MANUFACTURER, |
| BOOSTER FAN SUBMITTAL AND ENGINEERING |
| DATA.THIS WILL BE REVIEWED UNDER 2001 |
| FBC 103.7.1, ALTERNATE MEANS AND |
| METHODS |
| AND WILL REQUIRE REVIEW AND APPROVAL BY |
| THE BUILDING OFFICIAL/DIRECTOR. |
| |
| 13.CW RISERS AND BRANCH LINES ARE NOT |
| SIZED.(INCOMPLETE) |
| |
| 14.PROVIDE SUBMITTALS FOR THE PUMPS, |
| COOLING TOWERS, HEAT EXCHANGERS, HEAT |
| PUMPS, EXHAUST FANS, AIR SEPARATOR, |
| EXPANSION TANK AND ALL PERTINANT VALVES |
| AND CONTROLS REQUIRED TO COMPLETE AND |
| OPERATE SYSTEM. |
| |
| 15.PROVIDE OUTSIDE AIR CALCULATIONS |
| FOR ALL COMMON AREAS AS WELL AS THE |
| RESIDENCE.SHOW COMPLIANCE WITH 2001 |
| FBC(M) TABLE 403.3 AND 402. |
| |
| 16. CONDENSATE RISER ON PLAN SHEET |
| P3.13 |
| & P3.14.PLAN SHEET P3.13 IS NOT IN |
| THE |
| SUBMITTAL AND PLAN SHEET P3.14 SHOWS A |
| SANITARY RISER. |
| |
| 17.PROVIDE PLANS FOR VENTILATION FOR |
| ALL COMMON HABITABLE AREAS AS WELL AS |
| NON HABITABLE (EQUIPMENT RMS, |
| MECHANICAL |
| ROOMS, ETC.)INDICATE ALL LOUVERS, |
| DUCTS, EXAUST AND FRESH AIR INTAKES ON |
| THE PLAN AND IDENTIFY ACCORDINGLY. |
| |