Text |
2004-12-03 00:00:00 | ************ UNSAT ************** |
| |
| 1)NOTE: PLEASE SEE ALL LIGHTING SHOWN |
| ON |
| ONE CIRCUIT. PLEASE VERIFY. |
| FIXTURES ARE SHOWN AS 2X4 LAY-IN TYPE |
| BUT NO INFORMATION ON 3-LT, 4LT, 34W, |
| 40W TYPE. |
| PLEASE ALSO SEE RECESSED LTS/EM/ EXT |
| LTS |
| ARE ALSO ON SAME CIRCUIT? |
| |
| 2)NOTE: PLEASE VERIFY NEW OR EXSITING |
| SIGN CIRCUIT PER 600.5 PLEASE SEE EACH |
| COMMERCIAL BUILDING AND EACH COMMERCIAL |
| OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE |
| OUTLET IN AN ACCESSIBLE LOCATION AT |
| EACH |
| ENTRANCE TO EACH TENANT SPACE FOR SIGN |
| OR OUTLINE LIGHTING SYSTEM USE. THE |
| OUTLET(S) SHALL BE SUPPLIED BY A BRANCH |
| CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. |
| |
| 3)NOTE: PLEASE VERIFY LOAD AND OCP FOR |
| AHU/HEAT. MECH PLANS INDICATE 45A FOR |
| 10KW OF HEAT. PLEASE SEE 424.3B FOR MIN |
| OCP. THE AMPACITY OF THE BRANCH-CIRCUIT |
| CONDUCTORS AND THE RATING OR SETTING OF |
| OVERCURRENT PROTECTIVE DEVICES |
| SUPPLYING |
| FIXED ELECTRIC SPACE-HEATING EQUIPMENT |
| CONSISTING OF RESISTANCE ELEMENTS WITH |
| OR WITHOUT A MOTOR SHALL NOT BE LESS |
| THAN 125 PERCENT OF THE TOTAL LOAD OF |
| THE MOTORS AND THE HEATERS. THE RATING |
| OR SETTING OF OVERCURRENT PROTECTIVE |
| DEVICES SHALL BE PERMITTED IN |
| ACCORDANCE |
| WITH 240.4(B). |
| OCP SHOWN FOR DISC INDICATES XX? |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET/COPY OF OLD SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |