Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop E
Sequence Number 1
Notes
Date Text
2005-01-06 00:00:00*************** UNSAT *****************
  
 PLAN REVIEW ONLY FOR "TWO CITY PLAZA"
 PLANS NOT SUBMITTED FOR PERMIT AT THIS
 TIME, ONLY IN FOR "PLAN REVIEW".
  
  
 ****************************************
 ***************************************
  
 PLEASE SEE THAT DUE TO PLANS NOT BEING
 COMPLETE AT THIS TIME, A FULL REVIEW
 FOR 2002 NEC CODE COMPLIANCE CAN NOT BE
 DONE.
 ****************************************
 ***************************************
  
 THE FOLLOWING NOTES ARE ONLY BASED ON
 WHAT INFORMATION IS AVAIBLAE AT THIS
 TIME.
 ****************************************
 ***************************************
  
 1)NOTE: PLEASE SEE SOME SHEETS HAVE THE
 ELECTRICAL PRINTED WITH DARKEN LINES
 AND MANY OF THE SHEETS ARE LT GRAY FOR
 ELECTRICAL. PLEASE DARKEN FOR EASE OF
 REVIEW PROCESS.
  
 2)NOTE: PLEASE SUBMIT WIND-LOADING FOR
 SITE/POLE LIGHTING AT THIS TIME. THIS
 IS REQUIRED FOR REVIEW AT THIS TIME.
 WIND LOADS 140MPH PER FBC.
  
 3)NOTE: PLEASE SEE FAC 61G15-23.002,
 61G1-16.004 FOR MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR BOTH
 ENGIEERING FIRM AND ARCH FIRM.
 FS 471.023,481.219
 PLEASE ALSO SEE PLANS ARE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY ENGINEER
 WHEN SUBMITTING FOR PERMIT.
  
 4)NOTE: PLEASE PROVIDE NOTE ON POOL
 PLANS: POOL TO BE UNDER SEPARATE:
 PLEASE PROVIDE NOTE FOR HOURS OF
 SWIMMING. IF AFTER DUSK SWIMMING IS TO
 TAKE PLACE AND COMPLETE PHOTOMETRICS
 WILL NEED TO BE SUBMITTED FOR REVIEW
 AND STAMPING BY THE PALM BEACH COUNTY
 HEALT DEPT. AND WILL BE REQUIRED TO BE
 IN THIS PLAN REVIEW.
  
 5)NOTE: PLEASE SEE FPL VAULT ROOM IS
 ALSO NOTED AS BEING ELECTRICAL ROOM FOR
 GARAGE. PLEASE SEE FPL VAULT
 REQUIREMENTS SET FORTH BY FPL AND
 PERMITTING NO OTHER ELECTRICAL
 EQUIPMENT
 IN THEIR VAULT.
  
 6)NOTE: ELECTRICAL PLANS DO NOT CLEARLY
 SHOW A DIRECT FIRE RATE ACCESS TO MAIN
 ELECTRICAL RM WHICH APPEARS TO BE
 LOCATED ABOVE GRADE LEVEL. PLEASE
 PROVIDE INFORMATION/DIRECTIONAL FOR
 ACCESS FOR FIRE DEPT PERSONNEL FOR
 SHUTTING DOWN OF MAINS. PLEASE ALSO
 PROVIDE NOTE ON PLANS FOR REQUIRED
 "KNOX BOX" FOR FIRE DEPT. PLEASE SEE
 FIRE REVIEW NOTES FOR THIS.
  
 7)NOTE: PLEASE SEE MANY AREAS OF PLANS
 FOR COMMON AREAS/COMMON HALLWAYS ETC DO
 NOT INDICATE ANY ELECTRICAL FOR
 LIGHTING, RECEPTS, FIRE DEVICES ETC.
 PLEASE SUBMIT COMPLETED COMMON AREAS.
  
 8)NOTE: PLEASE SEE 620.23,620.24 FOR
 REQUIREMENTS IN ELEV RMS/ PITS ETC.
  
