Date Text
2005-01-07 00:00:00DENIED:
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS PER 2001 FBC(M)TABLE
 403.3.
  
 2.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION, GAS AND WALK-IN
 COOLERS.PLEASE PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS WITH PERMIT
 APPLICATION.
  
 3.PLEASE INDICATE CLEARANCE BETWEEN
 GREASE DUCT TERMINATION IN RELATION TO
 THE LOT LINES, ADJACENT PROPERTY LINES
 CONTINGUOUS BUILDINGS AND FRESH AIR
 INTAKES.
  
 4.INDICATE LOCATION OF CONDENSORS FOR
 THE COOLERS/FREEZERS.CONDENSORS
 LOCATED ON THE ROOF SHALL COMPLY WITH
 2001 FBC TABLE 1511.7 FOR PROPER
 CLEARANCE BETWEEN THE ROOF SURFACE AND
 THE BOTTOMOF THE SUPPORT RAILING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.