2005-10-01 00:00:00PAUL SCHMITZ PLUMBING & GAS PLAN REVIEW
 FBS 2001 CH 11 FL ACESSSIBILITY CODE
 DENIED
 1) PREVIOUS REVIEW, TWO COMPLETE SETS OF
 MANFACTURE SHEET FOR GAS EQUIPPMENT, AND
 DEAPRTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION, HOTEL DIVISION, WITH EACH
 SET OF PLANS.
 2) PREVIOUS NOTE 1B, SHT A-1.1 EQUIPMENT
 SCHEDULE, ITEM 21 NOT SHOWN ON EQUIPMENT
 PLAN.
 3) SHT A-3 GREASE TRAP DETAIL. UTILITY
 AUTHORITY APPROVAL, NOT NOTED ON PLANS.
 ADDITIONAL COMMENTS
 4)SHT A-1 WATER RISER, CLARFY USE OF
 WATER HAMMER ARESSTORS OR AIR CHAMBERS.
 REMOVE AIR CHAMBERS FROM DETAIL OR
 PROVIDE DETAILPER STD PDI-WH 201 FOR
 PROPER INSTALLATION.
 5)SHT A-3 GAS RISER DOES NOT MATCH
 EQUIPMENT SCHEDULE ON SHT A-1.1
 END OF COMMENTS,
 QUESTIONS 561-805-6692