2005-10-01 00:00:00 | PAUL SCHMITZ PLUMBING & GAS PLAN REVIEW | | FBS 2001 CH 11 FL ACESSSIBILITY CODE | | DENIED | | 1) PREVIOUS REVIEW, TWO COMPLETE SETS OF | | MANFACTURE SHEET FOR GAS EQUIPPMENT, AND | | DEAPRTMENT OF BUSINESS AND PROFESSIONAL | | REGULATION, HOTEL DIVISION, WITH EACH | | SET OF PLANS. | | 2) PREVIOUS NOTE 1B, SHT A-1.1 EQUIPMENT | | SCHEDULE, ITEM 21 NOT SHOWN ON EQUIPMENT | | PLAN. | | 3) SHT A-3 GREASE TRAP DETAIL. UTILITY | | AUTHORITY APPROVAL, NOT NOTED ON PLANS. | | ADDITIONAL COMMENTS | | 4)SHT A-1 WATER RISER, CLARFY USE OF | | WATER HAMMER ARESSTORS OR AIR CHAMBERS. | | REMOVE AIR CHAMBERS FROM DETAIL OR | | PROVIDE DETAILPER STD PDI-WH 201 FOR | | PROPER INSTALLATION. | | 5)SHT A-3 GAS RISER DOES NOT MATCH | | EQUIPMENT SCHEDULE ON SHT A-1.1 | | END OF COMMENTS, | | QUESTIONS 561-805-6692 |
|