Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-20 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) WORKING DRAWING REVIEW ONLY.NO
 PERMIT CAN BE ISSUED UNTIL THE PERMIT
 APPLICATION AND FEES ARE SUBMITTED.
  
 2) FBC* 104.2IT IS NOTED THAT THE
 PLANS ARE NOT COMPLETE AT THIS STAGE.
 WHEN THE PLANS ARE SUBMITTED FOR PERMIT
 THEY SHALL BE COMPLETE AND SIGNED AND
 SEALED BY THE DESIGNERS OF RECORD.
  
 3) IMPACT FEES. IT IS NOTED THAT THE
 PLANS HAVE BEEN SUBMITTED FOR WORKING
 DRAWING REVIEW ONLY.PLEASE NOTE THAT
 BECAUSE THE PERMIT APPLICATION WILL BE
 FILED AFTER DECEMBER 30, 2004, THE FEE
 WILL BE BASED ON THE NEW (HIGHER)
 IMPACT FEE RATES.FOR MORE INFORMATION
 ON PALM BEACH COUNTY IMPACT FEES GO TO:
  
 HTTP://WWW.CO.PALM-BEACH.FL.US/PZB/
 IMPACTFEES/IMPACTFEES.HTM
  
 BEFORE A PERMIT CAN BE ISSUED, THE
 PLANS SHALL BE TAKEN TO PALM BEACH
 COUNTY BUILDING DEPARTMENT FOR IMPACT
 FEE ASSESSMENT. THEY SHALL BE STAMPED
 AT
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT SUBMITTED TO THE CITY OF WEST
 PALM BEACH DEPT OF CONSTRUCTION
 SERVICES
  
 4) NOTE THAT THE NOTICE OF
 COMMENCEMENT, IMPACT FEE RECEIPT AND
 SPECIAL INSPECTOR AGREEMENT WILL BE
 REQUIRED BEFORE A PERMIT CAN BE ISSUED.
 ALSO A DECLARATION OF CONDOMINIUM WILL
 BE REQUIRED BEFORE CERTIFICATE OF
 OCCUPANCY.
  
 5) FBC* 104.2.4SITE SURVEY.A SIGNED
 AND SEALED SURVEY DRAWING PREPARED BY A
 LICENSED SURVEYOR/MAPPER IS REQUIRED.
 (REF: 472.025(1) FL. STATUTES).UNITY
 OF TITLE AND HORIZONTAL SEPARATION
 REQUIREMENTS CANNOT BE ASSESSED WITHOUT
 A SITE SURVEY.
  
 6) A SEPARATE PERMIT APPLICATION WILL
 BE REQUIRED FOR THE SWIMMING POOL AND
 SPA.
  
 7) FBC* 105.13.1SPECIAL INSPECTOR
 AGREEMENT.BEFORE A PERMIT CAN BE
 ISSUED IT WILL BE NECESSARY TO ARRANGE,
 WITH HAROLD PISKURA (INSPECTION
 SERVICES
 MANAGER - TEL: 561 805 6711), A MEETING
 INVOLVING THE OWNER, THRESHOLD
 INSPECTOR, JOB INSPECTOR, CONTRACTOR
 AND ENGINEER.
  
 8) FBC* 1804.2.2SHEET S-0, GENERAL
 NOTES - FOUNDATIONS.SUBMIT THREE
 COPIES OF ARDAMAN & ASSOCIATES SOIL
 REPORT DATED 7/28/04 AS REFERENCED
 UNDER THE 'FOUNDATION' NOTE.
  
 9) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE CODE COMPLIANCE FORMS
  
 10) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, STOREFRONTS, EXTERIOR DOORS
 AND ROOFING PRODUCTS.
  
 11) FBC TABLE 600SHEET A1.01, FIRE
 RESISTANCE OF STRUCTURAL ELEMENTS.IT
 IS NOTED THAT THE INDEX OF DRAWINGS
 REFERS TO SHEETS LS0.00 - CODE DATA AND
 LS1.00 - SITE PLAN & LIFE SAFETY NOTES
 AND THESE SHEETS WERE NOT SUBMITTED.
 THE REQUIRED FIRE RESISTANCE RATINGS OF
 STRUCTURAL ELEMENTS (WALLS, COLUMNS,
 BEAMS, FLOORS ETC) FOR A TYPE I
 BUILDING ARE NOT STATED ON THE PLANS
 AND
 SHOULD BE ADDED TO ONE OF THE
 ARCHITECTURAL SHEETS OR STRUCTURAL
 NOTES
 SHEET S-0.0
  
 12) FBC TABLE 600SHEET LS1.01,
 HORIZONTAL SEPARATION.THE GENERAL
 NOTES AND THE BUILDING ELEVATION SHEETS
 A3.01 TO A3.04 DO NOT STATE WHETHER THE
 AREA OF WALL OPENINGS EXCEEDS 40% OF
 THE WALL AREA.ADD A TABLE OR NOTES TO
 SHOW THAT THE AREA OF WALL OPENINGS
 DOES
 NOT EXCEED THAT ALLOWED BY THE PROVIDED
 HORIZONTAL SEPARATION.SEE THE ABOVE
 COMMENT REQUIRING A SURVEY DRAWING.
  
 13) FBC 707.1 SHEET S A9.02 AND A9.12,
 COMBUSTIBLES IN CONCEALED SPACES.IN
 TYPE I CONSTRUCTION., ALL WOOD BUCKS,
 HEADERS, FURRING STRIPS ETC SHALL BE
 APPROVED FIRE RETARDANT TREATED LUMBER.
 NOTE 1 ON SHEETA9.13 REFERS TO WOOD
 BACKING, BLOCKING ETC FOR THE
 INSTALLATION OF FINISHES.
 AMEND/ANNOTATE SHEETS A9.02 AND A9.12
 TO DEMONSTRATE COMPLIANCE.
  
 14) FBC 704.2.4SHEET LS1.01, EXIT
 ACCESS CORRIDORS.THE CROSS-CORRIDOR
 WALL LINKING THE MAIL ROOM TO ELEVATOR
 VESTIBULE #3, AND THE MECHANICAL ROOM
 TO THE CONFERENCE ROOM, AND THE WALLS
 SEPERATING THE CORRIDOR FROM THE
 JANITOR?S, MECHANICAL AND CONFERENCE
 ROOM ARE NOT SHOWN AS FIRE-RATED.IT
 IS NOTED THAT THE DOORS IN THESE WALLS
 ARE ALREADY SPECIFIED AS FIRE-RATED ON
 SHEET A9.11, DOOR SCHEDULE.
  
 15) FBC 701.1.1SHEET LS1.01,
 EMERGENCY GENERATOR ROOM.NO FIRE
 SEPARATION IS CURRENTLY SHOWN BETWEEN
 THE GENERATOR ROOM AND THE ADJACENT
 ENTRY/EXIT. AMEND THE PLAN.
  
 16) FBC 701.1.1SHEET LS1.01,WASTE
 CONTAINER TOWING EQUIPMENT AREA.THE
 REQUIRED 2 HOUR FIRE SEPARATION IS NOT
 SHOWN BETWEEN THIS STORAGE ROOM AND THE
 PARKING GARAGE.AMEND THE PLAN.ALSO,
 SHEET A4.11 DOES NOT SHOW ANY DOOR
 SCHEDULE REFERENCE FOR THE DOOR IN
 ORDER TO VERIFY THE DOOR FIRE RATING.
  
 17) FBC 701.1.1SHEETS LS1.01 AND
 LS1.02,BUILDING STORAGE ROOM.THE
 REQUIRED 2 HOUR FIRE SEPARATION IS NOT
 SHOWN FOR THE WALL BETWEEN THE PARKING
 GARAGE AND THE BUILDING STORAGE ROOM AT
 THE WEST END OF THE PARKING GARAGE.
 AMEND THE PLAN
  
 18) FBC 704.1.3.2SHEETS LS1.04,
 LS1.05 AND LS1.06, TENANT STORAGE
 ROOMS.
 THESE ARE REQUIRED TO HAVE 2 HOUR FIRE
 SEPARATION FROM THE PARKING GARAGE.
 FBC 704.1.2.2 DOES NOT APPLY HERE AS
 THE
 STORAGE ROOMS ARE ACCESSORY TO THE
 RESIDENTIAL OCCUPANCY NOT THE PARKING
 GARAGE.
  
 19) FBC 704.2.4SHEET LS1.04, WALL
 BETWEEN TENANT STORAGE ROOM AND PUBLIC
 CORRIDOR.THE NOTE ON THE PLAN REFERS
 TO FBC 704.1.2.2 EXCEPTION NO.4 AS
 JUSTIFICATION FOR NOT FIRE-RATING THIS
 WALL.THAT SECTION IS NOT APPLICABLE
 IN THIS CASE BECAUSE THE CORRIDOR IS AN
 EXIT ACCESS CORRIDOR AND IS REQUIRED TO
 BE FIRE RATED.AMEND THE PLAN.
  
 20) FBC* 104.2.1SHEETS A2.02, A2.05,
 A2.07 AND A2.09.ADD NOTES TO THESE
 SHEETS TO CLARIFY THAT THE UNLABELLED
 SPACE AROUND THE PARKING GARAGE IS
 ACTUALLY OCCUPIED BY 'RESIDENTIAL UNIT
 BELOW' AND 'CORRIDOR BELOW'.THE NOTES
 SHOULD STATE THAT THE REQUIRED
 FIRE-RATING FOR THE WALLS IS STATED ON
 THE PLAN FOR THE FLOOR BELOW.
  
 21) FBC* F102.2.7SHEETS A3.01 TO
 A3.06 ELEVATIONS.THE KEY NOTES REFER
 TO 'F11'-FOAM COLUMN AND 'A'-MOULDING
 TYPES SEE SHEETS A??.ARCHITECTURAL
 TRIM, ON BUILDINGS LOCATED IN THE FIRE
 DISTRICT, SHALL BE CONSTRUCTED OF
 APPROVED NON-COMBUSTIBLE MATERIALS OR
 FIRE RETARDANT TREATED WOOD.ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 22) FBC 1012.1.2SHEET A2.16, EXIT
 DOOR LEADING TO STAIR #2.THIS DOOR
 SHALL OPEN IN THE DIRECTION OF EGRESS.
 AMEND THE PLAN.
  
 23) FBC 1012.1.4SHEET A7.12,STAIR
 #6.DURING ITS SWING, THE EXIT DOOR AT
 LEVELS P2 TO P9 SHALL LEAVE AT LEAST
 HALF OF THE REQUIRED STAIR WIDTH
 UNOBSTRUCTED.AMEND/ANNOTATE THE PLAN
 WITH DIMENSIONS TO DEMONSTRATE
 COMPLIANCE.
  
 24) FBC 1015.3SHEET A9.21, DETAIL 10,
 TYPICAL BALCONY GUARDRAIL.THE
 ORNAMENTAL PATTERN SHALL BE SUCH THAT A
 4? DIAMETER SPHERE CANNOT PASS THROUGH
 ANY OPENING UP TO A HEIGHT OF 34?.A
 BOTTOM RAIL OR CURB SHALL BE PROVIDED
 TO REJECT THE PASSAGE OF A 2? DIAMETER
 SPHERE.AMEND THE PLANS TO DEMONSTRATE
 COMPLIANCE.THE NOTE ON SHEET A10.02,
 DETAIL 1 IS FOR A DIFFERENT
 SITUATION/LOCATION.
  
 25) NFPA 823-2.4.3.1SHEET A7.14,
 TRASH CHUTE SERVICE OPENING ROOM.
 THERE SHALL BE MINIMUM 6" CLEARANCE
 BETWEEN THE OPEN CHUTE LOADING DOOR AND
 CLOSED SERVICE OPENING ROOM DOOR.
 AMEND
 THE PLANS.
  
 26)FBC 11-4.9.4SHEETS A7.05 AND
 A7.05A, STAIR #2.THE REQUIRED
 HANDRAIL EXTENSION LENGTHS AT THE TOP
 AND BOTTOM OF EACH FLIGHT ARE
 TRANSPOSED
 (TOP=BOTTOM, BOTTOM=TOP) AT 6TH LEVEL,
 7-14TH LEVEL, 15TH LEVEL AND 16TH
 LEVEL.
 AMEND THE PLANS.
  