 9)NOTE: PLEASE CLARIFY RECEPTS W/IN 20'
 OF POOL ON ROOF.620.22A3 WHERE A
 PERMANENTLY INSTALLED POOL IS INSTALLED
 AT A DWELLING UNIT(S), NO FEWER THAN
 ONE 125-VOLT 15- OR 20-AMPERE RECEPTACLE
 ON A GENERAL-PURPOSE BRANCH CIRCUIT
 SHALL BE LOCATED NOT LESS THAN 3.0 M (10
 FT)FROM AND NOT MORE THAN 6.0 M (20 FT)
 FROM THE INSIDE WALL OF THE POOL.
  
 10)NOTE: PLEASE SEE GENERAL NOTES ON
 UNIT ELECTRICLA PLANS REFERENCE 1999
 NEC. PLEASE SEE AS OF JULY 1ST, 2003,
 WE ARE UNDER THE 2002 NEC. PLEASE
 ADJUST
 NOTES AND PLEASE ALSO ADJUST ALL OTHER
 SHEETS WHERE CODES ARE REFERENCED.
  
 11)NOTE: PLEASE PROVIDE A COMPLETE
 FIXTURE SCHEDULE. PLEASE ALSO CORRELATE
 WITH PLANS.
  
 12)NOTE: PLEASE CLARIFY UNITS,
 1,2,3,AND 4. IT APPEARS THERE IS NO
 ACCESS TO UNITS FROM GARAGE?
  
 13)NOTE: PLEASE SEE 210.70 FOR CONTROL
 OF EGRESS LIGHTING FOR UNITS W/ ACCESS
 FROM OUTSIDE WITH WHAT APPEARS TO HAVE
 NO CONTROL/SWICTHING OF LIGHTING WHEN
 ENTERING THE UNITS.
 PLEASE ALSO SEE ANY OTHER GRADE LEVEL
 ACCESS UNITS WHICH 3-WAY SWITCHING MAY
 BE REQUIRED. LS-101 5-8
  
 14)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE UNITS #6, 17
  
 15)NOTE: PLEASE SEE SD'S APPEAR TO BE
 SHOWN ON LITCHEN/BATH LIGHTING
 CIRCUITS.
 THIS IS FINE, HOWEVER ARC FAULT
 PROTECTION WOULD ALSO BE REQUIRED FOR
 THISE CIRCUITS AND NEED TO BE NOTED ON
 PANEL SCHEDULES. (NOTE 6) ON PANEL
 SCHEDULES.
 PLEASE SEE 2002 NEC 210.12
  
 16)NOTE: PLEASE SEE SOME UNITS, IN SOME
 BEDRMS, SD'S ARE MISSING. ( #11)
 NFPA-72 8-1.4.1.6.2
  
 17)NOTE: PLEASE SEE 210.52D FOR GFI
 RECEPTS REQUIRED WITHIN 3' OF THE EDGE
 OF LAVS. PLEASE SEE AREAS WITH TWO
 SINKS. GFI MAY BE MOVED TO CENTER OF
 SINKS OR MAYHAVE AN ADDITIONAL GFI
 ADDED.
  
 18)NOTE:PLEASE SEE PANEL NOT PERMITTED
 IN STORAGE/CLOTHES CLOSET. 240.24
 OVERCURRENT DEVICES SHALL NOT BE
 LOCATED IN THE VICINITY OF EASILY
 IGNITIBLE MATERIAL, SUCH AS IN CLOTHES
 CLOSETS.
 PLEASE ALSO SEE 408.7
  
 19)NOTE:PLEASE SEE SOME UNITS APPEAR TO
 BE SHOWING TWO PANELS. UNIT VV.
  
 20)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCE REQUIREMENTS FOR PANELS SHOWN
 IN SOME UNITS. ONE SHOWN FACING
 COUNTERSPACE/ DISHWASHER. UNIT M.
  
