2005-01-20 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) WORKING DRAWING REVIEW ONLY.NO |
| PERMIT CAN BE ISSUED UNTIL THE PERMIT |
| APPLICATION AND FEES ARE SUBMITTED. |
| |
| 2) FBC* 104.2IT IS NOTED THAT THE |
| PLANS ARE NOT COMPLETE AT THIS STAGE. |
| WHEN THE PLANS ARE SUBMITTED FOR PERMIT |
| THEY SHALL BE COMPLETE AND SIGNED AND |
| SEALED BY THE DESIGNERS OF RECORD. |
| |
| 3) IMPACT FEES. IT IS NOTED THAT THE |
| PLANS HAVE BEEN SUBMITTED FOR WORKING |
| DRAWING REVIEW ONLY.PLEASE NOTE THAT |
| BECAUSE THE PERMIT APPLICATION WILL BE |
| FILED AFTER DECEMBER 30, 2004, THE FEE |
| WILL BE BASED ON THE NEW (HIGHER) |
| IMPACT FEE RATES.FOR MORE INFORMATION |
| ON PALM BEACH COUNTY IMPACT FEES GO TO: |
| |
| HTTP://WWW.CO.PALM-BEACH.FL.US/PZB/ |
| IMPACTFEES/IMPACTFEES.HTM |
| |
| BEFORE A PERMIT CAN BE ISSUED, THE |
| PLANS SHALL BE TAKEN TO PALM BEACH |
| COUNTY BUILDING DEPARTMENT FOR IMPACT |
| FEE ASSESSMENT. THEY SHALL BE STAMPED |
| AT |
| THAT OFFICE AND A COPY OF THE PAID |
| RECEIPT SUBMITTED TO THE CITY OF WEST |
| PALM BEACH DEPT OF CONSTRUCTION |
| SERVICES |
| |
| 4) NOTE THAT THE NOTICE OF |
| COMMENCEMENT, IMPACT FEE RECEIPT AND |
| SPECIAL INSPECTOR AGREEMENT WILL BE |
| REQUIRED BEFORE A PERMIT CAN BE ISSUED. |
| ALSO A DECLARATION OF CONDOMINIUM WILL |
| BE REQUIRED BEFORE CERTIFICATE OF |
| OCCUPANCY. |
| |
| 5) FBC* 104.2.4SITE SURVEY.A SIGNED |
| AND SEALED SURVEY DRAWING PREPARED BY A |
| LICENSED SURVEYOR/MAPPER IS REQUIRED. |
| (REF: 472.025(1) FL. STATUTES).UNITY |
| OF TITLE AND HORIZONTAL SEPARATION |
| REQUIREMENTS CANNOT BE ASSESSED WITHOUT |
| A SITE SURVEY. |
| |
| 6) A SEPARATE PERMIT APPLICATION WILL |
| BE REQUIRED FOR THE SWIMMING POOL AND |
| SPA. |
| |
| 7) FBC* 105.13.1SPECIAL INSPECTOR |
| AGREEMENT.BEFORE A PERMIT CAN BE |
| ISSUED IT WILL BE NECESSARY TO ARRANGE, |
| WITH HAROLD PISKURA (INSPECTION |
| SERVICES |
| MANAGER - TEL: 561 805 6711), A MEETING |
| INVOLVING THE OWNER, THRESHOLD |
| INSPECTOR, JOB INSPECTOR, CONTRACTOR |
| AND ENGINEER. |
| |
| 8) FBC* 1804.2.2SHEET S-0, GENERAL |
| NOTES - FOUNDATIONS.SUBMIT THREE |
| COPIES OF ARDAMAN & ASSOCIATES SOIL |
| REPORT DATED 7/28/04 AS REFERENCED |
| UNDER THE 'FOUNDATION' NOTE. |
| |
| 9) FBC 13-103.0ENERGY CODE COMPLIANCE |
| SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| APPROPRIATE CODE COMPLIANCE FORMS |
| |
| 10) SUBMIT PRODUCT APPROVALS FOR THE |
| WINDOWS, STOREFRONTS, EXTERIOR DOORS |
| AND ROOFING PRODUCTS. |
| |
| 11) FBC TABLE 600SHEET A1.01, FIRE |
| RESISTANCE OF STRUCTURAL ELEMENTS.IT |
| IS NOTED THAT THE INDEX OF DRAWINGS |
| REFERS TO SHEETS LS0.00 - CODE DATA AND |
| LS1.00 - SITE PLAN & LIFE SAFETY NOTES |
| AND THESE SHEETS WERE NOT SUBMITTED. |
| THE REQUIRED FIRE RESISTANCE RATINGS OF |
| STRUCTURAL ELEMENTS (WALLS, COLUMNS, |
| BEAMS, FLOORS ETC) FOR A TYPE I |
| BUILDING ARE NOT STATED ON THE PLANS |
| AND |
| SHOULD BE ADDED TO ONE OF THE |
| ARCHITECTURAL SHEETS OR STRUCTURAL |
| NOTES |
| SHEET S-0.0 |
| |
| 12) FBC TABLE 600SHEET LS1.01, |
| HORIZONTAL SEPARATION.THE GENERAL |
| NOTES AND THE BUILDING ELEVATION SHEETS |
| A3.01 TO A3.04 DO NOT STATE WHETHER THE |
| AREA OF WALL OPENINGS EXCEEDS 40% OF |
| THE WALL AREA.ADD A TABLE OR NOTES TO |
| SHOW THAT THE AREA OF WALL OPENINGS |
| DOES |
| NOT EXCEED THAT ALLOWED BY THE PROVIDED |
| HORIZONTAL SEPARATION.SEE THE ABOVE |
| COMMENT REQUIRING A SURVEY DRAWING. |
| |
| 13) FBC 707.1 SHEET S A9.02 AND A9.12, |
| COMBUSTIBLES IN CONCEALED SPACES.IN |
| TYPE I CONSTRUCTION., ALL WOOD BUCKS, |
| HEADERS, FURRING STRIPS ETC SHALL BE |
| APPROVED FIRE RETARDANT TREATED LUMBER. |
| NOTE 1 ON SHEETA9.13 REFERS TO WOOD |
| BACKING, BLOCKING ETC FOR THE |
| INSTALLATION OF FINISHES. |
| AMEND/ANNOTATE SHEETS A9.02 AND A9.12 |
| TO DEMONSTRATE COMPLIANCE. |
| |
| 14) FBC 704.2.4SHEET LS1.01, EXIT |
| ACCESS CORRIDORS.THE CROSS-CORRIDOR |
| WALL LINKING THE MAIL ROOM TO ELEVATOR |
| VESTIBULE #3, AND THE MECHANICAL ROOM |
| TO THE CONFERENCE ROOM, AND THE WALLS |
| SEPERATING THE CORRIDOR FROM THE |
| JANITOR?S, MECHANICAL AND CONFERENCE |
| ROOM ARE NOT SHOWN AS FIRE-RATED.IT |
| IS NOTED THAT THE DOORS IN THESE WALLS |
| ARE ALREADY SPECIFIED AS FIRE-RATED ON |
| SHEET A9.11, DOOR SCHEDULE. |
| |
| 15) FBC 701.1.1SHEET LS1.01, |
| EMERGENCY GENERATOR ROOM.NO FIRE |
| SEPARATION IS CURRENTLY SHOWN BETWEEN |
| THE GENERATOR ROOM AND THE ADJACENT |
| ENTRY/EXIT. AMEND THE PLAN. |
| |
| 16) FBC 701.1.1SHEET LS1.01,WASTE |
| CONTAINER TOWING EQUIPMENT AREA.THE |
| REQUIRED 2 HOUR FIRE SEPARATION IS NOT |
| SHOWN BETWEEN THIS STORAGE ROOM AND THE |
| PARKING GARAGE.AMEND THE PLAN.ALSO, |
| SHEET A4.11 DOES NOT SHOW ANY DOOR |
| SCHEDULE REFERENCE FOR THE DOOR IN |
| ORDER TO VERIFY THE DOOR FIRE RATING. |
| |
| 17) FBC 701.1.1SHEETS LS1.01 AND |
| LS1.02,BUILDING STORAGE ROOM.THE |
| REQUIRED 2 HOUR FIRE SEPARATION IS NOT |
| SHOWN FOR THE WALL BETWEEN THE PARKING |
| GARAGE AND THE BUILDING STORAGE ROOM AT |
| THE WEST END OF THE PARKING GARAGE. |
| AMEND THE PLAN |
| |
| 18) FBC 704.1.3.2SHEETS LS1.04, |
| LS1.05 AND LS1.06, TENANT STORAGE |
| ROOMS. |
| THESE ARE REQUIRED TO HAVE 2 HOUR FIRE |
| SEPARATION FROM THE PARKING GARAGE. |
| FBC 704.1.2.2 DOES NOT APPLY HERE AS |
| THE |
| STORAGE ROOMS ARE ACCESSORY TO THE |
| RESIDENTIAL OCCUPANCY NOT THE PARKING |
| GARAGE. |
| |
| 19) FBC 704.2.4SHEET LS1.04, WALL |
| BETWEEN TENANT STORAGE ROOM AND PUBLIC |
| CORRIDOR.THE NOTE ON THE PLAN REFERS |
| TO FBC 704.1.2.2 EXCEPTION NO.4 AS |