 27) FBC 11-4.13.6SHEET A4.42,
 MANEUVERING CLEARANCES AT DOORS.IT IS
 NOTED THAT THIS SHEET IS NOT COMPLETE.
 THE DOORS PENCILED IN AS DOORP24 (TO
 THERAPY ROOM) SHALL HAVE A MIN. 18?
 CLEARANCE BETWEEN THE STRIKE EDGE OF
 THE DOOR AND THE ADJACENT PERPENDICULAR
 WALL.AMEND/ANNOTATE THE PLANS WITH
 DIMENSIONS TO DEMONSTRATE COMPLIANCE.
 THE SAME ALSO APPLIES TO DOOR REFERENCE
 S14, SHOWN ON SHEET A4.02.
  
 28) FBC 411.2.3SHEET A2.02, A2.05,
 A2.07 AND A2.09, VEHICLE IMPACT
 WALLS/GUARDRAILS.AMEND THE PLANS TO
 SHOW THE REQUIRED IMPACT
 WALLS/GUARDRAILS AT THE PERIMETER WALLS
 OF THE PARKING GARAGE.THIS ALSO
 APPLIES TO THE WALL, SHOWN ON SHEET
 A2.02, BETWEEN THE PARKING GARAGE AND
 THE VOID ABOVE THE NORTH PARKING GARAGE
 ENTRY/EXIT, AND TO THE NORTH PORTION OF
 THE WEST WALL AT ALL PARKING GARAGE
 LEVELS ABOVE GROUND.IMPACT GUARDRAILS
 ARE ALSO REQUIRED IN FRONT OF THE
 GARAGE EXHAUST AIR SHAFT LOUVERS AT THE
 WEST END OF EACH PARKING GARAGE LEVEL
 ABOVE GROUND.AMEND THE PLANS.
  
 29) FBC 1608.2.2SHEET A8.21, DETAILS
 A AND A1 AND SHEET A9.21, DETAIL 10.
 THE GUARDRAIL SHALL BE DESIGNED
 AND CONSTRUCTED FOR A CONCENTRATED LOAD
 OF 200 LB APPLIED IN ANY DIRECTION AT
 THE TOP OF THE GUARDRAIL, A
 CONCENTRATED HORIZONTAL LOAD OF 200 LB
 APPLIED ON A 1 SQ FT AREA AT ANY POINT,
 AND A LINE LOAD OF 50 PLF APPLIED
 HORIZONTALLY AT THE REQUIRED GUARDRAIL
 HEIGHT WITH A SIMULTANEOUS LINE LOAD OF
 100 PLF APPLIED VERTICALLY DOWNWARD ON
 THE TOP OF THE GUARDRAIL. THESE LOADS
 SHALL NOT BE APPLIED SIMULTANEOUSLY
 (UNLESS NOTED ABOVE) BUT SHALL BE
 APPLIED INDIVIDUALLY TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE COMPONENTS OR
 SUPPORTS.AMEND/ANNOTATE THE PLANS.
  
 30) FBC* 104.2.1THE SUBMITTED
 STRUCTURAL PLAN SET DOES INCLUDE A
 GROUND FLOOR REINFORCING PLAN AND THE
 HIGH ROOF REINFORCING PLAN IS NOT
 COMPLETE. SUBMIT COMPLETE PLANS FOR
 REVIEW.
  
 31) FBC 3502SHEET S-0.0, GENERAL
 NOTES THE PLANS REFERENCE ACI 530.1-99
 AND ACI 318-99 (TWICE) UNDER THE
 SUB-TITLES 'CODES' AND 'THRESHOLD
 BUILDING INSPECTION PLAN'.THE
 VERSIONS
 OF THESE STANDARDS REFERENCED BY
 FLORIDA
 BUILDING CODE ARE ACI 530.1-02 AND ACI
 318-02. AMEND THE GENERAL NOTES.
  
 32) FBC 3502SHEET S-0.0, GENERAL
 NOTES THE PLANS REFERENCE ASTM A 185-85
 AND ASTM A 615-84A (TWICE) UNDER THE
 SUB-TITLES 'WELDED WIRE FABRIC' AND
 'REINFORCING STEEL'.THE VERSIONS OF
 THESE STANDARDS REFERENCED BY FLORIDA
 BUILDING CODE ARE ASTM A 185-97 AND
 ASTM A 615-94.AMEND THE GENERAL
 NOTES.
  
 33) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE
 RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS