Notes
Date Text
2004-12-27 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 215.5
  
 2)NOTE: PLEASE SHOW SEC'S ON RISER PER
 310.16, 240.4B. NONE LOCATED ON RISER.
 215.5
  
 3)NOTE: PLEASE SEE 250.50 FOR GROUNDING
 ELECTRODE SYSTEM. PLEASE SEE 250.104
 FOR METALPIPING SYSTEMS.
  
 4)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/EXT LTS ON LOCAL BRANCH
 CIRCUIT.
  
 5)NOTE: PLEASE SEE 210.62 FOR REQUIRED
 SHOW/DISPLAY WINDOW RECEPTS REQUIRED.
 PLEASE ALSO SEE 220.12A
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED DIRECTLY ABOVE A SHOW WINDOW
 FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR
 FRACTION THEREOF OF SHOW WINDOW AREA
 MEASURED HORIZONTALLY AT ITS MAXIMUM
 WIDTH.
 FOR SHOW-WINDOW LIGHTING, A LOAD OF NOT
 LESS THAN 660 VOLT-AMPERES/LINEAR METER
 OR 200 VOLT-AMPERES/LINEAR FOOT SHALL BE
 INCLUDED FOR A SHOW WINDOW, MEASURED
 HORIZONTALLY ALONG ITS BASE.
  
 6)NOTE: PLEASE SEE PANEL LOCATION ON
 PLANS DO NOT SEEM TO MEET 110.26 FOR
 CLEARENCE REQUIREMENTS.
 PLEASE ALSO SHOW LOCATION OF SERVICE ON
 PLANS.
  
 7)NOTE: PLEASE CORRELATE A/C SYSTEMS ON
 MECH PLANS WITH ELECTRICAL PLANS. ONE
 SHOWS 5KW, THE OTHER 10KW??
 215.5
  
 8)NOTE: PLEASE SEE 600.5
 EACH COMMERCIAL BUILDING AND EACH
 COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT
 LEAST ONE OUTLET IN AN ACCESSIBLE
 LOCATION AT EACH ENTRANCE TO EACH TENANT
 SPACE FOR SIGN OR OUTLINE LIGHTING
 SYSTEM USE. THE OUTLET(S) SHALL BE
 SUPPLIED BY A BRANCH CIRCUIT RATED AT
 LEAST 20 AMPERES THAT SUPPLIES NO OTHER
 LOAD.
  
 9)NOTE: PLEASE SEE 2002 NEC FOR GFI
 PROTECTION OF RECEPTS IN KITCHENS OTHER
 THAN DWELLING UNITS. 210.8B3
  
 10 )NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.3,230.42
  
 11)NOTE: PLEASE PROVIDE NOTE ON
 ELECTRICAL PLANS FOR SHUT-DOWN OF ALL
 ELECTRICAL EQUIPMENT UNDER HOOD.
 NFPA-96
  
 12)NOTE: PLEASE INCLUDE SIZE OF
 EQUIPMENT GROUNDING CONDUCTOR FROM MAINS
 TO PANELS. SIZE PER 250.122
  
 13)NOTE: PLEASE INDICATE GFI RECEPT
 REQUIRED AT ROOFTOP LOCATION PERE
 210.63
  
 14)NOTE: NOTE: PLEASE SUBMIT AIC RATINGS
 FOR ALL NEW SERVICE EQUIPMENT BEING
 INSTALL- ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT. PER 110.9/215.5
 PROVIDE RATINGS/TYPE FUSE FOR MAINS.
  
 PLEASE SEE POSSIBLE REVIEW COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW SHEETS INTO TWO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW