Plan Review Notes For Permit 04120217 |
Permit Number |
04120217 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-05-02 00:00:00 | ********* NOTES REDLINED ********* | | | | PLEASE SEE FIRST REVIEW AND ALSO NEW | | COMMENT DUE TO INFORMATION GIVEN FOR | | GROUNDING ELECTRODE SYSTEM. | | | | 1)NOTE: PLEASE SEE 210.8B3 UNDER 2002 | | NEC FOR REQUIRED GFI PROTECTION FOR | | KITCHEN RECEPTS. | | | | 2)NOTE: PLEASE SEE 210.63 FOR ROOFTOP | | GFI. | | | | 3)NOTE: PLEASE SEE GROUNDING ELECTRODE | | NOW SHOWN AS #6, PLEASE SEE MIN #2 PER | | 250.66. | | | | THESE ITEMS WERE REDLINED ON PLANS AS A | | "PROVISO" IF PLANS FAIL FOR ANY OTHER | | TRADES, PLEASE MAKE THE ABOVE | | CORRECTIONS AT THAT TIME BEFORE PERMIT | | IS ISSED. | | | | PLEASE ALSO SEE NOC HAS EXPIRED PER FS | | 713.13 IF WORK HAS NOT COMMENCED WITIN | | 90 DAYS, NOC EXPIRES. | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS FOR | | REVIEW BEFORE ROUGH ELECTRICAL | | INSPECTION. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|