2005-01-07 00:00:00 | DENIED; |
| 1.GREASE TRAPSARE REQUIRED TO HAVE |
| UTILITY DEPARTMENT APPROVAL. PLEASE |
| CONTACT RODNEY COMPO AT 561-837-4074. |
| 2.MANUFACTOR'S SPECIFICATIONS ARE |
| REQUIRED FOR GREASE TRAP (WADE #5120. |
| 3.THREE COMPARTMENT SINK TO DUMP INTO A |
| FLOOR SINK WITH AN AIR GAP NOT SHOWN ON |
| FLAT DRAWING. |
| 4.FLOOR DRAINS NOT PERMITED IN WALKIN |
| COOLERS. |
| 5.PLANS TO BE APPROVEDBY THE DEPARTMENT |
| OF HOTEL AND RESTAURANT, BEFOREREVIEW BY |
| THE CITY OF WEST PALM BEACH. |
| 6.HAND SINK REQUIRED IN FOOD PREP AREA. |
| 7.MOP SINK,AND FLOORDRAINS IN KICHEN AND |
| PREP AREA ARE REQUIRED TO GO TO GREASE |
| TRAP. |
| 8.PLEASE SHOW A DETAIL OF BATHROOM SHOW |
| ALL MESUREMENTS TO COMPLY WITH FHC |
| CHAPTER 11. TOILET, LAV, GRAB BARS, |
| ETC. |
| GAS |
| 1.SHOW ALL CUT SECTIONS OF PIPE AND |
| CORRESPONDING LENTHS OER. FBC 2001 FUEL |
| GAS. |
| 2.SHOW BTU'S LOAD OF EACH APPLIANCE. |
| (MISSING BTU'S FOR STEAM TABLE) AND |
| TOTAL BTU'S AND TOTAL LENTH ( LONGEST |
| RUN) |
| 3.SHUTOFF VALVES TO BE ACCESSABLE. |
| 4.A UNION IS REQUIRED ON THE DOWN STREAM |
| SIDE OF THE ENSUL VALVE FOR SERVICE. |
| 5.INDICATE THE DELIVERY PRESSURE PER. |
| FBC FUEL GAS 402.2. SPECIFY .5 OR 2 |
| PSI. |
| 6.SUBMIT MANUFACTURES SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDERDS FUEL GAS SEC. 402.2. |
| 7.PLEASE USE GAS SIZING CHARTS CHAPTER 4 |
| OF THE FBC FUEL GAS AND NOTE ON PLANS |
| WHAT TABLE WAS USED. |
| PLUMBING PLAN REVIEW BY; |
| |
| JOHN LEECH |
| |
| 805-6695 |