| JUSTIFICATION FOR NOT FIRE-RATING THIS |
| WALL.THAT SECTION IS NOT APPLICABLE |
| IN THIS CASE BECAUSE THE CORRIDOR IS AN |
| EXIT ACCESS CORRIDOR AND IS REQUIRED TO |
| BE FIRE RATED.AMEND THE PLAN. |
| |
| 20) FBC* 104.2.1SHEETS A2.02, A2.05, |
| A2.07 AND A2.09.ADD NOTES TO THESE |
| SHEETS TO CLARIFY THAT THE UNLABELLED |
| SPACE AROUND THE PARKING GARAGE IS |
| ACTUALLY OCCUPIED BY 'RESIDENTIAL UNIT |
| BELOW' AND 'CORRIDOR BELOW'.THE NOTES |
| SHOULD STATE THAT THE REQUIRED |
| FIRE-RATING FOR THE WALLS IS STATED ON |
| THE PLAN FOR THE FLOOR BELOW. |
| |
| 21) FBC* F102.2.7SHEETS A3.01 TO |
| A3.06 ELEVATIONS.THE KEY NOTES REFER |
| TO 'F11'-FOAM COLUMN AND 'A'-MOULDING |
| TYPES SEE SHEETS A??.ARCHITECTURAL |
| TRIM, ON BUILDINGS LOCATED IN THE FIRE |
| DISTRICT, SHALL BE CONSTRUCTED OF |
| APPROVED NON-COMBUSTIBLE MATERIALS OR |
| FIRE RETARDANT TREATED WOOD.ANNOTATE |
| THE PLANS TO DEMONSTRATE COMPLIANCE. |
| |
| 22) FBC 1012.1.2SHEET A2.16, EXIT |
| DOOR LEADING TO STAIR #2.THIS DOOR |
| SHALL OPEN IN THE DIRECTION OF EGRESS. |
| AMEND THE PLAN. |
| |
| 23) FBC 1012.1.4SHEET A7.12,STAIR |
| #6.DURING ITS SWING, THE EXIT DOOR AT |
| LEVELS P2 TO P9 SHALL LEAVE AT LEAST |
| HALF OF THE REQUIRED STAIR WIDTH |
| UNOBSTRUCTED.AMEND/ANNOTATE THE PLAN |
| WITH DIMENSIONS TO DEMONSTRATE |
| COMPLIANCE. |
| |
| 24) FBC 1015.3SHEET A9.21, DETAIL 10, |
| TYPICAL BALCONY GUARDRAIL.THE |
| ORNAMENTAL PATTERN SHALL BE SUCH THAT A |
| 4? DIAMETER SPHERE CANNOT PASS THROUGH |
| ANY OPENING UP TO A HEIGHT OF 34?.A |
| BOTTOM RAIL OR CURB SHALL BE PROVIDED |
| TO REJECT THE PASSAGE OF A 2? DIAMETER |
| SPHERE.AMEND THE PLANS TO DEMONSTRATE |
| COMPLIANCE.THE NOTE ON SHEET A10.02, |
| DETAIL 1 IS FOR A DIFFERENT |
| SITUATION/LOCATION. |
| |
| 25) NFPA 823-2.4.3.1SHEET A7.14, |
| TRASH CHUTE SERVICE OPENING ROOM. |
| THERE SHALL BE MINIMUM 6" CLEARANCE |
| BETWEEN THE OPEN CHUTE LOADING DOOR AND |
| CLOSED SERVICE OPENING ROOM DOOR. |
| AMEND |
| THE PLANS. |
| |
| 26)FBC 11-4.9.4SHEETS A7.05 AND |
| A7.05A, STAIR #2.THE REQUIRED |
| HANDRAIL EXTENSION LENGTHS AT THE TOP |
| AND BOTTOM OF EACH FLIGHT ARE |
| TRANSPOSED |
| (TOP=BOTTOM, BOTTOM=TOP) AT 6TH LEVEL, |
| 7-14TH LEVEL, 15TH LEVEL AND 16TH |
| LEVEL. |
| AMEND THE PLANS. |
| |
| 27) FBC 11-4.13.6SHEET A4.42, |
| MANEUVERING CLEARANCES AT DOORS.IT IS |
| NOTED THAT THIS SHEET IS NOT COMPLETE. |
| THE DOORS PENCILED IN AS DOORP24 (TO |
| THERAPY ROOM) SHALL HAVE A MIN. 18? |
| CLEARANCE BETWEEN THE STRIKE EDGE OF |
| THE DOOR AND THE ADJACENT PERPENDICULAR |
| WALL.AMEND/ANNOTATE THE PLANS WITH |
| DIMENSIONS TO DEMONSTRATE COMPLIANCE. |
| THE SAME ALSO APPLIES TO DOOR REFERENCE |
| S14, SHOWN ON SHEET A4.02. |
| |
| 28) FBC 411.2.3SHEET A2.02, A2.05, |
| A2.07 AND A2.09, VEHICLE IMPACT |
| WALLS/GUARDRAILS.AMEND THE PLANS TO |
| SHOW THE REQUIRED IMPACT |
| WALLS/GUARDRAILS AT THE PERIMETER WALLS |
| OF THE PARKING GARAGE.THIS ALSO |
| APPLIES TO THE WALL, SHOWN ON SHEET |
| A2.02, BETWEEN THE PARKING GARAGE AND |
| THE VOID ABOVE THE NORTH PARKING GARAGE |
| ENTRY/EXIT, AND TO THE NORTH PORTION OF |
| THE WEST WALL AT ALL PARKING GARAGE |
| LEVELS ABOVE GROUND.IMPACT GUARDRAILS |
| ARE ALSO REQUIRED IN FRONT OF THE |
| GARAGE EXHAUST AIR SHAFT LOUVERS AT THE |
| WEST END OF EACH PARKING GARAGE LEVEL |
| ABOVE GROUND.AMEND THE PLANS. |
| |
| 29) FBC 1608.2.2SHEET A8.21, DETAILS |
| A AND A1 AND SHEET A9.21, DETAIL 10. |
| THE GUARDRAIL SHALL BE DESIGNED |
| AND CONSTRUCTED FOR A CONCENTRATED LOAD |
| OF 200 LB APPLIED IN ANY DIRECTION AT |
| THE TOP OF THE GUARDRAIL, A |
| CONCENTRATED HORIZONTAL LOAD OF 200 LB |
| APPLIED ON A 1 SQ FT AREA AT ANY POINT, |
| AND A LINE LOAD OF 50 PLF APPLIED |
| HORIZONTALLY AT THE REQUIRED GUARDRAIL |
| HEIGHT WITH A SIMULTANEOUS LINE LOAD OF |
| 100 PLF APPLIED VERTICALLY DOWNWARD ON |
| THE TOP OF THE GUARDRAIL. THESE LOADS |
| SHALL NOT BE APPLIED SIMULTANEOUSLY |
| (UNLESS NOTED ABOVE) BUT SHALL BE |
| APPLIED INDIVIDUALLY TO PRODUCE MAXIMUM |
| STRESS IN EACH OF THE COMPONENTS OR |
| SUPPORTS.AMEND/ANNOTATE THE PLANS. |
| |
| 30) FBC* 104.2.1THE SUBMITTED |
| STRUCTURAL PLAN SET DOES INCLUDE A |
| GROUND FLOOR REINFORCING PLAN AND THE |
| HIGH ROOF REINFORCING PLAN IS NOT |
| COMPLETE. SUBMIT COMPLETE PLANS FOR |
| REVIEW. |
| |
| 31) FBC 3502SHEET S-0.0, GENERAL |
| NOTES THE PLANS REFERENCE ACI 530.1-99 |
| AND ACI 318-99 (TWICE) UNDER THE |
| SUB-TITLES 'CODES' AND 'THRESHOLD |
| BUILDING INSPECTION PLAN'.THE |
| VERSIONS |
| OF THESE STANDARDS REFERENCED BY |
| FLORIDA |
| BUILDING CODE ARE ACI 530.1-02 AND ACI |
| 318-02. AMEND THE GENERAL NOTES. |
| |
| 32) FBC 3502SHEET S-0.0, GENERAL |
| NOTES THE PLANS REFERENCE ASTM A 185-85 |
| AND ASTM A 615-84A (TWICE) UNDER THE |
| SUB-TITLES 'WELDED WIRE FABRIC' AND |
| 'REINFORCING STEEL'.THE VERSIONS OF |
| THESE STANDARDS REFERENCED BY FLORIDA |
| BUILDING CODE ARE ASTM A 185-97 AND |
| ASTM A 615-94.AMEND THE GENERAL |
| NOTES. |
| |
| 33) TO EXPEDITE REVIEW OF A RESUBMITTAL |
| WHICH REQUIRES NEW PLANS IN ORDER TO |
| ADDRESS THE ABOVE COMMENTS, THE OLD |
| SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHOULD BE STAPLED/CLIPPED TO THE |
| REMAINING OLD SHEETS, TO FORM A SET OF |
| 'OLD/VOID SHEETS', FOR COMPARISON OF |
| REVISIONS WHEN REVIEWING THE |
| RESUBMITTED |
| PLANS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |
| THE CODE REFERENCES GIVE ADDITIONAL |
| INFO |
| TELEPHONE: (561) 805 6716ROBERT |
| BROWN |
| E-MAIL: [email protected] |