2004-12-27 00:00:00 | ************* UNSAT *************** |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH THE SUBMITTED |
| PANEL SCHEDULE. |
| 215.5 |
| |
| 2)NOTE: PLEASE SHOW SEC'S ON RISER PER |
| 310.16, 240.4B. NONE LOCATED ON RISER. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE 250.50 FOR GROUNDING |
| ELECTRODE SYSTEM. PLEASE SEE 250.104 |
| FOR METALPIPING SYSTEMS. |
| |
| 4)NOTE: PLEASE SEE 700.12E FOR |
| CIRCUITING OF EM/EXT LTS ON LOCAL BRANCH |
| CIRCUIT. |
| |
| 5)NOTE: PLEASE SEE 210.62 FOR REQUIRED |
| SHOW/DISPLAY WINDOW RECEPTS REQUIRED. |
| PLEASE ALSO SEE 220.12A |
| AT LEAST ONE RECEPTACLE OUTLET SHALL BE |
| INSTALLED DIRECTLY ABOVE A SHOW WINDOW |
| FOR EACH 3.7 LINEAR M (12 FT) OR MAJOR |
| FRACTION THEREOF OF SHOW WINDOW AREA |
| MEASURED HORIZONTALLY AT ITS MAXIMUM |
| WIDTH. |
| FOR SHOW-WINDOW LIGHTING, A LOAD OF NOT |
| LESS THAN 660 VOLT-AMPERES/LINEAR METER |
| OR 200 VOLT-AMPERES/LINEAR FOOT SHALL BE |
| INCLUDED FOR A SHOW WINDOW, MEASURED |
| HORIZONTALLY ALONG ITS BASE. |
| |
| 6)NOTE: PLEASE SEE PANEL LOCATION ON |
| PLANS DO NOT SEEM TO MEET 110.26 FOR |
| CLEARENCE REQUIREMENTS. |
| PLEASE ALSO SHOW LOCATION OF SERVICE ON |
| PLANS. |
| |
| 7)NOTE: PLEASE CORRELATE A/C SYSTEMS ON |
| MECH PLANS WITH ELECTRICAL PLANS. ONE |
| SHOWS 5KW, THE OTHER 10KW?? |
| 215.5 |
| |
| 8)NOTE: PLEASE SEE 600.5 |
| EACH COMMERCIAL BUILDING AND EACH |
| COMMERCIAL OCCUPANCY ACCESSIBLE TO |
| PEDESTRIANS SHALL BE PROVIDED WITH AT |
| LEAST ONE OUTLET IN AN ACCESSIBLE |
| LOCATION AT EACH ENTRANCE TO EACH TENANT |
| SPACE FOR SIGN OR OUTLINE LIGHTING |
| SYSTEM USE. THE OUTLET(S) SHALL BE |
| SUPPLIED BY A BRANCH CIRCUIT RATED AT |
| LEAST 20 AMPERES THAT SUPPLIES NO OTHER |
| LOAD. |
| |
| 9)NOTE: PLEASE SEE 2002 NEC FOR GFI |
| PROTECTION OF RECEPTS IN KITCHENS OTHER |
| THAN DWELLING UNITS. 210.8B3 |
| |
| 10 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 11)NOTE: PLEASE PROVIDE NOTE ON |
| ELECTRICAL PLANS FOR SHUT-DOWN OF ALL |
| ELECTRICAL EQUIPMENT UNDER HOOD. |
| NFPA-96 |
| |
| 12)NOTE: PLEASE INCLUDE SIZE OF |
| EQUIPMENT GROUNDING CONDUCTOR FROM MAINS |
| TO PANELS. SIZE PER 250.122 |
| |
| 13)NOTE: PLEASE INDICATE GFI RECEPT |
| REQUIRED AT ROOFTOP LOCATION PERE |
| 210.63 |
| |
| 14)NOTE: NOTE: PLEASE SUBMIT AIC RATINGS |
| FOR ALL NEW SERVICE EQUIPMENT BEING |
| INSTALL- ED. MAINS/BRKRS AND PANELS ARE |
| ALL TO BE RATED FOR THE AVAILABLE FAULT |
| CURRENT. PER 110.9/215.5 |
| PROVIDE RATINGS/TYPE FUSE FOR MAINS. |
| |
| PLEASE SEE POSSIBLE REVIEW COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE AN |
| AFFECT ON ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW SHEETS INTO TWO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |