Plan Review Notes
Plan Review Notes For Permit 04120217
Permit Number 04120217
Review Stop B
Sequence Number 2
Notes
Date Text
2005-05-13 00:00:00SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC IS
 EXPIRED; OVER 90 DAYS WITHOUT COMMENCING
 WORK, FS713.13.THE NOC IS FOR A
 DIFFERENT LOT THAN REFERENCED ON YOUR
 PERMIT APPLICATION.TWO DIFFERENT
 PARCEL ID NUMBERS ARE ON THE NOC.
  
 2.)TO EXPEDITE PLAN REVIEW, ALL
 CHANGES SHOULD BE CLOUDED WITH OLD
 SHEETS SUBMITTED SEPARATELY.NO CHANGES
 ARE INDICATED AND THE OLD SHEETS ARE NOT
 IN THE PACKAGE.
  
 3.)SEE THE PREVIOUS LIST, ITEM #1.
 RESTAURANT IS A OCCUPANCY (WAS M FOR
 FIRST REVIEW, NOW IS B ON THE INDEX
 SHEET).FBC304.
  
 4.)SEE THE PREVIOUS LIST, ITEM #2.
 THE TOTAL OCCUPANT LOAD CANNOT BE LESS
 THAN SPECIFIED IN FBC TABLE 1003.1 AS
 PER FBC1003.1.1.YOU CAN STATE THE
 OCCUPANCY FOR THE FIXED SEATING AREA BUT
 THE REMAINING AREA MUST BE CALCULATED
 AND OCCUPANCY PER FBC TABLE 1003.1 IS TO
 BE APPLIED.
  
 5.)INDEX SHEET, ITEM #9 STATES ?REROOF
 BUILDING?.THIS WILL NOT BE INCLUDED IN
 THIS REVIEW UNLESS PRODUCT APPROVALS ARE
 SUBMITTED.
  
 6.)THE DUPLICATE APPLICATION IS
 INCOMPLETE.INCLUDE THE PARCEL ID AS
 REQUIRED BY FLORIDA STATUTE.
  
 7.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
  
 8.)INDEX SHEET DECLARES TYPE IV
 CONSTRUCTION.A1 SHOWS EXISTING 2X10S
 WHICH APPEAR TO BE ROOF JOISTS.TYPE IV
 REQUIRES NONCOMBUSTIBLE ROOF.
  
 9.)SEE PREVIOUS LIST, SHOW COMPLIANCE
 FOR THE ADA PARKING SPACE.SEE ATTACHED
 DETAIL.
  
 10.) A MINIMUM OF TWO INDEPENDENT EXITS
 REQUIRED, FBC1004.2, IN ACCORDANCE WITH
 FBC1004.1.4.
  
 11.)PRODUCT APPROVALS REQUIRED:
 ROOF
 EXTERIOR DOORS
 SHUTTERS
 WINDOWS
  
 ANY PRODUCT APPROVALS NOT SUBMITTED AND
 REVIEWED PRIOR TO ISSUANCE WILL REQUIRE
 SEPARATE PERMITS FOR THOSE ITEMS.
  
 VARIOUS PRODUCT APPROVALS WERE
 SUBMITTED.THE NOAS DID NOT HAVE A
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 AND THE FLORIDA STATE PRODUCT APPROVAL
 DID NOT HAVE A TEST REPORT/INSTALLATION
 INSTRUCTIONS ATTACHED AS PREVIOUSLY
 REQUESTED.
  
 12.)SHEET A1 STATES ?RECONDITION
 WINDOWS?,APPLICATION STATES INSTALLING
 NEW WINDOWS.
  
 13.)THE PLANS STATES ?ACOUSTICAL
 CEILING, SEE PLAN?.WHAT PLAN?
  
 14.)SHOW MANEUVERING CLEARANCE FOR
 DOORS #2 AND #3, FBC11 FIGURE 25.
  
 15.)THE FIRE EXTINGUISHER APPEARS TO
 BE IN THE MANEUVERING CLEARANCE REQUIRED
 FOR DOOR #1, FBC11 FIGURE 25.
  
 16.)PROVIDE A DIMENSION FOR THE GRAB
 BAR BEHIND THE TOILET.NONE OF THE GRAB
 BARS SHOWN HAVE AN ACTUAL DIMENSION AND
 ARE SHOWN GRAPHICALLY AS SMALLER THAN
 THE 36 IN MINIMUM REQUIRED.THE FLOOR
 PLAN GRAPHIC IS IN CONFLICT WITH YOUR
 FIGURE 29.
  
 17.)THE APPLICATION INDICATES THAT
 DRYWALL WILL BE INSTALLED.ON ALL
 EXTERIOR WALLS? SCOPE OF WORK NOT CLEAR.
 INSULATION REQUIRED, FBC13-402.
  
 18.)SEE ATTACHED FS553.
  