Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-01-21 00:00:001. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 2. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE
 STORIES OR 30 FEET IN HEIGHT.
  
 3. SINCE THE BUILDING WILL BE
 CONSIDERED HIGH-RISE IT MUST
 COMPLY WITH APPLICABLE BUILDING AND
 FIRE CODE REQUIREMENTS FOR HIGH-RISE
 BUILDINGS.
  
 4. PLEASE EXPLAIN CONTROLLED ENTRY
 AND EXIT NOTES ON PAGE LS1.01.
  
 5. PLEASE INDICATE WHAT ELEVATORS
 ARE STRETCHER ACCESSIBLE.
  
 6. EXIT SIGN PLACEMENT SHALL NOT
 EXCEED 100 FEET.
  
 7. PLEASE ILLUSTRATE ALL EXIT
 DISCHARGE LOCATIONS FROM THE
 BUILDING. EXIT DISCHARGE LOCATIONS
 SHALL COMPLY WITH APPLICABLE FIRE
 CODE REQUIREMENTS.
  
 8. KNOX-BOXES WILL BE REQUIRED FOR
 THE BUILDING.
  
 9. ON PAGE LS1.03 PLANS MAKE REFERENCE
 TO HORIZONTAL EXITS. PLEASE EXPLAIN
 HOW THE CODE REQUIREMENTS FOR
 HORIZONTAL EXITS ARE BEING MET.
  
 10. ON PAGE LS1.03 EXITING IS SHOWN
 THRU TENANT STORAGE ROOM B. PLEASE
 EXPLAIN WHAT CODE ALLOWS THIS TO
 OCCUR.
  
 11. EXIT PATH ON LS1.05 IS GOING
 BETWEEN TWO HANDICAP VEHICLES. PLEASE
 EXPLAIN.
  
 12. PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND
 CEILINGS.
  
 13. PLEASE INDICATE OCCUPANT LOAD
 FOR THE 5TH FLOOR LANAI SHOWN
 ON PAGE LS1.07.
  
 14. PLEASE VERIFY OCCUPANT LOADS
 FOR THE HEALTH CLUB AND MULTI-PURPOSE
 ROOMS TO DETERMINE IF EXIT DOORS
 SWINGS ARE PROPER. LS1.07.
  
 15. WHAT CODE REQUIREMENTS ARE BEING
 MET
 TO EXIT FROM THE DECK OF THE LANAI
 AREA.
  
 16. IS THE AREA CALLED OUT ON PAGE
 LS1.10 "EXIT PATH OF TRAVEL-LIGHTED
 AND PAINTED LINES OF DEMARKATION"
 ALSO SLIP RESISTANT.
  
 17. NO STORAGE OF ANY KIND WILL BE
 ALLOWED IN LOCATIONS NOTED FOR
 INSPECTION AND SERVICE ONLY.
  
 18. THE FIRE PROTECTION FOR THE
 COOLING TOWERS SHALL COMPLY WITH
 NFPA 214.
  
 19. PLEASE PROVIDE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR ALL
 HANDRAILS AND GUARDRAILS.
  
 20. SOME DOOR SWINGS ON THE MEZZANINE
 LEVEL AND PARKING LEVEL P3 ON
 PAGE A2.03 MAY NOT SWING IN THE
 PROPER DIRECTION.
  
 21. PARKING AREA TO COMPLY WITH
 NFPA 88A.
  
 22. NO NOTE INDICATING THAT STAIR #6
 IS PRESSURIZED.
  
 23. PLANS ILLUSTRATE A 21ST FLOOR
 BUT IT IS BELIEVED THAT THE PERMIT
 APPLICATION INDICATES A 20 STORY
 BUILDING.
  
 24. DOOR SWINGS ON STAIR # 2,7,AND 8
 ARE SWINGING IN THE WRONG DIRECTION
 ON PAGE A2.16.
  
 25. WRONG ADDRESS NOTED ON F10 NOTE
 ON PAGE A3.01. SAME CONDITION EXISTS
 ON A3.03.
  
 26. TWO FIRE DEPARTMENT CONNECTIONS
 WILL BE REQUIRED SINCE IT IS A
 HIGH-RISE BUILDING.
  
 27. NEW FIRE ALARM SYSTEM SHALL BE
 MONITORED UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 28. IS ANY ACCESS PROVIDED FOR
 MECHANICAL SPACES SHOWN ON PAGE A3.21.
  
 29. A DOOR IS NOTED WITHIN THE EXIT
 ENCLOSURE FOR STAIR # 2 NEAR
 ELEVATOR # 3. PLEASE EXPLAIN CODE
 PROVISIONS THAT YOU MEET THAT
 ALLOWS FOR THIS.
  
 30. PLEASE INDICATE SIZE OF PEDESTRIAN
 PASS DOOR ON PAGE A4.11.
  
 31. KNOX-BOX LOCKING CAPS WILL BE
 REQUIRED ON FIRE DEPARTMENT
 CONNECTIONS.
  
 32. ALL SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF THREE FEET
 FROM AC DIFFUSERS.
  
 33. WHAT IS THE ELEVATION OF THE
 TERRACE SHOWN ON PAGE A4.41.
  
 34. HAND WRITTEN NOTES APPEAR ON
 SEVERAL PAGES OF THE PLAN.
  
 35. EXIT STAIRS ARE TO BE KEPT UP
 WITH CONSTRUCTION.
  
 36. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUM. NOTES LOCATED IN
 PLANS.
  
 37. NO SMOKE DETECTOR SHOWN IN FIRE
 COMMAND ROOM.
  
 38. ELEVATOR WARNING SIGNS REQUIRED
 AT ELEVATOR LOBBIES.
  
 39. PLEASE INDICATE LOCATIONS OF
 SPEAKER STROBES FOR APARTMENTS
 PROVIDED FOR THE HANDICAPPED.
  
 40. ANY SOFFITS THAT ARE PLANNED SHALL
 NOT INTERFERE WITH ANY FIRE PROTECTION
 EQUIPMENT OR DEVICES.
  
 41. PLEASE PROVIDE FLAMESPREAD DETAILS
 ON HIGH-DENSITY STYROFOAM BLOCK
 SHOWN ON A7.02. PLEASE EXPLAIN
 PURPOSE OF MATERIAL.
  
 42. STAIR PRESSURIZZATION DUCT SHOWN
 ON PAGE A7.11 MUST BE A MINIMUM 2
 HOUR RATED SHAFT.
  
 43. WHAT ACTIVITIES OCCUR IN OPEN
 AIR COVERED STRUCTURE SHOWN ON PAGE
 A8.11.
  
 44. BUILDING IS LOCATED IN THE CITY
 FIRE LIMITS. CERTAIN RESTRICTIONS
 WILL APPLY SEE APPENDIX F, LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING
 CODE.
  
 45. PLEASE EXPLAIN USE OF CARD READERS
 FOR THE BUILDING. WHAT ISSUES DO
 THEY RAISE IF ANY TO EXITING.
  
 46. ALL FIRE DOORS AND WINDOWS TO
 COMPLY WITH NFPA 80, FIRE DOORS AND
 WINDOWS. PLEASE ADD NOTE TO
 DRAWINGS.
  
 47. NO CUTTING OR WELDING OPERATIONS
 TO OCCUR WITHOUT APPROVAL OF THE
 FIRE PREVENTION BUREAU AND COMPLIANCE
 WITH NFPA 51B.
  
 48. ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY WITH 6" HIGH
 LETTERS.
  
 49. ALL ARCHITECURAL TRIM LOCATED
 IN THE FIRE LIMITS SHALL BE
 NON-COMBUSTIBLE.
  
 50. PAGE E0.01 INSERTED UPSIDE DOWN
 IN SET.
  
 51. A SITE PLAN DETAILING ALL EXISTING
 OR NEW FIRE HYDRANTS AND WATER MAINS
 SHALL BE PROVIDED.
  
 52. PLEASE INDICATE EMERGENCY LIGHTING
 FOR LANAI DECK, PAGE E1.03.
  
 53. CLASS B FIRE ALARM CIRCUITS SHOWN
 ON PAGE E8.04. ONLY CLASS A, STYLE D
 OR FULLY ADDRESSABLE FIRE ALARM
 CIRCUITS
 SHALL BE PERMITTED.
  
 54. FIRE ALARM SYSTEM SHALL MEET THE
 SURVIVABILITY REQUIREMENTS OF NFPA 72.
  
 55. NOTE # 40 ON PAGE E8.04 IS
 INCORRECT. LIFE SAFETY CODE 2003
 EDITION SHOULD BE REFERENCED.
  
 56. BUILDING IS TO COMPLY WITH
 SECTON 11-8, LIFE SAFETY CODE, 2003
 EDITION.
  
 57. THE FIREFIGHTER SMOKE MANAGEMENT
 PANEL SHALL PROVIDE A GRAPHIC
 REPRESENTATION OF THE BUILDING. HOA
 SWITCHES WITH NO OVERLAY OF THE
 BUILDING WILL NOT BE ACCEPTABLE.
  
 58. MORE DETAILS REQUIRED ON PROPOSED
 DRYER BOOSTER FANS. SHOWN ON
 ELECTRICAL PAGES.
  
 59. EXIT SIGN SHOWN ON PAGE E2.01
 DIRECTING PERSONS INTO LOADING
 AREA. PLEASE EXPLAIN.
  
 60. EXIT SIGNS APPEAR TO BE MISSING
 ON SOME OF THE ELECTRICAL DRAWINGS.
  
 61. MORE EXIT SIGNS APPEAR TO BE
 NEEDED ON PAGE E2.02.
  
 62. MORE EXIT SIGNS APPEAR TO BE
 NEEDED ON PAGE E2.08.
  
 63. ONLY TWO EXIT SIGNS SHOWN ON
 PAGE E2.11.
  
 64. THE ANTICPATED STACK EFFECT NOTE
 WORDING SHALL BE ADDED TO THE
 MECHANICAL PLANS.
  
 65. FIRE DAMPERS TO COMPLY WITH
 UL 555.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910