Date |
Text |
2005-01-06 00:00:00 | *************** UNSAT ***************** |
| |
| PLAN REVIEW ONLY FOR "TWO CITY PLAZA" |
| PLANS NOT SUBMITTED FOR PERMIT AT THIS |
| TIME, ONLY IN FOR "PLAN REVIEW". |
| |
| |
| **************************************** |
| *************************************** |
| |
| PLEASE SEE THAT DUE TO PLANS NOT BEING |
| COMPLETE AT THIS TIME, A FULL REVIEW |
| FOR 2002 NEC CODE COMPLIANCE CAN NOT BE |
| DONE. |
| **************************************** |
| *************************************** |
| |
| THE FOLLOWING NOTES ARE ONLY BASED ON |
| WHAT INFORMATION IS AVAIBLAE AT THIS |
| TIME. |
| **************************************** |
| *************************************** |
| |
| 1)NOTE: PLEASE SEE SOME SHEETS HAVE THE |
| ELECTRICAL PRINTED WITH DARKEN LINES |
| AND MANY OF THE SHEETS ARE LT GRAY FOR |
| ELECTRICAL. PLEASE DARKEN FOR EASE OF |
| REVIEW PROCESS. |
| |
| 2)NOTE: PLEASE SUBMIT WIND-LOADING FOR |
| SITE/POLE LIGHTING AT THIS TIME. THIS |
| IS REQUIRED FOR REVIEW AT THIS TIME. |
| WIND LOADS 140MPH PER FBC. |
| |
| 3)NOTE: PLEASE SEE FAC 61G15-23.002, |
| 61G1-16.004 FOR MISSING INFORMATION |
| REQUIRED ON TITLE BLOCKS FOR BOTH |
| ENGIEERING FIRM AND ARCH FIRM. |
| FS 471.023,481.219 |
| PLEASE ALSO SEE PLANS ARE REQUIRED TO |
| BE SIGNED, DATED AND SEALED BY ENGINEER |
| WHEN SUBMITTING FOR PERMIT. |
| |
| 4)NOTE: PLEASE PROVIDE NOTE ON POOL |
| PLANS: POOL TO BE UNDER SEPARATE: |
| PLEASE PROVIDE NOTE FOR HOURS OF |
| SWIMMING. IF AFTER DUSK SWIMMING IS TO |
| TAKE PLACE AND COMPLETE PHOTOMETRICS |
| WILL NEED TO BE SUBMITTED FOR REVIEW |
| AND STAMPING BY THE PALM BEACH COUNTY |
| HEALT DEPT. AND WILL BE REQUIRED TO BE |
| IN THIS PLAN REVIEW. |
| |
| 5)NOTE: PLEASE SEE FPL VAULT ROOM IS |
| ALSO NOTED AS BEING ELECTRICAL ROOM FOR |
| GARAGE. PLEASE SEE FPL VAULT |
| REQUIREMENTS SET FORTH BY FPL AND |
| PERMITTING NO OTHER ELECTRICAL |
| EQUIPMENT |
| IN THEIR VAULT. |
| |
| 6)NOTE: ELECTRICAL PLANS DO NOT CLEARLY |
| SHOW A DIRECT FIRE RATE ACCESS TO MAIN |
| ELECTRICAL RM WHICH APPEARS TO BE |
| LOCATED ABOVE GRADE LEVEL. PLEASE |
| PROVIDE INFORMATION/DIRECTIONAL FOR |
| ACCESS FOR FIRE DEPT PERSONNEL FOR |
| SHUTTING DOWN OF MAINS. PLEASE ALSO |
| PROVIDE NOTE ON PLANS FOR REQUIRED |
| "KNOX BOX" FOR FIRE DEPT. PLEASE SEE |
| FIRE REVIEW NOTES FOR THIS. |
| |
| 7)NOTE: PLEASE SEE MANY AREAS OF PLANS |
| FOR COMMON AREAS/COMMON HALLWAYS ETC DO |
| NOT INDICATE ANY ELECTRICAL FOR |
| LIGHTING, RECEPTS, FIRE DEVICES ETC. |
| PLEASE SUBMIT COMPLETED COMMON AREAS. |
| |
| 8)NOTE: PLEASE SEE 620.23,620.24 FOR |
| REQUIREMENTS IN ELEV RMS/ PITS ETC. |
| |
| 9)NOTE: PLEASE CLARIFY RECEPTS W/IN 20' |
| OF POOL ON ROOF.620.22A3 WHERE A |
| PERMANENTLY INSTALLED POOL IS INSTALLED |
| AT A DWELLING UNIT(S), NO FEWER THAN |
| ONE 125-VOLT 15- OR 20-AMPERE RECEPTACLE |
| ON A GENERAL-PURPOSE BRANCH CIRCUIT |
| SHALL BE LOCATED NOT LESS THAN 3.0 M (10 |
| FT)FROM AND NOT MORE THAN 6.0 M (20 FT) |
| FROM THE INSIDE WALL OF THE POOL. |
| |
| 10)NOTE: PLEASE SEE GENERAL NOTES ON |
| UNIT ELECTRICLA PLANS REFERENCE 1999 |
| NEC. PLEASE SEE AS OF JULY 1ST, 2003, |
| WE ARE UNDER THE 2002 NEC. PLEASE |
| ADJUST |
| NOTES AND PLEASE ALSO ADJUST ALL OTHER |
| SHEETS WHERE CODES ARE REFERENCED. |
| |
| 11)NOTE: PLEASE PROVIDE A COMPLETE |
| FIXTURE SCHEDULE. PLEASE ALSO CORRELATE |
| WITH PLANS. |
| |
| 12)NOTE: PLEASE CLARIFY UNITS, |
| 1,2,3,AND 4. IT APPEARS THERE IS NO |
| ACCESS TO UNITS FROM GARAGE? |
| |
| 13)NOTE: PLEASE SEE 210.70 FOR CONTROL |
| OF EGRESS LIGHTING FOR UNITS W/ ACCESS |
| FROM OUTSIDE WITH WHAT APPEARS TO HAVE |
| NO CONTROL/SWICTHING OF LIGHTING WHEN |
| ENTERING THE UNITS. |
| PLEASE ALSO SEE ANY OTHER GRADE LEVEL |
| ACCESS UNITS WHICH 3-WAY SWITCHING MAY |
| BE REQUIRED. LS-101 5-8 |
| |
| 14)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULES. |
| PLEASE SEE UNITS #6, 17 |
| |
| 15)NOTE: PLEASE SEE SD'S APPEAR TO BE |
| SHOWN ON LITCHEN/BATH LIGHTING |
| CIRCUITS. |
| THIS IS FINE, HOWEVER ARC FAULT |
| PROTECTION WOULD ALSO BE REQUIRED FOR |
| THISE CIRCUITS AND NEED TO BE NOTED ON |
| PANEL SCHEDULES. (NOTE 6) ON PANEL |
| SCHEDULES. |
| PLEASE SEE 2002 NEC 210.12 |
| |
| 16)NOTE: PLEASE SEE SOME UNITS, IN SOME |
| BEDRMS, SD'S ARE MISSING. ( #11) |
| NFPA-72 8-1.4.1.6.2 |
| |
| 17)NOTE: PLEASE SEE 210.52D FOR GFI |
| RECEPTS REQUIRED WITHIN 3' OF THE EDGE |
| OF LAVS. PLEASE SEE AREAS WITH TWO |
| SINKS. GFI MAY BE MOVED TO CENTER OF |
| SINKS OR MAYHAVE AN ADDITIONAL GFI |
| ADDED. |
| |
| 18)NOTE:PLEASE SEE PANEL NOT PERMITTED |
| IN STORAGE/CLOTHES CLOSET. 240.24 |
| OVERCURRENT DEVICES SHALL NOT BE |
| LOCATED IN THE VICINITY OF EASILY |
| IGNITIBLE MATERIAL, SUCH AS IN CLOTHES |
| CLOSETS. |
| PLEASE ALSO SEE 408.7 |
| |
| 19)NOTE:PLEASE SEE SOME UNITS APPEAR TO |
| BE SHOWING TWO PANELS. UNIT VV. |
| |
| 20)NOTE: PLEASE SEE 110.26 FOR MIN |
| CLEARENCE REQUIREMENTS FOR PANELS SHOWN |
| IN SOME UNITS. ONE SHOWN FACING |
| COUNTERSPACE/ DISHWASHER. UNIT M. |
| |
| 21)NOTE: PLEASE SEE 210.70 FOR LT |
