2005-05-13 00:00:00 | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| 1.) A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED.THE NOC IS |
| EXPIRED; OVER 90 DAYS WITHOUT COMMENCING |
| WORK, FS713.13.THE NOC IS FOR A |
| DIFFERENT LOT THAN REFERENCED ON YOUR |
| PERMIT APPLICATION.TWO DIFFERENT |
| PARCEL ID NUMBERS ARE ON THE NOC. |
| |
| 2.)TO EXPEDITE PLAN REVIEW, ALL |
| CHANGES SHOULD BE CLOUDED WITH OLD |
| SHEETS SUBMITTED SEPARATELY.NO CHANGES |
| ARE INDICATED AND THE OLD SHEETS ARE NOT |
| IN THE PACKAGE. |
| |
| 3.)SEE THE PREVIOUS LIST, ITEM #1. |
| RESTAURANT IS A OCCUPANCY (WAS M FOR |
| FIRST REVIEW, NOW IS B ON THE INDEX |
| SHEET).FBC304. |
| |
| 4.)SEE THE PREVIOUS LIST, ITEM #2. |
| THE TOTAL OCCUPANT LOAD CANNOT BE LESS |
| THAN SPECIFIED IN FBC TABLE 1003.1 AS |
| PER FBC1003.1.1.YOU CAN STATE THE |
| OCCUPANCY FOR THE FIXED SEATING AREA BUT |
| THE REMAINING AREA MUST BE CALCULATED |
| AND OCCUPANCY PER FBC TABLE 1003.1 IS TO |
| BE APPLIED. |
| |
| 5.)INDEX SHEET, ITEM #9 STATES ?REROOF |
| BUILDING?.THIS WILL NOT BE INCLUDED IN |
| THIS REVIEW UNLESS PRODUCT APPROVALS ARE |
| SUBMITTED. |
| |
| 6.)THE DUPLICATE APPLICATION IS |
| INCOMPLETE.INCLUDE THE PARCEL ID AS |
| REQUIRED BY FLORIDA STATUTE. |
| |
| 7.)PROVIDE A SURVEY FOR THIS PROPERTY. |
| |
| |
| 8.)INDEX SHEET DECLARES TYPE IV |
| CONSTRUCTION.A1 SHOWS EXISTING 2X10S |
| WHICH APPEAR TO BE ROOF JOISTS.TYPE IV |
| REQUIRES NONCOMBUSTIBLE ROOF. |
| |
| 9.)SEE PREVIOUS LIST, SHOW COMPLIANCE |
| FOR THE ADA PARKING SPACE.SEE ATTACHED |
| DETAIL. |
| |
| 10.) A MINIMUM OF TWO INDEPENDENT EXITS |
| REQUIRED, FBC1004.2, IN ACCORDANCE WITH |
| FBC1004.1.4. |
| |
| 11.)PRODUCT APPROVALS REQUIRED: |
| ROOF |
| EXTERIOR DOORS |
| SHUTTERS |
| WINDOWS |
| |
| ANY PRODUCT APPROVALS NOT SUBMITTED AND |
| REVIEWED PRIOR TO ISSUANCE WILL REQUIRE |
| SEPARATE PERMITS FOR THOSE ITEMS. |
| |
| VARIOUS PRODUCT APPROVALS WERE |
| SUBMITTED.THE NOAS DID NOT HAVE A |
| FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| AND THE FLORIDA STATE PRODUCT APPROVAL |
| DID NOT HAVE A TEST REPORT/INSTALLATION |
| INSTRUCTIONS ATTACHED AS PREVIOUSLY |
| REQUESTED. |
| |
| 12.)SHEET A1 STATES ?RECONDITION |
| WINDOWS?,APPLICATION STATES INSTALLING |
| NEW WINDOWS. |
| |
| 13.)THE PLANS STATES ?ACOUSTICAL |
| CEILING, SEE PLAN?.WHAT PLAN? |
| |
| 14.)SHOW MANEUVERING CLEARANCE FOR |
| DOORS #2 AND #3, FBC11 FIGURE 25. |
| |
| 15.)THE FIRE EXTINGUISHER APPEARS TO |
| BE IN THE MANEUVERING CLEARANCE REQUIRED |
| FOR DOOR #1, FBC11 FIGURE 25. |
| |
| 16.)PROVIDE A DIMENSION FOR THE GRAB |
| BAR BEHIND THE TOILET.NONE OF THE GRAB |
| BARS SHOWN HAVE AN ACTUAL DIMENSION AND |
| ARE SHOWN GRAPHICALLY AS SMALLER THAN |
| THE 36 IN MINIMUM REQUIRED.THE FLOOR |
| PLAN GRAPHIC IS IN CONFLICT WITH YOUR |
| FIGURE 29. |
| |
| 17.)THE APPLICATION INDICATES THAT |
| DRYWALL WILL BE INSTALLED.ON ALL |
| EXTERIOR WALLS? SCOPE OF WORK NOT CLEAR. |
| INSULATION REQUIRED, FBC13-402. |
| |
| 18.)SEE ATTACHED FS553. |
| |