 21)NOTE: PLEASE SEE 210.70 FOR LT
 REQUIRED FOR AHU'S IN HALL CLOSETS,
 PLEASE ALSO SEE 210.63
  
 22)NOTE: PLEASE SEE 210.52C1-4
 PENINSULAR COUNTER SPACES. AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH PENINSULAR COUNTER SPACE WITH A
 LONG DIMENSION OF 600 MM (24 IN.) OR
 GREATER AND A SHORT DIMENSION OF 300 MM
 (12 IN.) OR GREATER. A PENINSULAR
 COUNTERTOP IS MEASURED FROM THE
 CONNECTING EDGE.COUNTERTOP SPACES
 SEPARATED BY RANGE TOPS, REFRIGERATORS,
 OR SINKS SHALL BE CONSIDERED AS
 SEPARATE COUNTERTOP SPACES IN APPLYING
 THE REQUIREMENTS OF 210.52(C)(1), (2),
 AND (3). UNITS D, G, A ETC.
  
 23)NOTE: PLEASE PLACE NOTE ON PLANS FOR
 SD LOCATION REQUIREMENTS PER NFPA-72
 8-1.4.2
  
 24)NOTE: PLEASE VERIFY IF THERE ARE
 GOING TO BE ANY TERRACE LTS/GFI'S?
 PLEASE SEE ARCH SHEETS, ELEVATION PLANS
 SHOWS LTS. PLEASE CORRLELATE.
 PLEASE ALSO CORRELATE LAYOUT OF TERRACE
 ON ELECTRICAL PLANS WITH LAYOUT AS
 SHOWN ON FLR PLANS ON ARCH.
  
 25)NOTE:PLEASE VERIFY IF UNITS WITH
 JACUZZI/SPA UNITS. PANEL SCHEDULES
 INDICATE SOME AS FUTURE AND SOME APPEAR
 TO BE INSTALLED AT THIS TIME, HOWEVER
 THE FLR LAYOUTS DO NOT INDICATE THIS OR
 GFI RECEPTS OR GFI BRKRS.680.62A THE
 OUTLET(S) THAT SUPPLIES A
 SELF-CONTAINED THERAPEUTIC TUB OR
 HYDROTHERAPEUTIC TANK, A PACKAGED
 THERAPEUTIC TUB OR HYDROTHERAPEUTIC
 TANK, OR A FIELD-ASSEMBLED THERAPEUTIC
 TUB OR HYDROTHERAPEUTIC TANK SHALL BE
 PROTECTED BY A GROUND-FAULT CIRCUIT
 INTERRUPTER.
  
 26)NOTE: PLEASE SEE OCP FOR FIRE PUMP
 IS TO BE PER LOCKED ROTOR AS NOTED ON
 RISER. PLEASE SUBMIT ALL INFORMATION
 FOR FIRE PUMP, FIRE PUMP CONTROLLER.
 ETC
 SUBMIT ALL MANUFACT SPECS.
 PLEASE SPECIFY CODE LTR FOR PUMP.
  
  
 27)NOTE: PLEASE ALSO SUBMIT ALL
 MANUFACTURER SPECS FOR GENERATOR, ALL
 TRANSFER SWITCHES AND FUEL TANK, SHOWING
 ALL LISTINGS BY THE NRTL.
  
 28)NOTE: PLEASE SEE 110.26 FOR ALL
 CLEARENCE REQUIREMENTS FOR ELECTRICAL
 RMS AND CLOSETS. MANY OF THE LAYOUTS
 SHOWN DO NOT MEET 110.26 FOR CLEARENCE
 OF EQUIPMENT.
 PLEASE ALSO SEE 110.26 FOR DOOR SWING,
 AND REQUIREMENTS FOR PANIC HARDWARE ON
 DOORS. A NOTE NEEDS TO BE PLACED ON
 PLANS FOR THIS REQUIREMT.
  
 29)NOTE:PLEASE CORRELATE ELECTRICAL
 RISER WITH ELECTRICAL EQUIPMENT SHOWN
 IN
 ELECTRICAL RMS. PLEASE SEE MISSING
 "SHE".
  