| REQUIRED FOR AHU'S IN HALL CLOSETS, |
| PLEASE ALSO SEE 210.63 |
| |
| 22)NOTE: PLEASE SEE 210.52C1-4 |
| PENINSULAR COUNTER SPACES. AT LEAST ONE |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT |
| EACH PENINSULAR COUNTER SPACE WITH A |
| LONG DIMENSION OF 600 MM (24 IN.) OR |
| GREATER AND A SHORT DIMENSION OF 300 MM |
| (12 IN.) OR GREATER. A PENINSULAR |
| COUNTERTOP IS MEASURED FROM THE |
| CONNECTING EDGE.COUNTERTOP SPACES |
| SEPARATED BY RANGE TOPS, REFRIGERATORS, |
| OR SINKS SHALL BE CONSIDERED AS |
| SEPARATE COUNTERTOP SPACES IN APPLYING |
| THE REQUIREMENTS OF 210.52(C)(1), (2), |
| AND (3). UNITS D, G, A ETC. |
| |
| 23)NOTE: PLEASE PLACE NOTE ON PLANS FOR |
| SD LOCATION REQUIREMENTS PER NFPA-72 |
| 8-1.4.2 |
| |
| 24)NOTE: PLEASE VERIFY IF THERE ARE |
| GOING TO BE ANY TERRACE LTS/GFI'S? |
| PLEASE SEE ARCH SHEETS, ELEVATION PLANS |
| SHOWS LTS. PLEASE CORRLELATE. |
| PLEASE ALSO CORRELATE LAYOUT OF TERRACE |
| ON ELECTRICAL PLANS WITH LAYOUT AS |
| SHOWN ON FLR PLANS ON ARCH. |
| |
| 25)NOTE:PLEASE VERIFY IF UNITS WITH |
| JACUZZI/SPA UNITS. PANEL SCHEDULES |
| INDICATE SOME AS FUTURE AND SOME APPEAR |
| TO BE INSTALLED AT THIS TIME, HOWEVER |
| THE FLR LAYOUTS DO NOT INDICATE THIS OR |
| GFI RECEPTS OR GFI BRKRS.680.62A THE |
| OUTLET(S) THAT SUPPLIES A |
| SELF-CONTAINED THERAPEUTIC TUB OR |
| HYDROTHERAPEUTIC TANK, A PACKAGED |
| THERAPEUTIC TUB OR HYDROTHERAPEUTIC |
| TANK, OR A FIELD-ASSEMBLED THERAPEUTIC |
| TUB OR HYDROTHERAPEUTIC TANK SHALL BE |
| PROTECTED BY A GROUND-FAULT CIRCUIT |
| INTERRUPTER. |
| |
| 26)NOTE: PLEASE SEE OCP FOR FIRE PUMP |
| IS TO BE PER LOCKED ROTOR AS NOTED ON |
| RISER. PLEASE SUBMIT ALL INFORMATION |
| FOR FIRE PUMP, FIRE PUMP CONTROLLER. |
| ETC |
| SUBMIT ALL MANUFACT SPECS. |
| PLEASE SPECIFY CODE LTR FOR PUMP. |
| |
| |
| 27)NOTE: PLEASE ALSO SUBMIT ALL |
| MANUFACTURER SPECS FOR GENERATOR, ALL |
| TRANSFER SWITCHES AND FUEL TANK, SHOWING |
| ALL LISTINGS BY THE NRTL. |
| |
| 28)NOTE: PLEASE SEE 110.26 FOR ALL |
| CLEARENCE REQUIREMENTS FOR ELECTRICAL |
| RMS AND CLOSETS. MANY OF THE LAYOUTS |
| SHOWN DO NOT MEET 110.26 FOR CLEARENCE |
| OF EQUIPMENT. |
| PLEASE ALSO SEE 110.26 FOR DOOR SWING, |
| AND REQUIREMENTS FOR PANIC HARDWARE ON |
| DOORS. A NOTE NEEDS TO BE PLACED ON |
| PLANS FOR THIS REQUIREMT. |
| |
| 29)NOTE:PLEASE CORRELATE ELECTRICAL |
| RISER WITH ELECTRICAL EQUIPMENT SHOWN |
| IN |
| ELECTRICAL RMS. PLEASE SEE MISSING |
| "SHE". |
| |
| 30)NOTE: PLEASE CORRELATE "K" NOTES ON |
| RISER WITH THE ACTUAL SCHEDULE OF KEYED |
| NOTES ON PLANS. K-10 ETC. |
| |
| 31)NOTE: PLEASE VERIFY COPPER EQUIPMENT |
| GROUNDING IN BUS-DUCT. PLEASE SEE LOAL |
| AMENDMENTS WHICH DOES NOT PERMIT ALUM |
| FOR GROUNDING OR BONDING.310.2,250.62 |
| |
| 32)NOTE: PLEASE PROVIDE NOTE WHEATHER |
| OR NOT GENERATOR WILL BE SEPARATELY |
| DERIVED OR NOT. IF YES, PLEASE SEE ATS, |
| TO 4-POLE. |
| |
| 33)NOTE: PLEASE SEE RISER FOR ATS SIZES |
| AND OCP FEEDING ATS SWITCHES. PLEASE |
| SEE 900A OCP FEEDING 800A ATS. |
| |
| 34)NOTE: PLEASE COMPLETE RISER DIAGRAM |
| WITH SIZE OF EQUIPMENT SHOWN ON RISER. |
| PLEASE PROVIDE SIZES OF ALL EQUIPMENT , |
| TRANSFORMERS, GROUNDING FOR |
| TRANSFORMERS, KEYED NOTES ON RISER ETC. |
| 215.5,250.30, ETC. |
| PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| EQUIPMENT SHOWN ON SERVICE RISER. |
| PLEASE SEE RISER/NOTES APPEAR TO HAVE |
| 4000A MAINS/OCP FEEDING 3000A BUS-DUCT. |
| MANY OF THESE ITEMS CAN NOT BE VERIFIED |
| AT THIS TIME, DUE TO NONE OFTHIS |
| INFORMATION SUBMITTED. |
| |
| 35)NOTE: PLEASE SUBMIT COMPLETE LOAD |
| CALCULATIONS FOR BUILDING. THE ONLY |
| LOAD CALCS SUBMITTED WERE FOR |
| INDIVIDUAL |
| UNITS AND METER CNTRS. |
| 215.5,220 |
| |
| 36)NOTE: PLEASE VERIFY MANY UNITS ONLY |
| SHOWING A "COOKTOP". ARE THESE RANGES, |
| CONTAINING AN OVEN ALSO? |
| SOME UNITS SHOW SEPARATE COOKTOPS AND |
| OVENS, BUT IT APPEARS UNITS ONLY WITH |
| "COOKTOP" WILL HAVE NO OVENS?? |
| |
| 37)NOTE: PLEASE SEE FEEDERS SCHEDULE |
| SET UP FOR UNITS SHOWN FOR 125A,150A |
| AND |
| 175A ONLY. PLEASE SEE LOADS CALCS/MTR |
| CNTRS SHOW SOME UNITS FED WITH 200A OCP |
| AND 250A OCP. PLEASE SEE MIN CONDUCTORS |
| FOR 250A PER 310.16 |
| |
| 38)NOTE: PLEASE VERIFY SIZE OF PANELS. |
| PANELS ARE SHOWN AS 200A , HOWEVER SOME |
| SHOWN W/ 250A OCP FROM METER CNTRS. |
| |
| 39)NOTE: PLEASE VERIFY OCP FOR SOME |
| WATER HEATERS ( 6KW) MAX OCP 150%, PER |
| 422.11, MIN 125% 422.13.A BRANCH |
| CIRCUIT |
| SUPPLYING A FIXED STORAGE-TYPE WATER |
| HEATER THAT HAS A CAPACITY OF 450 L |
| (120GAL) OR LESS SHALL HAVE A RATING |
| NOT |
| LESS THAN 125 PERCENT OF THE NAMEPLATE |
| RATING OF THE WATER HEATER. |
| |
| PLEASE SEE MANY OF THESE NOTES ARE |
| REDLINED ON ONE SET OF REVIEWED PLANS |
| FOR AREAS OF CONCERN. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| SUBMIT COMPLETED SETS FOR REVIEW. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE ANY |
| AFFECT ON ELECTRICAL PLANS. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |
2005-01-03 00:00:00 | IN ELECTRICAL FOR REVIEW. |
| NOTES TO FOLLOW. |