2005-01-21 00:00:00 | 1. CONSTRUCTION, DEMOLITION, AND |
| RENOVATION TO COMPLY WITH NFPA 241. |
| |
| 2. TEMPORARY STANDPIPES ARE REQUIRED |
| WHEN THE BUILDING REACHES THREE |
| STORIES OR 30 FEET IN HEIGHT. |
| |
| 3. SINCE THE BUILDING WILL BE |
| CONSIDERED HIGH-RISE IT MUST |
| COMPLY WITH APPLICABLE BUILDING AND |
| FIRE CODE REQUIREMENTS FOR HIGH-RISE |
| BUILDINGS. |
| |
| 4. PLEASE EXPLAIN CONTROLLED ENTRY |
| AND EXIT NOTES ON PAGE LS1.01. |
| |
| 5. PLEASE INDICATE WHAT ELEVATORS |
| ARE STRETCHER ACCESSIBLE. |
| |
| 6. EXIT SIGN PLACEMENT SHALL NOT |
| EXCEED 100 FEET. |
| |
| 7. PLEASE ILLUSTRATE ALL EXIT |
| DISCHARGE LOCATIONS FROM THE |
| BUILDING. EXIT DISCHARGE LOCATIONS |
| SHALL COMPLY WITH APPLICABLE FIRE |
| CODE REQUIREMENTS. |
| |
| 8. KNOX-BOXES WILL BE REQUIRED FOR |
| THE BUILDING. |
| |
| 9. ON PAGE LS1.03 PLANS MAKE REFERENCE |
| TO HORIZONTAL EXITS. PLEASE EXPLAIN |
| HOW THE CODE REQUIREMENTS FOR |
| HORIZONTAL EXITS ARE BEING MET. |
| |
| 10. ON PAGE LS1.03 EXITING IS SHOWN |
| THRU TENANT STORAGE ROOM B. PLEASE |
| EXPLAIN WHAT CODE ALLOWS THIS TO |
| OCCUR. |
| |
| 11. EXIT PATH ON LS1.05 IS GOING |
| BETWEEN TWO HANDICAP VEHICLES. PLEASE |
| EXPLAIN. |
| |
| 12. PLEASE INDICATE INTERIOR FINISH |
| CLASSIFICATIONS FOR WALLS AND |
| CEILINGS. |
| |
| 13. PLEASE INDICATE OCCUPANT LOAD |
| FOR THE 5TH FLOOR LANAI SHOWN |
| ON PAGE LS1.07. |
| |
| 14. PLEASE VERIFY OCCUPANT LOADS |
| FOR THE HEALTH CLUB AND MULTI-PURPOSE |
| ROOMS TO DETERMINE IF EXIT DOORS |
| SWINGS ARE PROPER. LS1.07. |
| |
| 15. WHAT CODE REQUIREMENTS ARE BEING |
| MET |
| TO EXIT FROM THE DECK OF THE LANAI |
| AREA. |
| |
| 16. IS THE AREA CALLED OUT ON PAGE |
| LS1.10 "EXIT PATH OF TRAVEL-LIGHTED |
| AND PAINTED LINES OF DEMARKATION" |
| ALSO SLIP RESISTANT. |
| |
| 17. NO STORAGE OF ANY KIND WILL BE |
| ALLOWED IN LOCATIONS NOTED FOR |
| INSPECTION AND SERVICE ONLY. |
| |
| 18. THE FIRE PROTECTION FOR THE |
| COOLING TOWERS SHALL COMPLY WITH |
| NFPA 214. |
| |
| 19. PLEASE PROVIDE PRESCRIPTIVE |
| STRENGTH REQUIREMENTS FOR ALL |
| HANDRAILS AND GUARDRAILS. |
| |
| 20. SOME DOOR SWINGS ON THE MEZZANINE |
| LEVEL AND PARKING LEVEL P3 ON |
| PAGE A2.03 MAY NOT SWING IN THE |
| PROPER DIRECTION. |
| |
| 21. PARKING AREA TO COMPLY WITH |
| NFPA 88A. |
| |
| 22. NO NOTE INDICATING THAT STAIR #6 |
| IS PRESSURIZED. |
| |
| 23. PLANS ILLUSTRATE A 21ST FLOOR |
| BUT IT IS BELIEVED THAT THE PERMIT |
| APPLICATION INDICATES A 20 STORY |
| BUILDING. |
| |
| 24. DOOR SWINGS ON STAIR # 2,7,AND 8 |
| ARE SWINGING IN THE WRONG DIRECTION |
| ON PAGE A2.16. |
| |
| 25. WRONG ADDRESS NOTED ON F10 NOTE |
| ON PAGE A3.01. SAME CONDITION EXISTS |
| ON A3.03. |
| |
| 26. TWO FIRE DEPARTMENT CONNECTIONS |
| WILL BE REQUIRED SINCE IT IS A |
| HIGH-RISE BUILDING. |
| |
| 27. NEW FIRE ALARM SYSTEM SHALL BE |
| MONITORED UL LISTED CENTRAL STATION |
| APPROVED FOR CENTRAL STATION SERVICE. |
| |
| 28. IS ANY ACCESS PROVIDED FOR |
| MECHANICAL SPACES SHOWN ON PAGE A3.21. |
| |
| 29. A DOOR IS NOTED WITHIN THE EXIT |
| ENCLOSURE FOR STAIR # 2 NEAR |
| ELEVATOR # 3. PLEASE EXPLAIN CODE |
| PROVISIONS THAT YOU MEET THAT |
| ALLOWS FOR THIS. |
| |
| 30. PLEASE INDICATE SIZE OF PEDESTRIAN |
| PASS DOOR ON PAGE A4.11. |
| |
| 31. KNOX-BOX LOCKING CAPS WILL BE |
| REQUIRED ON FIRE DEPARTMENT |
| CONNECTIONS. |
| |
| 32. ALL SMOKE DETECTORS SHALL BE |
| INSTALLED A MINIMUM OF THREE FEET |
| FROM AC DIFFUSERS. |
| |
| 33. WHAT IS THE ELEVATION OF THE |
| TERRACE SHOWN ON PAGE A4.41. |
| |
| 34. HAND WRITTEN NOTES APPEAR ON |
| SEVERAL PAGES OF THE PLAN. |
| |
| 35. EXIT STAIRS ARE TO BE KEPT UP |
| WITH CONSTRUCTION. |
| |
| 36. NO COMBUSTIBLES ALLOWED IN ANY |
| RETURN AIR PLENUM. NOTES LOCATED IN |
| PLANS. |
| |
| 37. NO SMOKE DETECTOR SHOWN IN FIRE |
| COMMAND ROOM. |
| |
| 38. ELEVATOR WARNING SIGNS REQUIRED |
| AT ELEVATOR LOBBIES. |
| |
| 39. PLEASE INDICATE LOCATIONS OF |
| SPEAKER STROBES FOR APARTMENTS |
| PROVIDED FOR THE HANDICAPPED. |
| |
| 40. ANY SOFFITS THAT ARE PLANNED SHALL |
| NOT INTERFERE WITH ANY FIRE PROTECTION |
| EQUIPMENT OR DEVICES. |
| |
| 41. PLEASE PROVIDE FLAMESPREAD DETAILS |
| ON HIGH-DENSITY STYROFOAM BLOCK |
| SHOWN ON A7.02. PLEASE EXPLAIN |
| PURPOSE OF MATERIAL. |
| |
| 42. STAIR PRESSURIZZATION DUCT SHOWN |
| ON PAGE A7.11 MUST BE A MINIMUM 2 |
| HOUR RATED SHAFT. |
| |
| 43. WHAT ACTIVITIES OCCUR IN OPEN |
| AIR COVERED STRUCTURE SHOWN ON PAGE |
| A8.11. |
| |
| 44. BUILDING IS LOCATED IN THE CITY |
| FIRE LIMITS. CERTAIN RESTRICTIONS |
