Notes |
Date |
Text |
2005-12-09 00:00:00 | PAUL SCHMITZ | | FBC2001 FUEL GAS CODEPLAN REVIEW | | FBC 2001 PLUMBING CODEPLAN REVIEW | | FBC 2001 FL ACESSIBILITY CODE PLAN | | REVIEW | | DENIED | | PREVIOUS NOTES DATED 10-01-05 NOT | | ADDRESSED. | | | | 4)SHT A-1 WATER RISER, CLARFY USE OF | | WATER HAMMER ARESSTORS OR AIR CHAMBERS. | | REMOVE AIR CHAMBERS FROM DETAIL OR | | PROVIDE DETAILPER STD PDI-WH 201 FOR | | PROPER INSTALLATION. | | SHUT OFF VALVES REQUIRED ON EACH DROP, | | NOT AS SHOWN IN THE MAINS. | | 2)SHT A-3 GAS LOAD CALCULATIONS: | | CHANGE CODE REFERENCE FROM 1999 EDITION | | TO 2001 EDITION. | | EXPLAIN THE PURPOSE OF THE VENT ON THE | | GAS RISER. | | EXPLAIN THE ABBREVIATION "POV" AT THE | | METER. | | GAS RISER, BTU LOAD DOES NOT MATCH THE | | GAS LOAD CALCULATION BTU'S | | END OF COMMENTS | | QUESTIONS 561-805-6692 |
|