Plan Review Notes
Plan Review Notes For Permit 04120217
Permit Number 04120217
Review Stop B
Sequence Number 4
Notes
Date Text
2005-09-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)SEE PREVIOUS LISTS IN REGARDS TO
 OCCUPANCY AND OCCUPANT LOAD.THE INDEX
 SHEET STATES NUMBER OF SEATS AS 44,
 NUMBER OF PEOPLE AS 44 AND 6 EMPLOYEES,
 AND OCCUPANCY COUNTY AS 42, MERCANTILE
 OCCUPANCY.TO BE MERCANTILE IT REQUIRES
 AN OCCUPANT LOAD OF LESS THAN 50, THIS
 OCCUPANT LOAD IS 50 (NOT 42).
  
 3.)TWO MEANS OF EGRESS MAY BE
 REQUIRED.CODE COMPLIANCE CANNOT BE
 DETERMINED WITHOUT REQUESTED
 INFORMATION.
  
 4.)THE KEY PLAN, INDEX SHEET, SHOWS A
 DIFFERENT PARKING CONFIGURATION THAN S1.
 IS ONE EXISTING, THE OTHER PROPOSED?
  
 5.)THE NEW SHEET, S1, SHOWS THE
 ACCESSIBLE ROUTE FROM THE HC PARKING
 SPACE TO THE FRONT DOOR OF THE
 RESTAURANT GOING ACROSS A CURB CUT.
 SHOW COMPLIANCE WITH FBC11-4.3.SHOW
 CROSS SLOPE.
  
 6.)THE USE OF SHUTTERS ON COMMERCIAL
 BUILDINGS REQUIRES APPROVAL BY THE
 BUILDING OFFICIAL.SEE ATTACHED POLICY
 FOR MISSILE IMPACT PROTECTION, ITEM #13.
 SUBMIT AN INSTALLATION PLAN AND
 INSTALLATION SCHEDULE, ATTACHED.
  
 7.)SEE PREVIOUS LISTS, FLORIDA STATE
 OR LOCAL PRODUCT APPROVAL REQUIRED IN
 ADDITION TO THE NOAS PROVIDED.PRODUCT
 APPROVALS NOT APPROVED PRIOR TO PERMIT
 ISSUANCE WILL REQUIRE SEPARATE PERMITS.
  
 8.)SEE PREVIOUS LIST IN REGARDS TO
 INDICATING ON THE PRODUCT APPROVAL WHICH
 PRODUCT YOU ARE USING.
  
 9.)A STATE PRODUCT APPROVAL FOR DOORS
 WAS SUBMITTED BUT DID NOT INDICATE WHICH
 DOOR ON THE PRODUCT APPROVAL WAS TO BE
 INSTALLED.THE EVALUATION REPORT OR
 TEST REPORT AND INSTALLATION
 INSTRUCTIONS ARE REQUIRED AS WELL.
  
 10.)PLEASE CLEARLY INDICATE ALL
 CHANGES TO THE PLAN.FOR EXAMPLE,
 "REROOF" WAS REMOVED FROM INDEX SHEET,
 ITEM #9, BUT IS NOT CLOUDED.
  
 11.)CHANGE OF USE MAY REQUIRE IMPACT
 FEES.561-233-5025
  
 12.)A 4X FEE HAS BEEN CHARGED AS
 REQUIRED BY FS553.80(2)(B).