| WILL APPLY SEE APPENDIX F, LOCAL |
| AMENDMENTS TO THE FLORIDA BUILDING |
| CODE. |
| |
| 45. PLEASE EXPLAIN USE OF CARD READERS |
| FOR THE BUILDING. WHAT ISSUES DO |
| THEY RAISE IF ANY TO EXITING. |
| |
| 46. ALL FIRE DOORS AND WINDOWS TO |
| COMPLY WITH NFPA 80, FIRE DOORS AND |
| WINDOWS. PLEASE ADD NOTE TO |
| DRAWINGS. |
| |
| 47. NO CUTTING OR WELDING OPERATIONS |
| TO OCCUR WITHOUT APPROVAL OF THE |
| FIRE PREVENTION BUREAU AND COMPLIANCE |
| WITH NFPA 51B. |
| |
| 48. ALL SHAFTS THAT ARE LARGE ENOUGH |
| FOR PERSONS TO FALL INTO MUST BE |
| MARKED SHAFTWAY WITH 6" HIGH |
| LETTERS. |
| |
| 49. ALL ARCHITECURAL TRIM LOCATED |
| IN THE FIRE LIMITS SHALL BE |
| NON-COMBUSTIBLE. |
| |
| 50. PAGE E0.01 INSERTED UPSIDE DOWN |
| IN SET. |
| |
| 51. A SITE PLAN DETAILING ALL EXISTING |
| OR NEW FIRE HYDRANTS AND WATER MAINS |
| SHALL BE PROVIDED. |
| |
| 52. PLEASE INDICATE EMERGENCY LIGHTING |
| FOR LANAI DECK, PAGE E1.03. |
| |
| 53. CLASS B FIRE ALARM CIRCUITS SHOWN |
| ON PAGE E8.04. ONLY CLASS A, STYLE D |
| OR FULLY ADDRESSABLE FIRE ALARM |
| CIRCUITS |
| SHALL BE PERMITTED. |
| |
| 54. FIRE ALARM SYSTEM SHALL MEET THE |
| SURVIVABILITY REQUIREMENTS OF NFPA 72. |
| |
| 55. NOTE # 40 ON PAGE E8.04 IS |
| INCORRECT. LIFE SAFETY CODE 2003 |
| EDITION SHOULD BE REFERENCED. |
| |
| 56. BUILDING IS TO COMPLY WITH |
| SECTON 11-8, LIFE SAFETY CODE, 2003 |
| EDITION. |
| |
| 57. THE FIREFIGHTER SMOKE MANAGEMENT |
| PANEL SHALL PROVIDE A GRAPHIC |
| REPRESENTATION OF THE BUILDING. HOA |
| SWITCHES WITH NO OVERLAY OF THE |
| BUILDING WILL NOT BE ACCEPTABLE. |
| |
| 58. MORE DETAILS REQUIRED ON PROPOSED |
| DRYER BOOSTER FANS. SHOWN ON |
| ELECTRICAL PAGES. |
| |
| 59. EXIT SIGN SHOWN ON PAGE E2.01 |
| DIRECTING PERSONS INTO LOADING |
| AREA. PLEASE EXPLAIN. |
| |
| 60. EXIT SIGNS APPEAR TO BE MISSING |
| ON SOME OF THE ELECTRICAL DRAWINGS. |
| |
| 61. MORE EXIT SIGNS APPEAR TO BE |
| NEEDED ON PAGE E2.02. |
| |
| 62. MORE EXIT SIGNS APPEAR TO BE |
| NEEDED ON PAGE E2.08. |
| |
| 63. ONLY TWO EXIT SIGNS SHOWN ON |
| PAGE E2.11. |
| |
| 64. THE ANTICPATED STACK EFFECT NOTE |
| WORDING SHALL BE ADDED TO THE |
| MECHANICAL PLANS. |
| |
| 65. FIRE DAMPERS TO COMPLY WITH |
| UL 555. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| 835-2910 |