 30)NOTE: PLEASE CORRELATE "K" NOTES ON
 RISER WITH THE ACTUAL SCHEDULE OF KEYED
 NOTES ON PLANS. K-10 ETC.
  
 31)NOTE: PLEASE VERIFY COPPER EQUIPMENT
 GROUNDING IN BUS-DUCT. PLEASE SEE LOAL
 AMENDMENTS WHICH DOES NOT PERMIT ALUM
 FOR GROUNDING OR BONDING.310.2,250.62
  
 32)NOTE: PLEASE PROVIDE NOTE WHEATHER
 OR NOT GENERATOR WILL BE SEPARATELY
 DERIVED OR NOT. IF YES, PLEASE SEE ATS,
 TO 4-POLE.
  
 33)NOTE: PLEASE SEE RISER FOR ATS SIZES
 AND OCP FEEDING ATS SWITCHES. PLEASE
 SEE 900A OCP FEEDING 800A ATS.
  
 34)NOTE: PLEASE COMPLETE RISER DIAGRAM
 WITH SIZE OF EQUIPMENT SHOWN ON RISER.
 PLEASE PROVIDE SIZES OF ALL EQUIPMENT ,
 TRANSFORMERS, GROUNDING FOR
 TRANSFORMERS, KEYED NOTES ON RISER ETC.
 215.5,250.30, ETC.
 PLEASE SUBMIT PANEL SCHEDULES FOR ALL
 EQUIPMENT SHOWN ON SERVICE RISER.
 PLEASE SEE RISER/NOTES APPEAR TO HAVE
 4000A MAINS/OCP FEEDING 3000A BUS-DUCT.
 MANY OF THESE ITEMS CAN NOT BE VERIFIED
 AT THIS TIME, DUE TO NONE OFTHIS
 INFORMATION SUBMITTED.
  
 35)NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR BUILDING. THE ONLY
 LOAD CALCS SUBMITTED WERE FOR
 INDIVIDUAL
 UNITS AND METER CNTRS.
 215.5,220
  
 36)NOTE: PLEASE VERIFY MANY UNITS ONLY
 SHOWING A "COOKTOP". ARE THESE RANGES,
 CONTAINING AN OVEN ALSO?
 SOME UNITS SHOW SEPARATE COOKTOPS AND
 OVENS, BUT IT APPEARS UNITS ONLY WITH
 "COOKTOP" WILL HAVE NO OVENS??
  
 37)NOTE: PLEASE SEE FEEDERS SCHEDULE
 SET UP FOR UNITS SHOWN FOR 125A,150A
 AND
 175A ONLY. PLEASE SEE LOADS CALCS/MTR
 CNTRS SHOW SOME UNITS FED WITH 200A OCP
 AND 250A OCP. PLEASE SEE MIN CONDUCTORS
 FOR 250A PER 310.16
  
 38)NOTE: PLEASE VERIFY SIZE OF PANELS.
 PANELS ARE SHOWN AS 200A , HOWEVER SOME
 SHOWN W/ 250A OCP FROM METER CNTRS.
  
 39)NOTE: PLEASE VERIFY OCP FOR SOME
 WATER HEATERS ( 6KW) MAX OCP 150%, PER
 422.11, MIN 125% 422.13.A BRANCH
 CIRCUIT
 SUPPLYING A FIXED STORAGE-TYPE WATER
 HEATER THAT HAS A CAPACITY OF 450 L
 (120GAL) OR LESS SHALL HAVE A RATING
 NOT
 LESS THAN 125 PERCENT OF THE NAMEPLATE
 RATING OF THE WATER HEATER.
  
 PLEASE SEE MANY OF THESE NOTES ARE
 REDLINED ON ONE SET OF REVIEWED PLANS
 FOR AREAS OF CONCERN.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 SUBMIT COMPLETED SETS FOR REVIEW.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE ANY
 AFFECT ON ELECTRICAL PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
2005-01-03 00:00:00IN ELECTRICAL FOR REVIEW.
 NOTES TO FOLLOW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved