Plan Review Notes
Plan Review Notes For Permit 04120217
Permit Number 04120217
Review Stop P
Sequence Number 5
Notes
Date Text
2005-12-09 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 FBC 2001 PLUMBING CODEPLAN REVIEW
 FBC 2001 FL ACESSIBILITY CODE PLAN
 REVIEW
 DENIED
 PREVIOUS NOTES DATED 10-01-05 NOT
 ADDRESSED.
  
 4)SHT A-1 WATER RISER, CLARFY USE OF
 WATER HAMMER ARESSTORS OR AIR CHAMBERS.
 REMOVE AIR CHAMBERS FROM DETAIL OR
 PROVIDE DETAILPER STD PDI-WH 201 FOR
 PROPER INSTALLATION.
 SHUT OFF VALVES REQUIRED ON EACH DROP,
 NOT AS SHOWN IN THE MAINS.
 2)SHT A-3 GAS LOAD CALCULATIONS:
 CHANGE CODE REFERENCE FROM 1999 EDITION
 TO 2001 EDITION.
 EXPLAIN THE PURPOSE OF THE VENT ON THE
 GAS RISER.
 EXPLAIN THE ABBREVIATION "POV" AT THE
 METER.
 GAS RISER, BTU LOAD DOES NOT MATCH THE
 GAS LOAD CALCULATION BTU'S
 END OF COMMENTS
 QUESTIONS 561-805-6692