2005-05-30 00:00:00DENIED:
 PLAN SHEET A-4.0 IS NOT SIGNED, SEALED
 AND DATED BY THE ARCHITECT/ENGINEER AS
 REQUIRED BY FS 481 & 471 RESPECTIVELY.
  
 PROVISO:
 GREASE HOOD EXHAUST TERMINATION SHALL
 COMPLY WITH 2001 FBC/M 506.3.14.1 &
 506.3.14.3.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 HOOD SUPPRESSION AND WALK-IN COOLERS.
 PROVIDE PLANS AND MANUFACTURER'S
 SUBMITTAL DATA WITH PERMIT APPLICATIONS.
  
 FAN SHUTDOWN REQUIRED FOR FINAL
 INSPECTION.
  