Date |
Text |
2005-09-03 00:00:00 | ******** UNSAT *********** |
| |
| |
| PLEASE SEE PLANS FROM MAY 2ND, 2005 WERE |
| REDLINED WITH THE "PROVSIO" IF PLANS |
| FAIL FOR ANY OTHER COMMENTS, PLEASE |
| CORRECT AT THAT TIME. PLEASE SEE PLANS |
| HAVE GONE BACK TWICE AND NO CORRECTIONS |
| WERE MADE. ? |
| PLEASE SEE NEW ELECTRICAL SHEETS HAVE |
| COME BACK IN SETS AND NO CORRECTIONS |
| WERE MADE ONCE AGAIN. |
| |
| NEW COMMENT: |
| 1)NOTE: PLEASE SEE ELECTRICAL AND SOME |
| OTHER SHEETS DO NOT CONTAIN ANY TITLE |
| BLOCK INFORMATION FOR THE ENGINEER OF |
| RECORD. |
| PLEASE SEE PLANS CONTAIN A TITLE BLOCK |
| FOR MR JAMES PAINE AND PLANS ARE SIGNED, |
| DATED AND SEALED BY THOMAS TWOMEY?? |
| FAC 61G15-23.002, FS 471.025 |
| |
| PREVIOUS COMMENTS REDLINED. |
| |
| |
| |
| 1)NOTE: PLEASE SEE 210.8B3 UNDER 2002 |
| NEC FOR REQUIRED GFI PROTECTION FOR |
| KITCHEN RECEPTS. |
| |
| 2)NOTE: PLEASE SEE 210.63 FOR ROOFTOP |
| GFI.***ONE LOCATED FOR REAR UNIT.THIS |
| COMMENT IS OK.** |
| |
| 3)NOTE: PLEASE SEE GROUNDING ELECTRODE |
| NOW SHOWN AS #6, PLEASE SEE MIN #2 PER |
| 250.66. |
| NOT CORRECTED. |
| PLEASE BE SURE SEC'S ARE SIZED FOR |
| ADEQUATE FUTURE LOADS. SEC'S RATED FOR |
| 225A'S AND 300A' OF SERVICE IS PROVIDED. |
| 240.4, 31.16, 90.7 |
| |
| 4)NOTE: PLEASE SEE "SIGN CIRCUIT" IS |
| SHOWN ON PANEL SCHEDULE, BUT COULD NOT |
| BE LOCATED ON PLANS? |
| |
| 5)NOTE: PLEASE SEE CIRCUIT SHOWN FOR |
| EXT/EM LT AT FRONT DOOR WHICH SHOWS |
| CIRCUIT TO "A-32"?? PLEASE SEE PANEL "A" |
| IS ONLY SHOWN AS A 30 CIR PANEL. |
| PLEASE CORRELATE AND PLEASE SEE 700.12E, |
| LOCAL BRANCH CIRCUIT FEEDING EXT/EM LTS. |
| |
| 6)NOTE: PLEASE SEE FIRE REVIEWS PREVIOUS |
| REVIEW WHICH REQUIRED AN ADDITIONAL EM |
| LT IN KITCHEN. |
| |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STMAPING. |
| |
| PLEASE ALSO SEE NOC HAS EXPIRED PER FS |
| 713.13 IF WORK HAS NOT COMMENCED WITIN |
| 90 DAYS, NOC EXPIRES. |
| |
| PLEASE SUBMIT THE ABOVE CORRECTIONS FOR |
| REVIEW BEFORE ROUGH ELECTRICAL |
| INSPECTION. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |